Plan Review Notes
Plan Review Notes For Permit 14090620
Permit Number 14090620
Review Stop B
Sequence Number 1
Notes
Date Text
2014-09-17 18:54:07****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724
 [email protected]
  
 FBC FLORIDA BUILDING CODE 2010
  
 TWO COMPLETE COLLATED SETS OF ALL DOCUMENTS REQUIRED
  
 PLEASE SEE LAST NOTE REGARDING MY CONTACT WITH THE
 MANUFACTURER SENT 8AM ON 9/18/2014. ALTHOUGH IT IS THE
 CONTRACTOR'S RESPONSIBILITY TO PROVIDE DOCUMENTS TO
 DEMONSTRATE CODE COMPLIANCE, I HAVE REQUESTED THESE
 DOCUMENTS FROM THE MANUFACTURER. IF THEY PROVIDE THEM
 TO ME, I WILL EMAIL TO YOU FOR RESUBMITTAL.
  
 1. FBC 1207.2, FLOOR/CEILING ASSEMBLIES SEPARATING
 DWELLING UNITS FROM EACH OTHER OR FROM PUBLIC OR
 SERVICE AREAS SHALL HAVE A SOUND TRANSMISSION CLASS
 (STC) OF NOT LESS THAN 50 (45 IF FIELD TESTED) FOR AIR
 BORNE NOISE WHEN TESTED IN ACCORDANCE WITH ASTM E 90.
 IF A SUSPENDED CEILING WAS USED AS A PART OF THE TEST,
 PROVIDE INFORMATION AS TO HOW IT HAS BEEN DETERMINED
 THAT THIS CONDITION CURRENTLY EXISTS AND HOW IT CAN BE
 GUARANTEED THAT THE CONDITIONS IN THE UNIT BELOW WILL
 NOT BE ALTERED.
  
 PLEASE PROVIDE A COPY OF THE TEST REPORT.
  
 2. FBC 1207.3, FLOOR/CEILING ASSEMBLIES BETWEEN
 DWELLING UNITS OR BETWEEN A DWELLING UNIT AND A PUBLIC
 OR SERVICE AREA WITHIN THE STRUCTURE SHALL HAVE AN
 IMPACT INSULATION CLASS (IIC) RATING OF NOT LESS THAN
 50 (45 IF FIELD TESTED) WHEN TESTED IN ACCORDANCE WITH
 ASTM E 492. IF A SUSPENDED CEILING WAS USED AS A PART
 OF THE TEST, PROVIDE INFORMATION AS TO HOW IT HAS BEEN
 DETERMINED THAT THIS CONDITION CURRENTLY EXISTS AND HOW
 IT CAN BE GUARANTEED THAT THE CONDITIONS IN THE UNIT
 BELOW WILL NOT BE ALTERED.
  
 PLEASE PROVIDE A COPY OF THE TEST REPORT.
  
 3. FBC 603.1, ALLOWABLE MATERIALS IN NON COMBUSTIBLE
 BUILDINGS, SEE ITEM 2, EXCEPTION 2, ACOUSTICAL
 INSULATION INSTALLED BETWEEN A FINISHED FLOOR AND SOLID
 DECKING WITHOUT INTERVENING AIRSPACE SHALL BE ALLOWED
 TO HAVE A FLAME SPREAD INDEX OF NOT MORE THAN 200.
  
 SEE 803.1.1, PROVIDE TEST DATA IN ACCORDANCE WITH ASTM
 E 84 OR UL 723.
  
 4. THE MANUFACTURER WAS CONTACTED IN AN ATTEMPT TO
 OBTAIN THE REQUIRED DOCUMENTS FOR YOU. ON THEIR WEBSITE
 (WWW.PROFLEX.US/WORDPRESS/CONTACT/) I PLACED THE
 FOLLOWING MESSAGE TO TECHNICAL SUPPORT:
  
 A CONTRACTOR HAS APPLIED FOR A PERMIT USING PROFLEX
 CISM 40 MIL. AS THIS APPLICATION IS IN A HIGH RISE (NON
 COMBUSTIBLE CONSTRUCTION) RESIDENTIAL CONDOMINIUM,
 PLEASE EMAIL THE THREE TEST RESULTS TO ME AS DESCRIBED
 BELOW. IF THEY ARE NOT AVAILABLE, PLEASE ADVISE. IF THE
 TESTRESULTS ARE CURRENTLY UNAVAILABLE BUT YOU ARE
 WILLING TO COMMIT IN WRITING TO HAVING THE TEST
 PERFORMED AND CAN EXPLAIN WHY YOU HAVE A REASONABLE
 EXPECTATION THAT THE TEST WILL PASS (COMPLY WITH THE
 MINIMUM REQUIREMENTS OF THE FBC/IBC), I WILL ISSUE THE
 PERMIT BASED ON THE COMMITMENT LETTER. PLEASE NOTE THAT
 ALL THREE REQUIREMENTS CAN ALSO BE FOUND IN THE IBC
 (THE BASE CODE), WHICH MAKES THIS A NATIONAL
 REQUIREMENT FOR ANY STATE/JURISDICTION WHICH HAS
 ADOPTED THE IBC (NOT A FLORIDA SPECIFIC REQUIREMENT).
  
 COMMENTS 1 - 3 WERE SENT TO THE MANUFACTURER.
  
  
  
  
  