2014-10-07 10:56:46 | RESIDENTIAL (R3) WINDOW ALTERATION, SECOND BUILDING |
| REVIEW COMMENTS. |
| CODE: 2010 FBC. |
| |
| 1- PROVIDE COMPLETE SHUTTERS INSTALLATION SCHEDULE. |
| INFORMATION SHOWN IN THE SHUTTERS INSTALLATION SCHEDULE |
| SUBMITTED IS INCOMPLETE. IT DOESN'T PROVIDE ANY |
| INFORMATION CONCERNING THE PROPOSED INSTALLATION. SEC. |
| 107.2.1 CITY AMENDMENTS TO FBC. |
| REPEAT COMMENT. NOT ADDRESSED. |
| |
| 2- SKETCH SUBMITTED: CLEARLY SPECIFY THE EXISTING |
| BEDROOM WINDOWS TYPE AND SIZE TO VERIFY COMPLIANCE WITH |
| THE EGRESS REQUIREMENTS OF SEC. 604 OF 2010 |
| FBC-EXISTING BUILDING CODE. |
| REPEAT COMMENT. NOT ADDRESSED. |
| |
| 3- VALUATION DECLARED IN THE PERMIT APPLICATION IS TOO |
| LOW. THERE ARE NO 12 WINDOWS TO BE REPLACED AS STATED |
| IN THE PERMIT APPLICATION. ACCORDING TO SKETCH |
| SUBMITTED, THERE ARE 19 WINDOWS AND 7 WINDOW MULLIONS |
| TO BE REPLACED. IN ADDITION, THERE WILL BE HURRICANE |
| PANELS INSTALLED ALSO. VALUATION TO INCLUDE ALL LABOR, |
| MATERIALS, AND CONTRACTOR'S OVERHEAD AND PROFIT AS |
| REQUIRED BY SEC. 1069.3 CITY AMENDMENTS TO FBC. UPDATE |
| VALUATION AS REQUIRED. |
| REPEAT COMMENT. NOT ADDRESSED. |
| |