Plan Review Notes For Permit 14090681 |
Permit Number |
14090681 |
|
Review Stop |
B |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2014-10-08 14:46:36 | RESIDENTIAL (R3) SHUTTERS, BUILDING REVIEW COMMENTS. | | CODE: 2010 FBC. | | | | 1- BAHAMA SHUTTERS OPENING #2: | | A) FLORIDA PRODUCT APPROVAL FL10630-R1 SUBMITTED: | | CLARIFY SPECIFIC DRAWINGS TO BE USED. CONTRACTOR | | HIGHLIGHTED DRAWING # 10630.2 ON PAGE 2 OF 2 AND | | CROSSED OUT THE OTHER TWO. DRAWING SUBMITTED WAS # | | 10630.3. REVISE AS REQUIRED TO MATCH. SEC. 107.2.1 CITY | | AMENDMENTS TO FBC. | | | | B) NEED TO SPECIFY GLASS SEPARATION IN THE SHUTTERS | | INSTALLATION SCHEDULE AS REQUIRED BY TABLE 1 ON SHEET 2 | | OF 7. (NOTE: THERE IS NOT ANY NOTE ON THE BAHAMA | | SHUTTERS PRODUCT APPROVAL THAT ELIMINATES THE GLASS | | SEPARATION FOR NON HVHZ). SEC. 107.2.1 CITY AMENDMENTS | | TO FBC. | | | | C) BAHAMA SHUTTERS MAXIMUM DESIGN PRESSURES IS -55PSF. | | THEY DON'T MEET THE DESIGN PRESSURES SHOWN ON THE | | INSTALLATION SCHEDULE. SEC. R301 OF 2010 FBC. REVISE AS | | REQUIRED. | | | | 2- BAHAMA SHUTTERS OPENINGS #1, #3, #4 AND #9: | | A) SAME COMMENT AS #1(A) ABOVE. HIGHLIGHTED DRAWING # | | 10630.1 BUT SUBMITTED DRAWING # 10630.3. SEC. 107.2.1 | | CITY AMENDMENTS. | | | | B) SAME AS #1(B) ABOVE. | | | | C) SAME AS #1(C) ABOVE. | | | | IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT | | JULIO GOMEZ | | COMMERCIAL COMBINATION PLANS EXAMINER | | DEVELOPMENT SERVICES DEPARTMENT | | (561)805-6712 | | [email protected] |
|