2014-12-01 14:54:07 | DATE: 12/01/2014 |
| PROJECT: BUS SHELTER |
| PERMIT#: 14090549 |
| CODE: 2008 EDITION OF THE NEC |
| 2010 EDITION OF THE FBC |
| 2010 WPB AMENDMENTS TO THE FBC, CHAPTER 1, |
| ADMINISTRATION, 2012 FBC SUPPLEMENTS. |
| |
| 2ND ELECTRICAL PLAN REVIEW |
| ACTION: DENIED |
| |
| 1) WHEN RESUBMITTING IT IS REQUIRED TO INSERT THE |
| CORRECTED PAGES INTO THE DENIED SUBMITTAL PACKAGE, VOID |
| THE PREVIOUSLY REVIEWED SHEETS AND LEAVE THEM FOR |
| COMPARATIVE REVIEW. PLEASE INSERT REVISED SHEETS FOR |
| NEXT RESUBMITTAL. |
| |
| 2) CLARIFICATION IS REQUIRED BETWEEN THE "FLOOR PLAN" |
| AND THE "ELECTRICAL PLAN" THE FLOOR PLAN INDICATES ONE |
| LIGHT FIXTURE IN WHAT APPEARS TO BE THE MIDDLE OF THE |
| FLOOR AND CALLS FOR CONTROL BY A TIME CLOCK. THE |
| ELECTRICAL PLAN INDICATES TWO LIGHT FIXTURES IN WHAT |
| APPEARS TO BE THE CEILING STRUCTURE AND TO BE CONTROLED |
| BY A PHOTO CELL. PLEASE CLARIFY AND INDICATE THE |
| LOCATION OF THE PHOTOCELL. |
| B) PROVIDE A LIGHT FIXTURE SCHEDULE TO INDICATE THE |
| TYPE AND APPROVED USE FOR THE PROPOSED LIGHT FIXTURES. |
| |
| 3) PROVIDE A SITE PLAN INDICATING THE BUS SHELTER, THE |
| LOCATION OF THE ELECTRICAL SERVICE AND THE ELECTRICAL |
| PANEL RELATIVE TO THE LOCATION OF THE BUS SHELTER. THE |
| ELECTRICAL PANEL ON THE RISER DIAGRAM IS INDICATED AS A |
| NEMA 1 ENCLOSURE. PLEASE CLARIFY THE PANEL IS IN A NEMA |
| 1 LOCATION OR REVISE TO APPROVED TYPE. |
| |
| WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| RE-SUBMITTAL FORM. SEE LINK: |
| HTTP://WPB.ORG/DEVELOPMENT/WP-CONTENT/UPLOADS/SITES/33/ |
| 2013/09/APPLICATION_RESUBMITTAL_FORM_04132010.PDF |
| |
| ADDITIONALLY, PLEASE INSERT CORRECTED PAGES INTO |
| SUBMITTAL PACKAGE AND LEAVE THE PREVIOUSLY REVIEWED |
| SHEETS FOR COMPARATIVE REVIEW. |
| |
| DAVID HAYES, ELECTRICAL PLANS EXAMINER, PX3421, |
| 561-805-6717 OR [email protected] |
| |