2014-10-07 10:56:46RESIDENTIAL (R3) WINDOW ALTERATION, SECOND BUILDING
 REVIEW COMMENTS.
 CODE: 2010 FBC.
  
 1- PROVIDE COMPLETE SHUTTERS INSTALLATION SCHEDULE.
 INFORMATION SHOWN IN THE SHUTTERS INSTALLATION SCHEDULE
 SUBMITTED IS INCOMPLETE. IT DOESN'T PROVIDE ANY
 INFORMATION CONCERNING THE PROPOSED INSTALLATION. SEC.
 107.2.1 CITY AMENDMENTS TO FBC.
 REPEAT COMMENT. NOT ADDRESSED.
  
 2- SKETCH SUBMITTED: CLEARLY SPECIFY THE EXISTING
 BEDROOM WINDOWS TYPE AND SIZE TO VERIFY COMPLIANCE WITH
 THE EGRESS REQUIREMENTS OF SEC. 604 OF 2010
 FBC-EXISTING BUILDING CODE.
 REPEAT COMMENT. NOT ADDRESSED.
  
 3- VALUATION DECLARED IN THE PERMIT APPLICATION IS TOO
 LOW. THERE ARE NO 12 WINDOWS TO BE REPLACED AS STATED
 IN THE PERMIT APPLICATION. ACCORDING TO SKETCH
 SUBMITTED, THERE ARE 19 WINDOWS AND 7 WINDOW MULLIONS
 TO BE REPLACED. IN ADDITION, THERE WILL BE HURRICANE
 PANELS INSTALLED ALSO. VALUATION TO INCLUDE ALL LABOR,
 MATERIALS, AND CONTRACTOR'S OVERHEAD AND PROFIT AS
 REQUIRED BY SEC. 1069.3 CITY AMENDMENTS TO FBC. UPDATE
 VALUATION AS REQUIRED.
 REPEAT COMMENT. NOT ADDRESSED.
  