Plan Review Notes
Plan Review Notes For Permit 14090266
Permit Number 14090266
Review Stop G
Sequence Number 1
Notes
Date Text
2014-09-13 06:06:13WPB ADMIN. AMEND. TO 2010 FBC SEC.107.2.1.
 1) SUBMIT A GAS PIPNG RISER THAT CLEARLY REFLECTS THE
 SCOPE OF WORK TO BE DONE.
 2) SHOW ALL THE APPLIANCES ON THE GAS RISER AND SHOW
 THE BTU LOAD FOR EACH APPLIANCE.
 3) SHOW THE DISTANCE FROM THE POINT OF GAS DELIVERY TO
 THE MOST REMOTE OUTLET.
 4) THE PLANS LIST 11 APPLIANCES BUT ONLY 3 SHUTOFF
 VALVES ARE SHOWN ON THE GAS RISER.
 5) SHOW THE PIPE SIZES OF ALL THE PIPING ON THE GAS
 RISER
 6) SUBMIT COPIES OF THE GAS SIZING TABLES FOR THE
 GALVANIZED PIPING AND THE CSST TUBING.
 7) SUBMIT CLEAR AND LEGIBLE COPIES OF THE MANUF. SHEETS
 FOR THE GAS DRYERS.
 8) THE DESCRIPTION OF WORK ON YOUR APPLICATION STATES
 "CONNECT TO EXISTING FIXTURES" YET YOU HAVE SUBMITTED
 SPEC SHEETS FOR WHAT APPEARS TO BE NEW EQUIPMENT.
 CLARIFY.
 9) SHOW ON THE FLOOR PLAN WHERE THE UNDERGROUND GAS
 PIPING IS TO BE ELIMINATED AND HOW THIS PIPING WILL BE
 ABANDONED.