2014-09-16 11:20:01 | DATE: 9/16/2014 | | PROJECT: EVERNIA PLACE | | PERMIT#: 14090358 | | CODE: 2008 EDITION OF THE NEC | | 2010 EDITION OF THE FBC | | 2010 WPB AMENDMENTS TO THE FBC, CHAPTER 1, | | ADMINISTRATION, 2012 FBC SUPPLEMENTS. | | | | 1ST ELECTRICAL PLAN REVIEW | | ACTION: PROVISO | | | | 1) NEC 600.6(A)(1) | | EACH SIGN AND OUTLINE LIGHTING SYSTEM, OR FEEDER | | CIRCUIT OR BRANCH CIRCUIT SUPPLYING A SIGN OR OUT-LINE | | LIGHTING SYSTEM, SHALL BE CONTROLLED BY AN EXTERNALLY | | OPERABLE SWITCH OR CIRCUIT BREAKER THAT WILL OPEN ALL | | UNGROUNDED CONDUCTORS WITHIN SIGHT OF THE SIGN OR | | OUTLINE LIGHTING SYSTEM THAT IT CONTROLS. | | | | 2) FBC-E 505.2.4 | | ALL EXTERIOR LIGHTING NOT EXEMPTED BY FBC 505.1 SHALL | | HAVE AUTOMATIC CONTROLS TO TURN OFF AT DAYLIGHT OR WHEN | | NOT REQUIRED. CONTROLS SHALL BE PHOTOSENSOR & TIME | | CLOCK OR ASTRONOMICAL TIME SWITCH. ALL TIME SWITCHES | | SHALL BE CAPABLE OF RETAINING PROGRAMING DURING A LOSS | | OF POWER FOR A MINIMUM OF 10 HOURS. | | | | DAVID HAYES, ELECTRICAL PLANS EXAMINER, PX3421, | | 561-805-6717 OR [email protected] | | |
|