2014-09-16 14:58:35RESIDENTIAL (R2) ALTERATION BUILDING REVIEW COMMENTS.
 CODE: 2010 FBC
  
 1- PROVIDE INFORMATION FOR THE FLAME SPREAD INDEX AND
 SMOKE DEVELOPED INDEX OF THE "SOUNDGUARD" INSULATION TO
 BE INSTALLED. INFORMATION SUBMITTED TO BE IN ACCORDANCE
 WITH ASTM E 84 OR UL 723 AS REQUIRED BY SEC. 719.1 OF
 2010 FBC.
  
 2- VALUATION DECLARED IN THE PERMIT APPLICATION IS TOO
 LOW. VALUATION TO INCLUDE ALL LABOR, MATERIALS AND
 CONTRACTOR'S OVERHEAD AND PROFIT AS REQUIRED BY SEC.
 109.3 OF CITY AMENDMENTS TO FBC. REVISE VALUATION AS
 REQUIRED.
  
  
 ***IMPORTANT:
 INFORMATION SUBMITTED SHOWS IIC RATING OF 71 AND STC
 RATING OF 67. THESE RESULTS ARE BASED ON A FLOOR
 ASSEMBLY OF 8" CONCRETE SLAB WITH SUSPENDED GYPSUM
 CEILING OVERLAY. VERIFY THAT THAT FLOOR ASSEMBLY IN
 THIS BUILDING MEETS THAT CRITERIA. OTHERWISE,
 ADDITIONAL INFORMATION WILL BE REQUIRED TO MATCH ACTUAL
 FLOOR ASSEMBLY IN THIS BUILDING.
  