2014-10-08 14:46:36RESIDENTIAL (R3) SHUTTERS, BUILDING REVIEW COMMENTS.
 CODE: 2010 FBC.
  
 1- BAHAMA SHUTTERS OPENING #2:
 A) FLORIDA PRODUCT APPROVAL FL10630-R1 SUBMITTED:
 CLARIFY SPECIFIC DRAWINGS TO BE USED. CONTRACTOR
 HIGHLIGHTED DRAWING # 10630.2 ON PAGE 2 OF 2 AND
 CROSSED OUT THE OTHER TWO. DRAWING SUBMITTED WAS #
 10630.3. REVISE AS REQUIRED TO MATCH. SEC. 107.2.1 CITY
 AMENDMENTS TO FBC.
  
 B) NEED TO SPECIFY GLASS SEPARATION IN THE SHUTTERS
 INSTALLATION SCHEDULE AS REQUIRED BY TABLE 1 ON SHEET 2
 OF 7. (NOTE: THERE IS NOT ANY NOTE ON THE BAHAMA
 SHUTTERS PRODUCT APPROVAL THAT ELIMINATES THE GLASS
 SEPARATION FOR NON HVHZ). SEC. 107.2.1 CITY AMENDMENTS
 TO FBC.
  
 C) BAHAMA SHUTTERS MAXIMUM DESIGN PRESSURES IS -55PSF.
 THEY DON'T MEET THE DESIGN PRESSURES SHOWN ON THE
 INSTALLATION SCHEDULE. SEC. R301 OF 2010 FBC. REVISE AS
 REQUIRED.
  
 2- BAHAMA SHUTTERS OPENINGS #1, #3, #4 AND #9:
 A) SAME COMMENT AS #1(A) ABOVE. HIGHLIGHTED DRAWING #
 10630.1 BUT SUBMITTED DRAWING # 10630.3. SEC. 107.2.1
 CITY AMENDMENTS.
  
 B) SAME AS #1(B) ABOVE.
  
 C) SAME AS #1(C) ABOVE.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 (561)805-6712