Plan Review Notes For Permit 14090353 |
Permit Number |
14090353 |
|
Review Stop |
B |
Sequence Number |
2 |
|
Notes |
Date |
Text |
2014-12-30 08:15:36 | ****PROVISO**** | | ****REVISION REQUIRED PRIOR TO FIRST INSPECTION**** | | | | | | SAMANTHA HILL | | BUILDING PLANS EXAMINER | | [email protected] | | 561-805-6724 | | | | SAME PLAN (SIGNED & SEALED ON 9/5/14) WAS SUBMITTED; | | THEREFORE, REVIEW PASSED WITH PROVISO, REVISION | | REQUIRED TO ADDRESS PREVIOUS COMMENT: | | | | 1. FASTENING PROPOSED SHOULD BE SPECIFIC: FASTENER | | TYPE, LENGTH OR MINIMUM EMBEDMENT, DIAMETER, MINIMUM | | NUMBER, FBC 1609. REVISE PLAN TO BE LESS VAGUE - | | "1/4-20 THROUGH BOLT APPROPRIATE FOR WEIGHT AND | | SURFACE." | | | | ALTHOUGH A THROUGH BOLT WAS SPECIFIED, GRAPHICALLY IT | | WAS NOT SHOWN AS EXTENDING THROUGH THE ENTIRE | | SUBSTRATE, SO THE BOLT WOULD THEREFORE REQUIRE A | | LENGTH. | | | | ALTERNATES (SCREWS, TOGGLE BOLTS) DID NOT INCLUDE | | LENGTH. | | | | REVISE PLAN TO INCLUDE FASTENER INFORMATION. | | | | | | | | | | | | | | | | | | |
|