2014-12-22 16:58:14 | 2ND REVIEW: FBC 2010 |
| ROBERT MCDOUGAL, CBO |
| COMMERCIAL COMBINATION PLANS EXAMINER |
| (561) 805-6714 |
| [email protected] |
| |
| PLEASE ADDRESS THE ITEMS NOTED BELOW: |
| |
| BUILDING |
| |
| 1) ( REPEAT COMMENT ) THE WIND DESIGN DATA ON SHEET S-3 |
| OF THE PLANS IS INCORRECT. THE WIND SPEED IS 170 MPH |
| AND THE 2010 FBC REFERENCES ASCE 7-10. FBC R301.2.1 AND |
| FBC-R CHAPTER 43 THE LOAD SCHEDULE ON S-3 WAS NOT |
| CORRECTED. |
| |
| 2) ( REPEAT COMMENT ) SPECIFY HOW THE BALCONY FLOOR AND |
| WALLS WILL BE WATERPROOFED AND HOW THE RAIN WATER WILL |
| BE DISCHARGED FROM THE SLAB FLOOR OF THE BALCONY THAT |
| WILL BE BUILT INTO THE ROOF OF THE EXISTING STRUCTURE. |
| FBC 107.2.1 |
| |
| 3) SPECIFY THE SIZE OF THE SECTIONAL GARAGE DOOR ON THE |
| PLANS. FBC 107.2.1 THE OPENING WIDTH FOR THE GARAGE |
| DOOR WAS SPECIFIED ON THE PLANS AS 9'-8" WIDE AND |
| HEIGHT WAS NOT SPECIFIED. THE PRODUCT APPROVAL FOR THE |
| GARAGE DOOR THAT WAS SUBMITTED HAS A MAXIMUM WIDTH OF 9 |
| FEET. THE OPENING IS TOO LARGE FOR A 9 FOOT WIDE DOOR. |
| |
| 4) ( REPEAT COMMENT ) THE ENERGY CALCULATION FORM THAT |
| WAS SUBMITTED DOES NOT MATCH THE PLANS FOR THE EXTERIOR |
| WALL AND CEILING INSULATION. PLEASE CORRECT. THE PLANS |
| SPECIFY AN UNVENTED ATTIC WITH R-20 INSULATION APPLIED |
| UNDER THE ROOF DECK AND MINIMUM R-4.2 INSULATION ON THE |
| WALLS. THE ENERGY FORM HAS |
| |
| 5) ( REPEAT COMMENT ) SUBMIT TWO COPIES OF PRODUCT |
| APPROVALS AS REQUIRED BY DCA RULE 9N-3 THAT HAVE BEEN |
| REVIEWED AND APPROVED IN WRITING BY THE DESIGNER OF |
| RECORD. FBC 107.3.4.1 THE FOLLOWING PRODUCT APPROVALS |
| WERE MISSING OR INCOMPLETE: |
| - SLIDING GLASS DOORS |
| - OUT SWING METAL DOORS (#8 & #9) |
| - OUT SWING WOOD FRONT ENTRY DOOR (#7) |
| - THE BALCONY WATERPROOFING MATERIAL ( CONCRETE AND |
| WOOD DECKS ) |
| - THE 53 INCHES WIDE CASEMENT WINDOWS ( NOA NO. |
| 11-1114.22 HAS A MAXIMUM WIDTH LIMITATION OF 36 INCHES) |
| |
| 6) REVISE THE STRUCTURAL PLANS TO SHOW THE FOUNDATION, |
| COLUMNS AND BEAMS THAT ARE REQUIRED FOR THE |
| CANTILEVERED BALCONY BASED ON THE CALCULATIONS AND |
| DETAILS FROM THE ENGINEER. FBC 107.2.1 |
| |
| 7) THE SLOPE OF THE BALCONY ROOFS COVERED WITH MODIFIED |
| BITUMEN ROOFING ARE REQUIRED TO BE A MINIMUM OF 1/4" |
| PER FOOT. FBC-R905.11.1 THE PLAN SPECIFIES 1/8" PER |
| FOOT SLOPE. |
| |
| 8) THE MODIFIED ROOF COVERING NOTE ON SHEETS A-1 AND |
| S-2 HAS AN ARROW POINTING TO THE BALCONY WITH THE WOOD |
| DECK, BUT INCORRECTLY STATES CONCRETE DECK. THE |
| CANTILEVER CONCRETE DECK IS THE ONE ON THE OPPSITE SIDE |
| OF THE SECOND FLOOR. FBC 107.2.1 |
| |
| IN ORDER TO REDUCE PLAN REVIEW TIME, PLEASE PROVIDE A |
| RESPONSE LETTER INDICATING HOW EACH REVIEW COMMENT WAS |
| ADDRESSED. |
| |
| |
| |
| |