Notes |
Date |
Text |
2014-10-02 14:48:28 | 1ST REVIEW: FBC 2010 | | | | R302.1 EXTERIOR WALLS. | | CONSTRUCTION, PROJECTIONS, OPENINGS AND PENETRATIONS OF | | EXTERIOR WALLS OF DWELLINGS AND ACCESSORY BUILDINGS | | SHALL COMPLY WITH TABLE R302.1, FIRE-RESISTANT | | CONSTRUCTION. | | WITHIN 3', 1 HOUR-TESTED IN ACCORDANCE WITH ASTM E 119 | | OR UL 263 WITH EXPOSURE FROM BOTH SIDES | | THE FLORIDA GLASS WALL PROPOSED AT 1'0" FROM THE | | PROPERTY LINE IS DOES NOT MEET THE ABOVE REQUIREMENT | | AND DOES NOT APPEAR TO QUALIFY FOR EXCEPTION 7 AS | | FOLLOWS: " SCREEN ENCLOSURE WALLS OF INSECT SCREENING | | WITH A MAXIMUM OF 25 PERCENT SOLID FLEXIBLE FINISHES." | | | | STEVEN KENNEDY, CBO | | CHIEF PLANS EXAMINER | | (561) 805-6710 | | [email protected] | | | | |
|