2014-09-22 16:17:59 | TO MISC. 2 |
| |
| |
2014-09-22 16:15:17 | DATE: 9/22/2014 |
| PROJECT: FOREVER 21 SIGN |
| PERMIT#: 14090505 |
| CODE: 2008 EDITION OF THE NEC |
| 2010 EDITION OF THE FBC |
| 2010 WPB AMENDMENTS TO THE FBC, CHAPTER 1, |
| ADMINISTRATION, 2012 FBC SUPPLEMENTS. |
| |
| 1ST ELECTRICAL PLAN REVIEW |
| ACTION: DENIED |
| |
| 1) NEC 600.6(A)(1)DISCONNECTS. |
| EACH SIGN AND OUTLINE LIGHTING SYSTEM, OR FEEDER |
| CIRCUIT OR BRANCH CIRCUIT SUPPLYING A SIGN OR OUT-LINE |
| LIGHTING SYSTEM, SHALL BE CONTROLLED BY AN EXTERNALLY |
| OPERABLE SWITCH OR CIRCUIT BREAKER THAT WILL OPEN ALL |
| UNGROUNDED CONDUCTORS WITHIN SIGHT OF THE SIGN OR |
| OUTLINE LIGHTING SYSTEM THAT IT CONTROLS. |
| |
| 2) FBC-E 505.2.4 ENERGY |
| ALL EXTERIOR LIGHTING NOT EXEMPTED BY FBC 505.1 SHALL |
| HAVE AUTOMATIC CONTROLS TO TURN OFF AT DAYLIGHT OR WHEN |
| NOT REQUIRED. CONTROLS SHALL BE PHOTOSENSOR & TIME |
| CLOCK OR ASTRONOMICAL TIME SWITCH. ALL TIME SWITCHES |
| SHALL BE CAPABLE OF RETAINING PROGRAMING DURING A LOSS |
| OF POWER FOR A MINIMUM OF 10 HOURS. |
| |
| 3) WPB AMENDMENTS TO THE FBC SECTION 109.3 VALUATION. |
| THE CLAIMED VALUATION OF THE, ALTERATION, APPEARS TO BE |
| UNDERESTIMATED ON THE APPLICATION.THE BUILDING OFFICIAL |
| SHALL RESERVE THE RIGHT TO DENY THE PERMIT. THE |
| APPLICANT HAS THE RIGHT TO SHOW DETAILED, QUANTITY |
| ESTIMATES, AND/OR BONA FIDE SIGNED CONTRACTS (EXCLUDING |
| LAND VALUE) TO MEET THE APPROVAL OF THE BUILDING |
| OFFICIAL. |
| FOR PERMITTING PURPOSES, VALUATION OF BUILDINGS AND |
| SYSTEMS SHALL BE TOTAL REPLACEMENT VALUE TO INCLUDE |
| STRUCTURAL, ELECTRIC, PLUMBING, MECHANICAL, INTERIOR |
| FINISH, RELATIVE SITE WORK, ARCHITECTURAL AND DESIGN |
| FEES, MARKETING COSTS, OVERHEAD AND PROFIT; EXCLUDING |
| ONLY LAND VALUE. VALUATION REFERENCES MAY INCLUDE THE |
| LATEST PUBLISHED DATA OF NATIONAL CONSTRUCTION COST |
| ANALYSIS SERVICES (MARSHALL-SWIFT, MEANS, ETC.), AS |
| PUBLISHED BY INTERNATIONAL CODE CONGRESS. FINAL |
| BUILDING PERMIT VALUATION SHALL BE SET BY THE BUILDING |
| OFFICIAL. FBC WPB AMENDMENTS. SECTION 109.3 |
| |
| WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| RE-SUBMITTAL FORM. SEE LINK: |
| HTTP://WPB.ORG/DEVELOPMENT/WP-CONTENT/UPLOADS/SITES/33/ |
| 2013/09/APPLICATION_RESUBMITTAL_FORM_04132010.PDF |
| |
| ADDITIONALLY, PLEASE INSERT CORRECTED PAGES INTO |
| SUBMITTAL PACKAGE AND LEAVE THE PREVIOUSLY REVIEWED |
| SHEETS FOR COMPARATIVE REVIEW. |
| |
| DAVID HAYES, ELECTRICAL PLANS EXAMINER, PX3421, |
| 561-805-6717 OR [email protected] |