Plan Review Notes
Plan Review Notes For Permit 14090741
Permit Number 14090741
Review Stop B
Sequence Number 2
Notes
Date Text
2014-12-09 12:23:13****CORRECTIONS****
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 1. SEE FIRE PROVISO; 90 MINUTE DOORS REQUIRED. ALSO SEE
 FBC 909.20. IT APPEARS THAT THE EXITING STRATEGY FOR
 THIS HIGH RISE BUILDING WAS THE USE OF A SMOKEPROOF
 ENCLOSURE (CORRIDOR WITH A 2 HOUR WALL SEPARATION TO
 THE OPEN EXTERIOR BALCONY, ENCLOSED STAIR). THE
 SMOKEPROOF ENCLOSURE DOOR IS TO BE 1 1/2 HOUR RATED.
  
 PROVIDE DOCUMENTATION TO SHOW THAT THE DOORS PROPOSED
 COMPLY WITH THE FIRE RESISTANCE RATING REQUIRED.
  
  