Plan Review Notes
Plan Review Notes For Permit 14090577
Permit Number 14090577
Review Stop B
Sequence Number 1
Notes
Date Text
2014-09-18 11:42:06****CORRECTIONS****
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 FBC 2010 RESIDENTIAL 301, FBC 2010 BUILDING 1609
 (RESISTANCE TO WIND LOADS)
  
 1. FOR THE FLAT DECK ROOF, INDICATE WHICH FASTENING
 OPTION WITHIN THE APPROVED ASSEMBLY IS PROPOSED.
  
 2. SEE GENERAL LIMITATION NUMBER 7 ON THE LAST PAGE OF
 THE MIAMI DADE NOA. FASTENER DENSITIES SHALL BE
 INCREASED IN COMPLIANCE WITH RAS 117. CALCULATIONS
 PREPARED, SIGNED AND SEALED BY A FLORIDA REGISTERED
 PROFESSIONAL ENGINEER, REGISTERED ARCHITECT, OR
 REGISTERED ROOF CONSULTANT IS REQUIRED.
  
 PLEASE NOTE THAT THE 400 SQUARE FOOT EXEMPTION TO
 ENGINEERING IS A PALM BEACH COUNTY EXEMPTION NOT
 APPLICABLE IN THE CITY OF WEST PALM BEACH.
  
  
  