2014-09-27 06:15:00WPB ADMIN. AMEND. TO 2010 FBC SEC. 107.2.1.
 1) THE REVISED DRAWING IS STILL VAGUE REGARDING THE
 SIZING AND TYPE OF PIPE BEING USED. IF YOU ARE USING
 THE LONGEST LENGTH METHOD I SUGGEST REFERRING TO SEC.
 402.4.1 OF THE 2010 FLORIDA FUEL GAS CODE AND ALSO THE
 DEFINITION OF "POINT OF DELIVERY."
 I CANNOT DO A PROPER REVIEW UNTIL THE FOLLOWING ISSUES
 ARE CLARIFIED:
 A) INDICATE THE TOTAL LENGTH OF THE PIPING FROM THE
 "POINT OF DELIVERY" TO THE MOST REMOTE OUTLET AND THE
 LOAD FOR THE SECTION.
 B) LABEL THE PIECES OF EQUIPMENT ON THE GAS RISER.
 C) YOU SUBMITTED A SIZING TABLE FOR PE PIPE YET THE GAS
 RISER SHOWS THE LETTER "G" WHICH I ASSUME TO BE IS
 GALVANIZED. CLEARLY INDICATE THE TYPE OF PIPE MATERIAL
 BEING INSTALLED.
 D) SUBMIT TWO COPIES OF THE APPROPRIATE SIZING TABLES
 AND HEATER SPEC. SHEETS.
  