2014-09-20 04:58:58WPB AMEND. TO 2010 FBC SEC. 107.2.1.
 1) THE GAS PIPING FOR THE FIRE PIT IS NOT SHOWN ON THE
 GAS RISER. SHOW THE PIPNG FOR THE FIRE PIT & BTU LOAD
 ON THE DRAWING.
 2) SIZE ALL SECTIONS THE PIPING ON THE GAS RISER.
 3) SUBMIT A COPY OF THE APPLICABLE SIZING TABLE USED
 FOR THE GAS SYSTEM.
 4) SUBMIT MANUFACTURER'S SPECIFICATION SHEETS FOR ALL
 GAS EQUIPMENT. ALL EQUIPMENT SHALL BE LISTED AND
 LABELED PER THE 2010 FUEL GAS CODE SEC. 301.3.
 5) THERE ARE TWO LONGEST LENGTHS SHOWN ON THE PLANS. IT
 APPEARS THAT THE LONGEST LENGTH IS THE RUN TO THE
 WADING POOL HEATER. THIS LENGTH SHALL BE USED FOR THE
 SIZING OF THE ENTIRE SYSTEM PER THE 2010 FGC
 SEC.402.4.1.
  