Plan Review Notes For Permit 14090347 |
Permit Number |
14090347 |
|
Review Stop |
P |
Sequence Number |
2 |
|
Notes |
Date |
Text |
2014-10-30 13:13:59 | WPB AMEND. TO 2010 FBC SEC. 107.2.1. | | 1) SUBMIT TWO COMPLETE COPIES OF THE MANUFACTURER'S | | SPECIFICATIONS/INSTALLATION MANUALS. THE INFORMATION | | YOU HAVE SUBMITTED IS INCOMPLETE. | | 2) THE EXISTING PLUMBING RISER HAS A FLAT DRY VENT FOR | | THE MOST UPSTREAM CHAIR. THE VENT CONNECTION OF A DRY | | VENT TO A HORIZONTAL DRAIN SHALL CONNECT ABOVE THE | | CENTERLINE OF THE HORIZONTAL DRAIN PIPE. 2010 FPC | | SEC.905.3. | | 3) THE PLUMBING INSTALLATION FOR THE ADDED CHAIRS | | CANNOT BE INSTALLED AS DESIGNED. CONSIDER A CIRCUIT | | VENT SYSTEM IN ACCORDANCE W/ 2010 FPC SEC.911. | | | | PLUMBING PLAN REVIEW | | TIM LARGE | | CHIEF PLUMBING INSPECTOR | | 561-805-6692 | | [email protected] | | |
|