Plan Review Notes
Plan Review Notes For Permit 14090490
Permit Number 14090490
Review Stop B
Sequence Number 1
Notes
Date Text
2014-09-17 08:53:43RESIDENTIAL (R3) WINDOW ALTERATION, BUILDING REVIEW
 COMMENTS.
 CODE: 2010 FBC.
  
 1- PROVIDE COMPLETE SHUTTERS INSTALLATION SCHEDULE.
 INFORMATION SUBMITTED IS INCOMPLETE. IT DOESN'T PROVIDE
 ANY INFORMATION CONCERNING THE PROPOSED INSTALLATION.
 SEC. 107.2.1 CITY AMENDMENTS TO FBC.
  
 2- SKETCH SUBMITTED: CLEARLY IDENTIFY ROOM DESIGNATIONS
 (FOR EXAMPLE BEDROOM, KITCHEN, LIVING ROOM, ETC). AND
 CLEARLY SPECIFY THE EXISTING BEDROOM WINDOWS TYPE AND
 SIZE TO VERIFY COMPLIANCE WITH THE EGRESS REQUIREMENTS
 OF SEC. 604 OF 2010 FBC-EXISTING BUILDING CODE.
  
 3- VALUATION DECLARED IN THE PERMIT APPLICATION IS TOO
 LOW. THERE ARE NO 12 WINDOWS TO BE REPLACED AS STATED
 IN THE PERMIT APPLICATION. ACCORDING TO SKETCH
 SUBMITTED, THERE ARE 19 WINDOWS AND 7 WINDOW MULLIONS
 TO BE REPLACED. IN ADDITION, THERE WILL BE HURRICANE
 PANELS INSTALLED ALSO. VALUATION TO INCLUDE ALL LABOR,
 MATERIALS, AND CONTRACTOR'S OVERHEAD AND PROFIT AS
 REQUIRED BY SEC. 1069.3 CITY AMENDMENTS TO FBC. UPDATE
 VALUATION AS REQUIRED.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CALL
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICE DEPARTMENT
 (561)805-6712
 [email protected]