Plan Review Notes For Permit 14090554 |
Permit Number |
14090554 |
|
Review Stop |
G |
Sequence Number |
2 |
|
Notes |
Date |
Text |
2014-09-27 06:15:00 | WPB ADMIN. AMEND. TO 2010 FBC SEC. 107.2.1. | | 1) THE REVISED DRAWING IS STILL VAGUE REGARDING THE | | SIZING AND TYPE OF PIPE BEING USED. IF YOU ARE USING | | THE LONGEST LENGTH METHOD I SUGGEST REFERRING TO SEC. | | 402.4.1 OF THE 2010 FLORIDA FUEL GAS CODE AND ALSO THE | | DEFINITION OF "POINT OF DELIVERY." | | I CANNOT DO A PROPER REVIEW UNTIL THE FOLLOWING ISSUES | | ARE CLARIFIED: | | A) INDICATE THE TOTAL LENGTH OF THE PIPING FROM THE | | "POINT OF DELIVERY" TO THE MOST REMOTE OUTLET AND THE | | LOAD FOR THE SECTION. | | B) LABEL THE PIECES OF EQUIPMENT ON THE GAS RISER. | | C) YOU SUBMITTED A SIZING TABLE FOR PE PIPE YET THE GAS | | RISER SHOWS THE LETTER "G" WHICH I ASSUME TO BE IS | | GALVANIZED. CLEARLY INDICATE THE TYPE OF PIPE MATERIAL | | BEING INSTALLED. | | D) SUBMIT TWO COPIES OF THE APPROPRIATE SIZING TABLES | | AND HEATER SPEC. SHEETS. | | | | PLUMBING PLAN REVIEW | | TIM LARGE | | CHIEF PLUMBING INSPECTOR | | 561-805-6692 | | [email protected] | | |
|