Plan Review Notes
Plan Review Notes For Permit 14090603
Permit Number 14090603
Review Stop E
Sequence Number 1
Notes
Date Text
2014-09-21 12:30:08TO TL'S DESK
  
  
  
2014-09-21 12:27:01DATE: 9/21/2014
 PROJECT: 5335 N. MILITARY TR.
 PERMIT#: 14060910
 CODE: 2008 EDITION OF THE NEC
 2010 EDITION OF THE FBC
 2010 WPB AMENDMENTS TO THE FBC, CHAPTER 1,
 ADMINISTRATION, 2012 FBC SUPPLEMENTS.
  
 1ST ELECTRICAL PLAN REVIEW
 ACTION: DENIED
  
 1) PROVIDE REVISED PLANS TO INDICATE A FLOOR PLAN THAT
 MATCHES THE RISER DIAGRAM. THERE ARE 5 ELECTRICAL
 PANELS INDICATED ON THE FLOOR PLAN SUBMITTED AND ONLY 2
 PANELS ON THE RISER SUBMITTED. LABEL AND IDENTIFY THE
 MAINS AT THE SERVICE RISER AND ALSO AT THE
 CORRESPONDING PANEL ON THE FLOOR PLAN. WPB AMENDMENTS
 TO FBC 1107.3.2
  
 2) REVISE RISER DIGRAM TO INDICATE A GROUNDING
 ELECTRODE SYSTEM DETAIL THAT INCLUDES THE MAIN BONDING
 JUMPER ATTACHMENT DETAIL AT THE NEUTRAL TERMINAL. THE
 RISER SHOWN ON THE PLAN SUBMITTED INCLUDES A # 6 GROUND
 WIRE IN THE NIPPLE WITH GROUNDED NEUTRAL CONDUCTOR.
 PLEASE REMOVE OR CLAIRIFY. WPB AMENDMENTS TO FBC
 1107.3.2
  
 3) INCLUDE THE LOCATION OF THE ELECTRICAL SERVICE AND
 MAINS ON THE PLAN. IF A SITE PLAN IS REQUIRED TO
 INDICATE THE LOCATION OF THE ELECTRCAL SERVICE PLEASE
 PROVIDE TO INDICATE THE LOACTION OF THE ELECTRICAL
 SERVICE IN RELATION TO THE SERVICE. WPB AMENDMENTS TO
 FBC 1107.3.2
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. SEE LINK:
 HTTP://WPB.ORG/DEVELOPMENT/WP-CONTENT/UPLOADS/SITES/33/
 2013/09/APPLICATION_RESUBMITTAL_FORM_04132010.PDF
  
 ADDITIONALLY, PLEASE INSERT CORRECTED PAGES INTO
 SUBMITTAL PACKAGE AND LEAVE THE PREVIOUSLY REVIEWED
 SHEETS FOR COMPARATIVE REVIEW.
  
 DAVID HAYES, ELECTRICAL PLANS EXAMINER, PX3421,
 561-805-6717 OR [email protected]
  