Plan Review Notes
Plan Review Notes For Permit 14090746
Permit Number 14090746
Review Stop E
Sequence Number 1
Notes
Date Text
2014-09-23 09:17:54B12
  
  
2014-09-23 09:17:23DATE: 9/23/2014
 PROJECT: DXL
 PERMIT#: 14070136
 CODE: 2008 EDITION OF THE NEC
 2010 EDITION OF THE FBC
 2010 WPB AMENDMENTS TO THE FBC, CHAPTER 1,
 ADMINISTRATION, 2012 FBC SUPPLEMENTS.
  
 1ST ELECTRICAL REVISION PLAN REVIEW
 ACTION: PROVISO
  
 1) RISER ON REVISION INDICATES A 150AMP MAIN BREAKER IN
 PANEL B ON THE SECONDARY SIDE OF THE NEW 75KVA
 TRANSFORMER. THE PANEL SCHEDULE INDICATE S A 225AMP MLO
 PANEL IN PANEL B. REVISE PLANS FOR CLARIFICATION.
  
 2) NEC 210.4(B) EACH MULTIWIRE BRANCH CIRCUIT SHALL BE
 PROVIDED WITH A MEANS THAT WILL SIMULTANEOUSLY
 DISCONNECT ALL UNGROUNDED CONDUCTORS AT THE POINT WHERE
 THE BRANCH CIRCUIT ORIGINATES.
  
 DAVID HAYES, ELECTRICAL PLANS EXAMINER, PX3421,
 561-805-6717 OR [email protected]
  