Plan Review Notes For Permit 14090410 |
Permit Number |
14090410 |
|
Review Stop |
E |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2014-09-13 13:11:57 | DATE: 9/13/2014 | | PROJECT: GOLDBERG BATHROOM RENNOVATION | | PERMIT#: 14090410 | | CODE: 2008 EDITION OF THE NEC | | 2010 EDITION OF THE FBC | | 2010 WPB AMENDMENTS TO THE FBC, CHAPTER 1, | | ADMINISTRATION, 2012 FBC SUPPLEMENTS. | | | | 1ST ELECTRICAL PLAN REVIEW | | ACTION: PROVISO | | | | 1) NEC 210.11(C)(3) | | BATHROOM BRANCH CIRCUITS. IN ADDITION TO THE NUMBER OF | | BRANCH CIRCUITS REQUIRED BY OTHER PARTS OF THIS | | SECTION, AT LEAST ONE 20-AMPERE BRANCH CIRCUIT SHALL BE | | PROVIDED TO SUPPLY BATHROOM RECEPTACLE OUTLET(S). SUCH | | CIRCUITS SHALL HAVE NO OTHER OUTLETS. VERFY EXISTING | | RECEPTACLE OUTLET CIRCUIT IS 20 AMP OR UPDATE TO FOR | | NEC COMPLIANCE | | | | 2) FBC-RESIDENTIAL 314 AND 315. | | WHEN ALTERATIONS, REPAIRS, OR ADDITIONS REQUIRING A | | PERMIT OCCUR, OR WHEN ONE OR MORE SLEEPING ROOMS ARE | | ADDED OR CREATED IN EXISTING DWELLINGS, THE INDIVIDUAL | | DWELLING UNIT SHALL BE EQUIPPED WITH SMOKE ALARMS | | LOCATED AS REQUIRED FOR NEW DWELLINGS. VERIFY DUAL | | VOLTAGE SMOKE DETECTORS ARE EXISTING OR UPDATE FOR FBC | | COMPLIANCE. | | | | DAVID HAYES, ELECTRICAL PLANS EXAMINER, PX3421, | | 561-805-6717 OR [email protected] | | | | | | | | | | |
|