Plan Review Notes
Plan Review Notes For Permit 14090353
Permit Number 14090353
Review Stop B
Sequence Number 1
Notes
Date Text
2014-10-14 18:30:20****CORRECTIONS****
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 1. FASTENING PROPOSED SHOULD BE SPECIFIC: FASTENER
 TYPE, LENGTH OR MINIMUM EMBEDMENT, DIAMETER, MINIMUM
 NUMBER, FBC 1609. REVISE PLAN TO BE LESS VAGUE -
 "1/4-20 THROUGH BOLT APPROPRIATE FOR WEIGHT AND
 SURFACE."
  
 ALTHOUGH A THROUGH BOLT WAS SPECIFIED, GRAPHICALLY IT
 WAS NOT SHOWN AS EXTENDING THROUGH THE ENTIRE
 SUBSTRATE, SO THE BOLT WOULD THEREFORE REQUIRE A
 LENGTH.
  
 WHAT DOES "APPROPRIATE FOR WEIGHT AND SURFACE" MEAN?
 SHOULDN'T THE ENGINEER SPECIFY THE FASTENER BASED ON
 JOB CONDITIONS? THIS ENGINEER'S PLANS ARE NOT NORMALLY
 THIS VAGUE.
  
 ALTERNATES (SCREWS, TOGGLE BOLTS) DID NOT INCLUDE
 LENGTH.
  
 REVISE PLAN TO INCLUDE REQUESTED INFORMATION.
  
  
  
  
  
  
  
  
  