2014-09-13 13:11:57DATE: 9/13/2014
 PROJECT: GOLDBERG BATHROOM RENNOVATION
 PERMIT#: 14090410
 CODE: 2008 EDITION OF THE NEC
 2010 EDITION OF THE FBC
 2010 WPB AMENDMENTS TO THE FBC, CHAPTER 1,
 ADMINISTRATION, 2012 FBC SUPPLEMENTS.
  
 1ST ELECTRICAL PLAN REVIEW
 ACTION: PROVISO
  
 1) NEC 210.11(C)(3)
 BATHROOM BRANCH CIRCUITS. IN ADDITION TO THE NUMBER OF
 BRANCH CIRCUITS REQUIRED BY OTHER PARTS OF THIS
 SECTION, AT LEAST ONE 20-AMPERE BRANCH CIRCUIT SHALL BE
 PROVIDED TO SUPPLY BATHROOM RECEPTACLE OUTLET(S). SUCH
 CIRCUITS SHALL HAVE NO OTHER OUTLETS. VERFY EXISTING
 RECEPTACLE OUTLET CIRCUIT IS 20 AMP OR UPDATE TO FOR
 NEC COMPLIANCE
  
 2) FBC-RESIDENTIAL 314 AND 315.
 WHEN ALTERATIONS, REPAIRS, OR ADDITIONS REQUIRING A
 PERMIT OCCUR, OR WHEN ONE OR MORE SLEEPING ROOMS ARE
 ADDED OR CREATED IN EXISTING DWELLINGS, THE INDIVIDUAL
 DWELLING UNIT SHALL BE EQUIPPED WITH SMOKE ALARMS
 LOCATED AS REQUIRED FOR NEW DWELLINGS. VERIFY DUAL
 VOLTAGE SMOKE DETECTORS ARE EXISTING OR UPDATE FOR FBC
 COMPLIANCE.
  
 DAVID HAYES, ELECTRICAL PLANS EXAMINER, PX3421,