Plan Review Notes
Plan Review Notes For Permit 14090734
Permit Number 14090734
Review Stop E
Sequence Number 2
Notes
Date Text
2014-10-27 07:14:2710/27/2014
 PROJECT: THE ALCHEMIST SIGN
 PERMIT#: 14090734
 CODE: 2008 EDITION OF THE NEC, 2010 EDITION OF THE FBC
 ,2010 WPB AMENDMENTS TO THE FBC, CHAPTER 1,
 ADMINISTRATION, 2012 FBC SUPPLEMENTS.
 2ND ELECTRICAL PLAN REVIEW
 ACTION: PASS WITH EXCEPTION.
  
 1) PLEASE PROVIDE THE FOLLOWING FOR VERIFICATION BY
 ELECTRICAL INSPECTOR IN THE FIELD.
 A) FBC-E 505.2.4
 ALL EXTERIOR LIGHTING NOT EXEMPTED BY FBC 505.1 SHALL
 HAVE AUTOMATIC CONTROLS TO TURN OFF AT DAYLIGHT OR WHEN
 NOT REQUIRED. CONTROLS SHALL BE PHOTOSENSOR & TIME
 CLOCK OR ASTRONOMICAL TIME SWITCH. ALL TIME SWITCHES
 SHALL BE CAPABLE OF RETAINING PROGRAMING DURING A LOSS
 OF POWER FOR A MINIMUM OF 10 HOURS.
 B) NEC 600.3
 ELECTRIC SIGNS, SECTION SIGNS, AND OUTLINE LIGHTING ?
 FIXED, MOBILE, OR PORTABLE ? SHALL BE LISTED AND
 INSTALLED IN CONFORMANCE WITH THAT LISTING, UNLESS
 OTHERWISE APPROVED BY SPECIAL PERMISSION.
 C) NEC 110.3(B)
 LISTED OR LABELED EQUIPMENT SHALL BE INSTALLED AND USED
 IN ACCORDANCE WITH ANY INSTRUCTIONS INCLUDED IN THE
 LISTING OR LABELING.
 D) NEC 600.5
 EACH COMMERCIAL OCCUPANCY ACCESSIBLE TO PEDESTRIANS
 SHALL BE PROVIDED WITH AT LEAST ONE OUTLET SUPPLIED BY
 A BRANCH CIRCUIT RATED AT LEAST 20 AMPERES THAT
 SUPPLIES NO OTHER LOAD.
  
 DAVID HAYES, ELECTRICAL PLANS EXAMINER, PX3421,
 561-805-6717 OR [email protected]
  