2014-09-26 14:37:41VOLUME # 4: WPB AMEND. TO 2010 FBC SEC. 107.2.1.
  
 1) ALL PLANS AND DOCUMENTS SHALL BE SIGNED AND SEALED
 BY THE DESIGN PROFESSIONAL OF RECORD PER THE FLA.
 ADMIN. CODE RULE 61G15-23.002, FL. STATUTES 481.221,
 481.321. THIS APPLIES TO ALL VOLUMES.
 2) SHT. C-GEN-01 - IDENTIFY ALL THE BUILDINGS ON THE
 SITE PLAN.
 3) SUBMIT A COPY OF THE JOB SPECIFICATIONS FOR REVIEW.
 SPECIFICATIONS SHALL BE SIGNED & SEALED BY THE EOR PER
 F.A.C 61G15-23.002
 4) THE FOLLOWING PAGES ARE MISSING FROM THE VOLUME # 4
 ROLL OF PLANS: C-PGD-13, C-PGD-14, C-PGD-16, C-YPP-20,
 C-YPP-21.
 5) INDICATE ON THE PLANS THE TYPE OF MATERIAL BEING
 USED FOR THE NEW POTABLE WATER SYSTEM, THE SANITARY
 SYSTEM, AND THE STORMWATER SYSTEM.
 6) INDICATE THE MAKE, MODEL, AND SIZES OF THE BACKFLOW
 PREVENTERS ON THE SYSTEMS.
 7) SHOW WHERE THE RUNOFF FROM THE ROOF
 SCUPPERS/DOWNSPOUTS WILL BE DIRECTED.
 8) SHT, M-ADF-09 - SHOW THE SIZE OF THE LP TANK, IF IT
 IS ABOVE OR BELOW GROUND, THE DISTANCE AWAY FROM THE
 BUILDING WALL AND ANY BUILDING OPENINGS, INDICATE ANY
 BTU LOAD ON TH SYSTEM AND SUBMIT A GAS PIPING RISER
 DIAGRAM IN ACCORDANCE WITH THE APPROPRIATE SIZING TABLE
 IN THE 2010 FLORIDA FUEL GAS CODE.AND NFPA 58.
 9) THE LP TANK SHALL BE PROPERLY ANCHORED TO WITHSTAND
 A 170 MPH WIND LOAD. SUBMIT CALULATIONS AND ANCHORING
 DETAILS FOR THE TANK FOR COMPLIANCE WITH THE FLORIDA
 FUEL GAS CODE SEC. 301.10.
 10) SHT. M-ADF-31 - SHOW THE HEIGHT OF THE 18 INCH
 FLUES ABOVE THE ROOF SURFACE. COMPLY W/FBC, FUEL GAS
 CHAPTER 5 & NFPA 54. THE FLUES SHALL BE ANCHORED TO
 WITHSTAND 170 MPH WINDLOAD.
 11) SHT. M-DEW-12 - LOWER ELEVATION PLAN - NOTE STATES
 "FOR ENLARGED PLAN SEE DWG. M-DEW-05." THERE IS NO
 ENLARGED PLAN ON THE REFERENCED SHEET.
 12) SHT. M-DEW-13 - THE WOMEN'S AND MEN'S
 LOCKERS/SHOWERS SHALL BE HANDICAPPED ACCESSIBLE PER THE
 FL.BUILDING CODE, ACCESSIBILITY, SEC.213.2.
 13)SHT.M-DEW-15 - THE ENLARGED PIPING PLAN BELOW ELEV.
 20.00 - REFERS TO DRAIN PROFILE ON DWG.M-DEW-09 BUT
 THERE IS NO DRAIN PROFILE ON THIS SHEET. CLARIFY.
 14) DWG. M-DEW-19 - 8" & 6" DRAIN PIPE PROFILE - REFERS
 TO SEC. "C" ON M-DEW-08 BUT THERE IS NO SUCH SECTION ON
 THAT DRAWING. CLARIFY.
 15) DWG. M-DEW-20 - SECTION "F" REFERS TO PWS & PW .
 THESE ACRONYMS ARE NOT LISTED IN THE DRAWINGS. THIS
 APPEARS TO BE TYPO ERROR. CLARIFY.
 16) DWG. M-OCS-01 - THE PIPING PLAN STATES "FOR
 CONTINUATION SEE CIVIL DRAWINGS...", SEE STRUCTURAL
 DRAWINGS,, ETC. PLEASE PROVIDE THE SPECIFIC DRAWING
 WHERE THE CONTINUATION OF THE LINES CAN BE REVIEWED.
 THIS APPLIES TO DRAWING M-OCS-02 ALSO.
  
