Plan Review Notes
Plan Review Notes For Permit 14090256
Permit Number 14090256
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2014-09-18 17:02:194395 EASLEY DRIVE
 PERMIT #14090256
 90% SUBMITTAL REVIEW COMMENTS - FIRE DEPARTMENT
  
 VOLUME 4 REVIEW:
 SHEET C-YPP-22: PROVIDE A SEPARATE DOMESTIC WATER LINE
 TAP FROM THE FIRE LINE TAP OR INDICATE THE GREATEST
 DOMESTIC WATER DEMAND TO BE EXPECTED SO THIS GPM DEMAND
 CAN BE ACCOUNTED FOR IN THE SPRINKLER SYSTEM HYDRAULIC
 CALCULATIONS.
  
 VOLUME 5 REVIEW:
 UPDATE THE CODE LIST TO REFERENCE THE 2010 EDITION OF
 THE FLORIDA FIRE PREVENTION CODE WHICH CONTAINS THE
 2009 EDITION OF BOTH NFPA 1 AND NFPA 101 WITH FLORIDA
 AMENDMENTS.
  
 SHEET A-DEW-05: FIRE RATED WALL INDICATORS ARE MISSING
 FROM STAIR #306, ELEVATOR, AND WALL ADJACENT TO
 EXTERIOR STAIR.
  
 SHEET A-DEW-28: OUTSIDE STAIRS MORE THAN 36 FEET ABOVE
 FINISHED GROUND LEVEL SHALL BE PROVIDED WITH OPAQUE
 VISUAL OBSTRUCTION NOT LESS THAN 48-INCHES IN HEIGHT TO
 ACCOMODATE PERSONS HAVING A FEAR OF HIGH PLACES PER
 NFPA 101 SECTION 7.2.2.6.2.
  
 SHEET A-DEW-25: DOOR #300 REFERENCES A NOTE #4 WHICH
 DOES NOT EXIST.
  
 GENERAL: PER NFPA 101 SECTION 8.3.2.4, EACH FIRE
 BARRIER SHALL BE PERMANENTLY IDENTIFIED WITH SIGNS OR
 STENCILING READING FIRE BARRIER-PROTECT ALL OPENINGS.
 CHARACTERS SHALL BE AT LEAST 4-INCHES IN HEIGHT AND
 HALF-INCH IN WIDTH. IDENTIFICATION SHALL BE SPACED NOT
 MORE THAN 15 FEET ON CENTER.
  
 GENERAL: PROVIDE TACTILE SIGNAGE AT ALL REQUIRED EXIT
 DOORS WITH EXIT SIGNS.
  
 GENERAL: PER SECTION 10.12.1.2 (NFPA 1), PROVIDE
 BUILDING ADDRESSES OR NAMES THAT ARE VISIBLE FROM THE
 STREET. NUMBERS/LETTERS SHALL BE ATTACHED TO THE
 BUILDING AND BE AT LEAST SIX-INCHES IN HEIGHT WITH
 1-INCH STROKE AND SHALL CONTRAST THE BACKGROUND.
  
 GENERAL: PROVIDE A PERMANENT WEATHERPROOF DIAMOND
 PLACARD PER NFPA 704 INDICATING THE HEALTH,
 FLAMMABILITY AND REACTIVITY RATING OF THE HAZARDOUS
 MATERIALS.
  
 ELECTRICAL ROOMS: PER NFPA 70 ARTICLE 110.26(C)(3)
 PERSONNEL DOORS. WHERE CONDUCTORS AND EQUIPMENT USED ON
 CIRCUITS ARE OVER 600 VOLTS OR EQUIPMENT IS RATED 1200
 A OR MORE THAT CONTAINS OVERCURRENT DEVICES, SWITCHING
 DEVICES, OR CONTROL DEVICES IS INSTALLED AND THERE IS A
 PERSONNEL DOOR(S) INTENDED FOR ENTRANCE TO AND EGRESS
 FROM THE WORKING SPACE LESS THAN 25 FEET FROM THE
 NEAREST EDGE OF THE WORKING SPACE, THE DOOR(S) SHALL
 OPEN IN THE DIRECTION OF EGRESS AND BE EQUIPPED WITH
 PANIC BARS, PRESSURE PLATES, OR OTHER DEVICES THAT ARE
 NORMALLY LATCHED BUT OPEN UNDER SIMPLE PRESSURE.
 CONFIRM CIRCUITS ARE NOT OVER 600 VOLTS AND EQUIPMENT
 IS NOT RATED 1200 A OR MORE.
  
 TOXIC FUMES: MOTOR VEHICLES WILL BE OPERATED IN THE
 ENCLOSED TRUCK BAYS. HOW WILL CARBON MONOXIDE LEVELS BE
 MAINTAINED BELOW ACCEPTABLE THRESHOLDS PER 502.14 M?
  
 VOLUME 6 REVIEW:
  
 VOLUME 7 REVIEW:
 SHEET FP-DEW-04: PER FBC SECTION 905.1, A CLASS I
 STANDPIPE SYSTEM SHALL BE PROVIDED IN ALL NEW BUILDINGS
 IN WHICH THE HIGHEST FLOOR IS MORE THAN 30 FEET ABOVE
 FIRE DEPARTMENT VEHICLE ACCESS.
  
 WESLEY JOLIN
 ASSISTANT FIRE MARSHAL
 FIRE INVESTIGATOR & INSPECTOR
 WEST PALM BEACH FIRE RESCUE
 [email protected]
 (561) 805-6730
  


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved