Plan Review Notes
Plan Review Notes For Permit 14090347
Permit Number 14090347
Review Stop P
Sequence Number 2
Notes
Date Text
2014-10-30 13:13:59WPB AMEND. TO 2010 FBC SEC. 107.2.1.
 1) SUBMIT TWO COMPLETE COPIES OF THE MANUFACTURER'S
 SPECIFICATIONS/INSTALLATION MANUALS. THE INFORMATION
 YOU HAVE SUBMITTED IS INCOMPLETE.
 2) THE EXISTING PLUMBING RISER HAS A FLAT DRY VENT FOR
 THE MOST UPSTREAM CHAIR. THE VENT CONNECTION OF A DRY
 VENT TO A HORIZONTAL DRAIN SHALL CONNECT ABOVE THE
 CENTERLINE OF THE HORIZONTAL DRAIN PIPE. 2010 FPC
 SEC.905.3.
 3) THE PLUMBING INSTALLATION FOR THE ADDED CHAIRS
 CANNOT BE INSTALLED AS DESIGNED. CONSIDER A CIRCUIT
 VENT SYSTEM IN ACCORDANCE W/ 2010 FPC SEC.911.
  