 VOLUME # 5
  
 17) DWG.A-MEB-01 - THE PLAN STATES THAT AN ACCESSIBLE
 RESTROOM IS LOCATED IN AN ADJACENT BUILDING WITHIN 500
 FEET. IDENTIFY THE BUILDING AND THE DISTANCE WHERE THE
 FACILITIES ARE LOCATED. FL. PLBG. CODE SEC.403.3.2.
 18) DWG.A-MEB-03 - INDICATE THE SQUARE FOOTAGE OF THE
 ROOF THAT IS BEING DRAINED BY EACH SCUPPER.COMPLY W/
 2010 FBC, PLUMBING, TABLE 1106.7 FOR THE SCUPPERS AND
 TABLE 1106.2(2) FOR THE DOWNSPOUTS.
 19) DWG. A-ADF-01 - STATES AN ACCESSIBLE RESTROOM IS IN
 AN ADJACENT BUILDING WITHIN 500 FT.IDENTIFY THE
 BUILDING AND THE DISTANCE WHERE THE FACILITIES ARE
 LOCATED. FBC, PLUMBING, SEC.403.3.2. REMOVE NOTE #3
 THAT REFERS TO BUSINESS AND MERCANTILE OCCUPANCIES.
 20) SHT.A-ADF-06 - DETAIL #2 SHOWS VERTICAL GRAB BARS.
 GRAB BARS SHALL BE INSTALLED IN A HORIZONTAL POSITION
 PER THE FBC, ACCESSIBILITY, SEC.609.4. SEE ALSO DWG.
 A-FOG-01.
 21) DWG. A-ADF-06 - DETAIL #1 - SHOW THE DISTANCE TO
 THE BOTTOM OF THE LAVATORY. COMPLY W/FBC,
 ACCESSIBILITY, SEC. 305, 606.
 22) DWG. A-ADF-06 - DETAIL #2 - THE TOILET PAPER
 DISPENSER SHALL BE LOCATED 7 INCHES MINIMUM AND 9
 INCHES MAXIMUM IN FRONT OF THE WATER CLOSET MEASURED TO
 THE CENTERLINE OF THE DISPENSER.FAC SEC.604.7.
 23) DWG.A-ADF-06 - A DRINKING FOUNTAIN IS REQUIRED IN
 THIS FACILITY PER THE FBC, PLUMBING, TABLE 403.1 (SEE
 FOOTNOTE "F' FOR EXCEPTION). IF INSTALLED, IT SHALL BE
 A MINIMUM OF TWO AS REQUIRED BY THE 2010 FBC,
 ACCESSIBILITY, SEC.211.2.
 24) SHTS,A-ADF-07 THRU A-ADF-10 - SHOW THE SQUARE
 FOOTAGE OF THE ROOF DRAINED BY EACH SCUPPER AND
 DOWNSPOUT PER FBC, PLUMBING TABLE 1106.2(2) & 1106.7.
 25) DWGS.A-DEW-03 & A-DEW-05 - A MINIMUM OF 2 DRINKING
 FOUNTAINS ARE REQUIRED IN THESE LOCATIONS PER THE 2010
 FBC, ACCESSIBILITY, SEC. 211.2.
 26) SHT.A-DEW-03 - SUBMIT DETAILS OF THE
 CONTROLS/SHOWER HEAD FOR THE HANDICAPPED ROLL-IN SHOWER
 IN T.R. # 104. CLEARLY IDENTIFY THIS AS A HANDICAP
 ACCESSIBLE SHOWER ON THE PLAN.2010 FBC, ACCESSIBILITY
 SECS.308,309, 608.6. SHOW THE WIDTH OF THE SHOWER IN
 T.R.#104 ON THE PLAN.
 27) DWG. A-DEW-05 - THE SINK IN THE BREAK ROOM SHALL BE
 HANDICAPPED ACCESSIBLE. 2010 FBC, ACCESSIBILITY,
 SEC.212.1, 606.
 28) DWG.A-DEW-05 - THE MEN'S AND WOMEN'S LOCKERS/SHOWER
 ROOMS SHALL BE HANDICAPPED ACCESSIBLE AND COMPLY W/THE
 FBC, ACCESSIBILITY, SECS.213.1.
 29) DWG. A-DEW-26 - CLEARLY SHOW THE WIDTH OF ALL THE
 TOILET STALLS. COMPLY W/FBC,ACCESSIBILITY, SEC.604.8.2.
 30) DWG.A-DEW-26 - DETAIL #9 - THE TOILET PAPER
 DISPENSER SHALL BE 48" MAX. ABOVE THE FINISHED FLOOR.
 FBC, ACCESSIBILITY SEC.604.7
 31) DWG.A-DEW-26 - DETAIL #A-10 - THE RIM OF THE URINAL
 SHALL BE 17" MAXIMUM ABOVE THE FINISHED FLOOR.FBC,
 ACCESSIBILITY SEC.605.2.
 32) DWG. A-DEW-26 - SUBMIT A PLAN VIEW OF THE
 ACCESSIBLE TRANSFER TYPE SHOWER (36" X 36") WITH THE
 SEAT. COMPLY W/ SEC.608.4, 604.8.1.6, 610. CONTROLS
 SHALL BE LOCATED IN COMPLIANCE WITH SEC.608.5.
 33) DWG. A-FOG-01 - THE SINK IN THE OFFICE SHALL COMPLY
 WITH SEC.212.1 & 606 OF THE FBC, ACCESSIBILITY.
 34) DWG. A-FOG-02- SHOW THE SQUARE FOOTAGE OF THE ROOF
 THAT IS DRAINED BY EACH SCUPPER AND DOWNSPOUT.COMPLY
 W/FBC PLUMBING TABLE 1106.2(2), 1106.7.
  
