2014-10-02 14:13:18 | BUILDING PLAN REVIEW |
| PERMIT:14090715 |
| ADD:325 EUCALYPTUS STREET |
| CONT: KAST |
| TEL: (561) 689-2910 |
| |
| 2010 FLORIDA BUILDING CODE W |
| * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA |
| BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION |
| 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013. |
| |
| 2010 EXISTING BUILDING CODE LEVEL II 701.3 |
| COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, |
| SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS |
| OF THE FLORIDA BUILDING CODE, BUILDING. |
| |
| 1ST REVIEW |
| DATE: THURS. OCT. 02/2014 |
| ACTION: DENIED |
| |
| 1) THE PERMIT APPLICATION INDICATES THE TEMPORARY |
| CONSTRUCTION TRAILERS ARE TEMPORARY, THAT MEANS 180 |
| DAYS OR LESS BY DEFINITON. PLEASE PROVIDE THE DATE THEY |
| WILL BE INSTALLED AND THE DATE THEY WILL BE REMOVED. |
| 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING |
| CODE, |
| CHAPTER 1, ADMINISTRATION, 2010 108.1 GENERAL. THE |
| BUILDING OFFICIAL IS AUTHORIZED TO ISSUE A PERMIT FOR |
| TEMPORARY STRUCTURES AND TEMPORARY USES. SUCH PERMITS |
| SHALL BE LIMITED AS TO TIME OF SERVICE, BUT SHALL NOT |
| BE PERMITTED FOR MORE THAN 6MONTHS. THE BUILDING |
| OFFICIAL IS AUTHORIZED TO GRANT EXTENSIONS FOR |
| DEMONSTRATED CAUSE. |
| |
| 2) SHEET 1 OF 4 FROM THE STATE APPROVED PLANS INDICATE |
| IN NOTE # 2 THEY WILL NEED TO PROVIDE STAIR, RAMP, |
| LANDINGS, DECKS AND GAURDRAIL DETAILS, THEY ARE NOT |
| INCLUDED IN THE STATE APPROVED PLANS. |
| 2A) 1009.6 STAIRWAY CONSTRUCTION. ALL STAIRWAYS SHALL |
| BE BUILT OF MATERIALS CONSISTENT WITH THE TYPES |
| PERMITTED FOR THE TYPE OF CONSTRUCTION OF THE BUILDING, |
| EXCEPT THAT WOOD HANDRAILS SHALL BE PERMITTED FOR ALL |
| TYPES OF CONSTRUCTION. |
| 2B) STAIR, RAMPS, LANDINGS & DECKS ARE TO BE DESIGN TO |
| TABLE 1607 LIVE LOADS. |
| 2C) 1010.2 SLOPE. RAMPS USED AS PART OF A MEANS OF |
| EGRESS SHALL HAVE A RUNNING SLOPE NOT STEEPER THAN ONE |
| UNIT VERTICAL IN 12 UNITS HORIZONTAL (8.333-PERCENT |
| SLOPE). THE SLOPE OF OTHER PEDESTRIAN RAMPS SHALL NOT |
| BE STEEPER THAN ONE UNIT VERTICAL IN EIGHT UNITS |
| HORIZONTAL (12.5-PERCENT SLOPE). ACC CODE 405, |
| HANDRAILS 1012 & GUARDRAILS 1013. |
| |
| 3) PROVIDE A SITE PLAN AND SHOW THE ACCESSIBLE ROUTE TO |
| THE MANUFACTURERD BUILDINGS FROM THE ACCESSIBLE PARKINS |
| SPOT AND ACCESS AISLE. |
| 2010 FBC- ACCESS 502.1. |
| |
| 4) SHEET 1 OF 4 FROM THE STATE APPROVED PLANS INDICATE |
| IN NOTE # 14 SITE INSTALLED ITEM GUTTERS. 1503.7 |
| PROTECTION AGAINST DECAY AND TERMITES. |
| CONDENSATE LINES AND ROOF DOWNSPOUTS SHALL DISCHARGE AT |
| LEAST 1 FOOT (305 MM) AWAY FROM THE STRUCTURE SIDEWALL, |
| WHETHER BY UNDERGROUND PIPING, TAIL EXTENSIONS, OR |
| SPLASH BLOCKS. GUTTERS WITH DOWNSPOUTS ARE REQUIRED ON |
| ALL BUILDINGS WITH EAVES OF LESS THAN 6 INCHES (152 MM) |
| HORIZONTAL PROJECTION EXCEPT FOR GABLE END RAKES OR ON |
| A ROOF ABOVE ANOTHER ROOF. |
| |
| 5) SHEET 1 OF 4 FROM THE STATE APPROVED PLANS INDICATE |
| IN NOTE # 16 STORM SHUTTERS. 2010 FBC-B 1609.1.2 |
| PROTECTION OF OPENINGS, 1609.6.4.41 COMPONENTS & |
| CLADDING |
| FLORIDA DEPARTMENT OF COMMUNITY AFFAIRS RULE 9N-3 NOV. |
| 01/ 2010 (31) SUB-CATEGORY OF PRODUCTS OR CONSTRUCTION |
| SYSTEMS THAT WILL REQUIRE PRODUCT APPROVALS: |
| (31)((E) SHUTTERS. |
| |
| 6) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION |
| & REMOVE & REPLACE ANY PAGES AS NECESSARY. A |
| TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW COMMENT |
| NUMBER, WITH A DESCRIPTION OF THE REVISION MADE, |
| IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE THE |
| CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR PERMIT. |
| THANK YOU FOR YOUR ANTICIPATED COOPERATION. |
| |