Plan Review Notes For Permit 14090547 |
Permit Number |
14090547 |
|
Review Stop |
FIRE |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2014-09-29 16:38:01 | THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE | | MARSHAL, WITH THE FOLLOWING COMMENTS: | | | | THE SITE PLAN DOES INDICATE ANY ENTRANCE/EXIT WAY WIDTH | | DIMENSIONS. THIS ENTRANCE IS A FIRE LANE WITH A MINIMUM | | WIDTH OF 20' AND INDICATED ON THE PLAN. | | | | THE SITE PLAN DOES NOT SHOW THE LOCATION OF ANY COLUMNS | | OR OTHER STRUCTURES THAT THE GATES WILL BE FASTENED TO. | | | | A KNOX KEY SYSTEM IS REQUIRED TO OPERATE THE GATE IN | | THE EVENT OF EMERGENCY 24 HOURS A DAY. A NOTE SHALL BE | | BE ADDED TO THE PLAN. | | | | THE RADUIS OF THE CURVES FOR THE ENTRANCE/EXIT LANES | | SHALL ACCOMMODATE A 40' FIRE TRUCK AND SHALL BE | | INDICATED ON THE PLAN. |
|