2014-09-17 15:39:00THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
 ACCESS-CONTROLLED EGRESS DOOR ASSEMBLIES (?MAG-LOCKS?)
  
 7.2.1.6.2 (NFPA 101) DOOR ASSEMBLIES IN THE MEANS OF
 EGRESS SHALL BE PERMITTED TO BE EQUIPPED WITH AN
 APPROVED ENTRANCE AND EGRESS ACCESS CONTROL SYSTEM,
 PROVIDED THAT ALL THE FOLLOWING CRITERIA ARE MET:
  
 (1) A SENSOR SHALL BE PROVIDED ON THE EGRESS SIDE,
 ARRANGED TO DETECT AN OCCUPANT APPROACHING DOOR LEAVES
 THAT ARE ARRANGED TO UNLOCK IN THE DIRECTION OF EGRESS
 UPON DETECTION OF AN APPROACHING OCCUPANT OR LOSS OF
 POWER TO THE SENSOR.
  
 (2) LOSS OF POWER TO THE PART OF THE ACCESS CONTROL
 SYSTEM THAT LOCKS THE DOOR LEAVES SHALL AUTOMATICALLY
 UNLOCK THE DOOR LEAVES IN THE DIRECTION OF EGRESS.
  
 (3) DOOR LEAVES SHALL BE ARRANGED TO UNLOCK IN THE
 DIRECTION OF EGRESS FROM A MANUAL RELEASE DEVICE
 LOCATED 40 IN. TO 48 IN. VERTICALLY ABOVE THE FLOOR AND
 WITHIN 60 IN. OF THE SECURED DOOR OPENINGS.
  
 (4) THE MANUAL RELEASE DEVICE SHALL BE READILY
 ACCESSIBLE AND CLEARLY IDENTIFIED BY A SIGN THAT READS
 AS FOLLOWS: PUSH TO EXIT.
  
 (5) WHEN OPERATED, THE MANUAL RELEASE DEVICE SHALL
 RESULT IN DIRECT INTERRUPTION OF POWER TO THE LOCK
 INDEPENDENT OF THE ACCESS CONTROL SYSTEM ELECTRONICS
 AND THE DOOR LEAVES SHALL REMAIN UNLOCKED FOR NOT LESS
 THAN 30 SECONDS.
  
 (6) ACTIVATION OF THE BUILDING FIRE-PROTECTIVE
 SIGNALING SYSTEM, IF PROVIDED, SHALL AUTOMATICALLY
 UNLOCK THE DOOR LEAVES IN THE DIRECTION OF EGRESS, AND
 THEY SHALL REMAIN UNLOCKED UNTIL THE FIRE-PROTECTIVE
 SIGNALING SYSTEM HAS BEEN MANUALLY RESET.
  
 (7) THE ACTIVATION OF MANUAL FIRE ALARM BOXES THAT
 ACTIVATE THE BUILDING FIRE-PROTECTIVE SIGNALING SYSTEM
 SHALL NOT BE REQUIRED TO UNLOCK THE DOOR LEAVES. (8)
 ACTIVATION OF THE BUILDING AUTOMATIC SPRINKLER OR FIRE
 DETECTION SYSTEM, IF PROVIDED, SHALL AUTOMATICALLY
 UNLOCK THE DOOR LEAVES IN THE DIRECTION OF EGRESS, AND
 THEY SHALL REMAIN UNLOCKED UNTIL THE FIRE-PROTECTIVE
 SIGNALING SYSTEM HAS BEEN MANUALLY RESET.
  
 ALL OF THESE REQUIRMENTS SHALL BE MET AND CLEARLY
 IDENTIFIED AND INDICATED ON THE PLAN AT EACH INTENDED
 INSTALLATION LOCATION.
  