Plan Review Notes For Permit 14090741 |
Permit Number |
14090741 |
|
Review Stop |
B |
Sequence Number |
2 |
|
Notes |
Date |
Text |
2014-12-09 12:23:13 | ****CORRECTIONS**** | | | | SAMANTHA HILL | | BUILDING PLANS EXAMINER | | [email protected] | | 561-805-6724 | | | | 1. SEE FIRE PROVISO; 90 MINUTE DOORS REQUIRED. ALSO SEE | | FBC 909.20. IT APPEARS THAT THE EXITING STRATEGY FOR | | THIS HIGH RISE BUILDING WAS THE USE OF A SMOKEPROOF | | ENCLOSURE (CORRIDOR WITH A 2 HOUR WALL SEPARATION TO | | THE OPEN EXTERIOR BALCONY, ENCLOSED STAIR). THE | | SMOKEPROOF ENCLOSURE DOOR IS TO BE 1 1/2 HOUR RATED. | | | | PROVIDE DOCUMENTATION TO SHOW THAT THE DOORS PROPOSED | | COMPLY WITH THE FIRE RESISTANCE RATING REQUIRED. | | | | |
|