2014-09-16 16:50:55 | DATE: 9/16/2014 |
| PROJECT: BUS SHELTER |
| PERMIT#: 14090549 |
| CODE: 2008 EDITION OF THE NEC |
| 2010 EDITION OF THE FBC |
| 2010 WPB AMENDMENTS TO THE FBC, CHAPTER 1, |
| ADMINISTRATION, 2012 FBC SUPPLEMENTS. |
| |
| 1ST ELECTRICAL PLAN REVIEW |
| ACTION: DENIED |
| |
| 1) PROVIDE THE MINIMUM PLAN REVIEW CRITERIA, RISER |
| DIAGRAM, PANEL SCHEDULE, LOAD CALCULATION. |
| |
| 2) INDICATE HOW THE DESIGN IS PROPOSED TO COMPLY WITH |
| THE FBC-E 505 LIGHTING FOR ALL EXTERIOR APPLICATIONS |
| NOT EXEMPTED IN SECTION 505.1 SHALL HAVE AUTOMATIC |
| CONTROLS CAPABLE OF TURNING OFF EXTERIOR LIGHTING WHEN |
| SUFFICIENT DAYLIGHT IS AVAILABLE OR WHEN THE LIGHTING |
| IS NOT REQUIRED DURING NIGHTTIME HOURS. LIGHTING NOT |
| DESIGNATED FOR DUSK-TO-DAWN OPERATION SHALL BE |
| CONTROLLED BY EITHER A COMBINATION OF A PHOTOSENSOR AND |
| A TIME SWITCH, OR AN ASTRONOMICAL TIME SWITCH |
| |
| WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| RE-SUBMITTAL FORM. SEE LINK: |
| HTTP://WPB.ORG/DEVELOPMENT/WP-CONTENT/UPLOADS/SITES/33/ |
| 2013/09/APPLICATION_RESUBMITTAL_FORM_04132010.PDF |
| |
| ADDITIONALLY, PLEASE INSERT CORRECTED PAGES INTO |
| SUBMITTAL PACKAGE AND LEAVE THE PREVIOUSLY REVIEWED |
| SHEETS FOR COMPARATIVE REVIEW. |
| |