 VOLUME # 6
 NO COMMENTS
  
 VOLUME #7
  
 35) ALL WASTTE STACKS TO HAVE CLEANOUTS IN BASE OF
 STACK. FBC,PLUMBING, 708.3.4.
 36) ALL HOSE BIBBS AND HOSE REELS TO HAVE SHUTOFF
 VALVES PER SEC.606.2 OF FBC, PLUMBING,
 37) SIZE ALL SECTIONS OF THE SANITARY AND VENTS ON ALL
 THE RISER DIAGRAMS.SIZE ALL SECTION OF THE WATER MAIN
 TO THE LOCKER/SHOWERS ON LEVEL 42.00. THE WATER RISERS
 FROM THE LOWER LEVEL (20.00' ) TO THE INTERMEDIATE
 LEVEL (42.00 ) SHALL BE EQUIPPED WITH FULL OPEN VALVES
 PER SEC.606.1. 2010 FBC, PLUMBING.
 38) SUBMIT SPECIFICATIONS FOR THE TANKLESS WATER
 HEATER. WPB AMEND. TO 2010 FBC SEC.107.2.1.
 39) DWG.P-DEW-05 - THE CONNECTION OF THE ELEVATOR SUMP
 TO THE DRAINAGE SYSTEM SHALL COMPLY W/FBC, PLUMBING,
 SEC.712.3.5.
 40) SUBMIT MANUF. SPECIFICATION SHEETS FOR THE STANCOR
 OIL MINDER PUMP. WPB AMEND. TO 2010 FBC SEC.107.2.1.
 41) A CHECK VALVE AND FULL OPEN VALVE LOCATED ON THE
 DISCHARGE SIDE OF THE CHECK VALVE SHALL BE INSTALLED IN
 THE PUMP/ EJECTOR DISCHARGE PIPING AND SHALL BE
 INSTALLED PER 2010 FBC,PLUMBING, SEC.712.2. CONNECTION
 TO THE DRAINAGE SYSTEM SHALL COMPLY WITH SEC.712.3.5.
 42) A VACUUM RELIEF VALVE IS REQD. ON THE WATER HEATER
 IN THE SEPTAGE FOG ATTENDANT BUILDING PER FBC,
 PLUMBING, SEC. 504.2.
 43) DWG.P-FOG-01 - SHOW THE REQUIRED CLEAR FLOOR SPACE
 FOR THE DRINKING FOUNTAINS IN ACCORRDANCE WITH 2010
 FBC, ACCESSIBILITY, SEC.602, 305, 306.
  