Plan Review Notes
Plan Review Notes For Permit 14090389
Permit Number 14090389
Review Stop B
Sequence Number 1
Notes
Date Text
2014-09-25 09:47:54BUILDING PLAN REVIEW
 PERMIT: 14090389
 ADD: 309 CLEMATIS ST
 CONT: TBD
 TEL: (561)296-7699 SCOTT SMITH
  
 2010 FLORIDA BUILDING CODE W
 * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION
 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013.
  
 2010 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: THURS. SEPT. 25TH/ 2014
 ACTION: DENIED
  
 1) PLEASE PROVIDE A EXIT PLAN FOR THE WHOLE BUILDING.
 PLEASE NOTE THIS IS A THREE STORY BUILDING A-2 / A3
 ASSEMBLY BUILDING WITH ONLY 2 ENCLOSED STAIRWELLS.
 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING
 CODE, CHAPTER 1, ADMINISTRATION,
 107.3.5 MINIMUM PLAN REVIEW CRITERIA FOR BUILDINGS. THE
 EXAMINATION OF THE DOCUMENTS BY THE BUILDING OFFICIAL
 SHALL INCLUDE THE FOLLOWING MINIMUM CRITERIA AND
 DOCUMENTS: A FLOOR PLAN;
 107.3.5.1 COMMERCIAL BUILDINGS:
 107.3.5.1.1 BUILDING
 OCCUPANCY GROUP AND SPECIAL OCCUPANCY REQUIREMENTS
 SHALL BE DETERMINED.
 MINIMUM TYPE OF CONSTRUCTION SHALL BE DETERMINED (SEE
 TABLE 503).
 OCCUPANCY LOAD/EGRESS REQUIREMENTS SHALL INCLUDE:
 OCCUPANCY LOAD
 GROSS
 NET
 MEANS OF EGRESS
 EXIT ACCESS
 EXIT
 EXIT DISCHARGE
 STAIRS CONSTRUCTION/GEOMETRY AND PROTECTION
 DOORS
  
 2) 2010 FBC-B 1016.1 DOES ALLOW FOR UNENCLOSED
 STAIRWELLS FOR 50 % OF EXITS BUT EXCEPTION # 3 ONLY
 ALLOWS THE EXIT ACCESS TRAVEL DISTANCE TO A MAXIMUM OF
 50 PERCENT OF THE EXITS IS PERMITTED TO BE MEASURED
 FROM THE MOST REMOTE POINT WITHIN A BUILDING TO AN EXIT
 USING UNENCLOSED EXIT ACCESS STAIRWAYS OR RAMPS WHEN
 CONNECTING A MAXIMUM OF TWO STORIES. THE TWO CONNECTED
 STORIES SHALL BE PROVIDED WITH AT LEAST TWO MEANS OF
 EGRESS. SUCH INTERCONNECTED STORIES SHALL NOT BE OPEN
 TO OTHER STORIES. THIS STAIR CONNECTS TO THE 3RD STORY
 A ROOF TOP ASSEMBLY FLOOR.
  
 3) NOTE THERE IS ALSO AN OPEN EXPIRED PERMIT FOR THE
 3RD STORY ROOFTOP ADDITION, NEVER ACHIEVED A
 CERTIFICATE OF OCUPANCY, PERMIT # 08060519.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION &
 REMOVE & REPLACE ANY PAGES AS NECESSARY. A TRANSMITTAL
 LETTER LISTING THE ORIGINAL REVIEW COMMENT NUMBER, WITH
 A DESCRIPTION OF THE REVISION MADE, IDENTIFYING THE
 SHEET OR SPECIFICATION PAGE WHERE THE CHANGES CAN BE
 FOUND WILL HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR
 YOUR ANTICIPATED COOPERATION.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
 DEVELOPMENT SERVICES HOME PAGE
 HTTP://WWW.CITYOFWPB.COM/CONSTRUCTION/INDEX.PHP
  
 PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS
 LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS
 REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO
 THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE
 THEREFORE SUBJECT TO PUBLIC DISCLOSURE.
  
 MEMBER OF BOAF: BUILDING OFFICIALS ASSOCIATION OF
 FLORIDA SAVING LIVES AND PROPERTY SINCE 1953
  