2014-10-02 14:13:18BUILDING PLAN REVIEW
 PERMIT:14090715
 ADD:325 EUCALYPTUS STREET
 CONT: KAST
 TEL: (561) 689-2910
  
 2010 FLORIDA BUILDING CODE W
 * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION
 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013.
  
 2010 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: THURS. OCT. 02/2014
 ACTION: DENIED
  
 1) THE PERMIT APPLICATION INDICATES THE TEMPORARY
 CONSTRUCTION TRAILERS ARE TEMPORARY, THAT MEANS 180
 DAYS OR LESS BY DEFINITON. PLEASE PROVIDE THE DATE THEY
 WILL BE INSTALLED AND THE DATE THEY WILL BE REMOVED.
 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING
 CODE,
 CHAPTER 1, ADMINISTRATION, 2010 108.1 GENERAL. THE
 BUILDING OFFICIAL IS AUTHORIZED TO ISSUE A PERMIT FOR
 TEMPORARY STRUCTURES AND TEMPORARY USES. SUCH PERMITS
 SHALL BE LIMITED AS TO TIME OF SERVICE, BUT SHALL NOT
 BE PERMITTED FOR MORE THAN 6MONTHS. THE BUILDING
 OFFICIAL IS AUTHORIZED TO GRANT EXTENSIONS FOR
 DEMONSTRATED CAUSE.
  
 2) SHEET 1 OF 4 FROM THE STATE APPROVED PLANS INDICATE
 IN NOTE # 2 THEY WILL NEED TO PROVIDE STAIR, RAMP,
 LANDINGS, DECKS AND GAURDRAIL DETAILS, THEY ARE NOT
 INCLUDED IN THE STATE APPROVED PLANS.
 2A) 1009.6 STAIRWAY CONSTRUCTION. ALL STAIRWAYS SHALL
 BE BUILT OF MATERIALS CONSISTENT WITH THE TYPES
 PERMITTED FOR THE TYPE OF CONSTRUCTION OF THE BUILDING,
 EXCEPT THAT WOOD HANDRAILS SHALL BE PERMITTED FOR ALL
 TYPES OF CONSTRUCTION.
 2B) STAIR, RAMPS, LANDINGS & DECKS ARE TO BE DESIGN TO
 TABLE 1607 LIVE LOADS.
 2C) 1010.2 SLOPE. RAMPS USED AS PART OF A MEANS OF
 EGRESS SHALL HAVE A RUNNING SLOPE NOT STEEPER THAN ONE
 UNIT VERTICAL IN 12 UNITS HORIZONTAL (8.333-PERCENT
 SLOPE). THE SLOPE OF OTHER PEDESTRIAN RAMPS SHALL NOT
 BE STEEPER THAN ONE UNIT VERTICAL IN EIGHT UNITS
 HORIZONTAL (12.5-PERCENT SLOPE). ACC CODE 405,
 HANDRAILS 1012 & GUARDRAILS 1013.
  
 3) PROVIDE A SITE PLAN AND SHOW THE ACCESSIBLE ROUTE TO
 THE MANUFACTURERD BUILDINGS FROM THE ACCESSIBLE PARKINS
 SPOT AND ACCESS AISLE.
 2010 FBC- ACCESS 502.1.
  
 4) SHEET 1 OF 4 FROM THE STATE APPROVED PLANS INDICATE
 IN NOTE # 14 SITE INSTALLED ITEM GUTTERS. 1503.7
 PROTECTION AGAINST DECAY AND TERMITES.
 CONDENSATE LINES AND ROOF DOWNSPOUTS SHALL DISCHARGE AT
 LEAST 1 FOOT (305 MM) AWAY FROM THE STRUCTURE SIDEWALL,
 WHETHER BY UNDERGROUND PIPING, TAIL EXTENSIONS, OR
 SPLASH BLOCKS. GUTTERS WITH DOWNSPOUTS ARE REQUIRED ON
 ALL BUILDINGS WITH EAVES OF LESS THAN 6 INCHES (152 MM)
 HORIZONTAL PROJECTION EXCEPT FOR GABLE END RAKES OR ON
 A ROOF ABOVE ANOTHER ROOF.
  
 5) SHEET 1 OF 4 FROM THE STATE APPROVED PLANS INDICATE
 IN NOTE # 16 STORM SHUTTERS. 2010 FBC-B 1609.1.2
 PROTECTION OF OPENINGS, 1609.6.4.41 COMPONENTS &
 CLADDING
 FLORIDA DEPARTMENT OF COMMUNITY AFFAIRS RULE 9N-3 NOV.
 01/ 2010 (31) SUB-CATEGORY OF PRODUCTS OR CONSTRUCTION
 SYSTEMS THAT WILL REQUIRE PRODUCT APPROVALS:
 (31)((E) SHUTTERS.
  
 6) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION
 & REMOVE & REPLACE ANY PAGES AS NECESSARY. A
 TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW COMMENT
 NUMBER, WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE THE
 CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR PERMIT.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  