Plan Review Notes For Permit 14090389 |
Permit Number |
14090389 |
|
Review Stop |
FIRE |
Sequence Number |
2 |
|
Notes |
Date |
Text |
2014-10-14 12:35:54 | THIS PLAN WAS REVIEWED AND TENTATTIVELY APPROVED BY | | PETER LEDUC, FIRE MARSHAL, WITH THE FOLLOWING COMMENTS: | | | | PROVISO: | | | | THE OCCUPANY LOAD AS PROPOSED COULD NOT BE VERIFIED. | | | | THE STAIRWAYS AND DOORS ASH SHOWN IS ACCEPTABLE AND | | WILL BE FIELD VERIFIED. | | | | DIMENSIONS OF THE OCCUPIED SPACE OR OCCUPANCY LOAD | | CALCULATIONS WERE NOT PROVIDED OR DID NOT MATCH | | DRAWINGS TO VERIFY THE OCCUPANCY LOADS PROPOSED. | | | | PROVIDE OCCUPANCY LOAD CALCULATIONS INCLUDING | | DIMENSIONS AND OTHER PERTINANT INFORMATION JUSTIFYING | | THE PROPOSED OCCUPANY LOADS THAT MATCH EXISTING OR | | PROPOSED FLOOR LAYOUTS. | | | | PROVIDE THE ABOVE INFORMATION TO THE FIRE INSPECTOR FOR | | VERIFICATION AT THE TIME OF FIRE INSPECTION. THE | | OCCUPANCY LOADS WILL BE POSTED BASED ON THOSE | | CALCULATIONS WITH VERIFICATION OF THE FIRE INSPECTOR. | | |
|