2014-09-25 09:47:54 | BUILDING PLAN REVIEW |
| PERMIT: 14090389 |
| ADD: 309 CLEMATIS ST |
| CONT: TBD |
| TEL: (561)296-7699 SCOTT SMITH |
| |
| 2010 FLORIDA BUILDING CODE W |
| * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA |
| BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION |
| 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013. |
| |
| 2010 EXISTING BUILDING CODE LEVEL II 701.3 |
| COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, |
| SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS |
| OF THE FLORIDA BUILDING CODE, BUILDING. |
| |
| 1ST REVIEW |
| DATE: THURS. SEPT. 25TH/ 2014 |
| ACTION: DENIED |
| |
| 1) PLEASE PROVIDE A EXIT PLAN FOR THE WHOLE BUILDING. |
| PLEASE NOTE THIS IS A THREE STORY BUILDING A-2 / A3 |
| ASSEMBLY BUILDING WITH ONLY 2 ENCLOSED STAIRWELLS. |
| 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING |
| CODE, CHAPTER 1, ADMINISTRATION, |
| 107.3.5 MINIMUM PLAN REVIEW CRITERIA FOR BUILDINGS. THE |
| EXAMINATION OF THE DOCUMENTS BY THE BUILDING OFFICIAL |
| SHALL INCLUDE THE FOLLOWING MINIMUM CRITERIA AND |
| DOCUMENTS: A FLOOR PLAN; |
| 107.3.5.1 COMMERCIAL BUILDINGS: |
| 107.3.5.1.1 BUILDING |
| OCCUPANCY GROUP AND SPECIAL OCCUPANCY REQUIREMENTS |
| SHALL BE DETERMINED. |
| MINIMUM TYPE OF CONSTRUCTION SHALL BE DETERMINED (SEE |
| TABLE 503). |
| OCCUPANCY LOAD/EGRESS REQUIREMENTS SHALL INCLUDE: |
| OCCUPANCY LOAD |
| GROSS |
| NET |
| MEANS OF EGRESS |
| EXIT ACCESS |
| EXIT |
| EXIT DISCHARGE |
| STAIRS CONSTRUCTION/GEOMETRY AND PROTECTION |
| DOORS |
| |
| 2) 2010 FBC-B 1016.1 DOES ALLOW FOR UNENCLOSED |
| STAIRWELLS FOR 50 % OF EXITS BUT EXCEPTION # 3 ONLY |
| ALLOWS THE EXIT ACCESS TRAVEL DISTANCE TO A MAXIMUM OF |
| 50 PERCENT OF THE EXITS IS PERMITTED TO BE MEASURED |
| FROM THE MOST REMOTE POINT WITHIN A BUILDING TO AN EXIT |
| USING UNENCLOSED EXIT ACCESS STAIRWAYS OR RAMPS WHEN |
| CONNECTING A MAXIMUM OF TWO STORIES. THE TWO CONNECTED |
| STORIES SHALL BE PROVIDED WITH AT LEAST TWO MEANS OF |
| EGRESS. SUCH INTERCONNECTED STORIES SHALL NOT BE OPEN |
| TO OTHER STORIES. THIS STAIR CONNECTS TO THE 3RD STORY |
| A ROOF TOP ASSEMBLY FLOOR. |
| |
| 3) NOTE THERE IS ALSO AN OPEN EXPIRED PERMIT FOR THE |
| 3RD STORY ROOFTOP ADDITION, NEVER ACHIEVED A |
| CERTIFICATE OF OCUPANCY, PERMIT # 08060519. |
| |
| WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION & |
| REMOVE & REPLACE ANY PAGES AS NECESSARY. A TRANSMITTAL |
| LETTER LISTING THE ORIGINAL REVIEW COMMENT NUMBER, WITH |
| A DESCRIPTION OF THE REVISION MADE, IDENTIFYING THE |
| SHEET OR SPECIFICATION PAGE WHERE THE CHANGES CAN BE |
| FOUND WILL HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR |
| YOUR ANTICIPATED COOPERATION. |
| |
| JAMES A. WITMER CBO |
| SENIOR COMMERCIAL COMBINATION PLANS EXAMINER |
| TEL: 561-805-6715 |
| FAX: 561-805-6676 |
| E-MAIL: [email protected] |
| |
| DEVELOPMENT SERVICES HOME PAGE |
| HTTP://WWW.CITYOFWPB.COM/CONSTRUCTION/INDEX.PHP |
| |
| PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS |
| LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS |
| REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO |
| THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE |
| THEREFORE SUBJECT TO PUBLIC DISCLOSURE. |
| |
| MEMBER OF BOAF: BUILDING OFFICIALS ASSOCIATION OF |
| FLORIDA SAVING LIVES AND PROPERTY SINCE 1953 |
| |