Plan Review Notes For Permit 14090266 |
Permit Number |
14090266 |
|
Review Stop |
G |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2014-09-13 06:06:13 | WPB ADMIN. AMEND. TO 2010 FBC SEC.107.2.1. | | 1) SUBMIT A GAS PIPNG RISER THAT CLEARLY REFLECTS THE | | SCOPE OF WORK TO BE DONE. | | 2) SHOW ALL THE APPLIANCES ON THE GAS RISER AND SHOW | | THE BTU LOAD FOR EACH APPLIANCE. | | 3) SHOW THE DISTANCE FROM THE POINT OF GAS DELIVERY TO | | THE MOST REMOTE OUTLET. | | 4) THE PLANS LIST 11 APPLIANCES BUT ONLY 3 SHUTOFF | | VALVES ARE SHOWN ON THE GAS RISER. | | 5) SHOW THE PIPE SIZES OF ALL THE PIPING ON THE GAS | | RISER | | 6) SUBMIT COPIES OF THE GAS SIZING TABLES FOR THE | | GALVANIZED PIPING AND THE CSST TUBING. | | 7) SUBMIT CLEAR AND LEGIBLE COPIES OF THE MANUF. SHEETS | | FOR THE GAS DRYERS. | | 8) THE DESCRIPTION OF WORK ON YOUR APPLICATION STATES | | "CONNECT TO EXISTING FIXTURES" YET YOU HAVE SUBMITTED | | SPEC SHEETS FOR WHAT APPEARS TO BE NEW EQUIPMENT. | | CLARIFY. | | 9) SHOW ON THE FLOOR PLAN WHERE THE UNDERGROUND GAS | | PIPING IS TO BE ELIMINATED AND HOW THIS PIPING WILL BE | | ABANDONED. |
|