Date |
Text |
2014-09-18 17:02:19 | 4395 EASLEY DRIVE |
| PERMIT #14090256 |
| 90% SUBMITTAL REVIEW COMMENTS - FIRE DEPARTMENT |
| |
| VOLUME 4 REVIEW: |
| SHEET C-YPP-22: PROVIDE A SEPARATE DOMESTIC WATER LINE |
| TAP FROM THE FIRE LINE TAP OR INDICATE THE GREATEST |
| DOMESTIC WATER DEMAND TO BE EXPECTED SO THIS GPM DEMAND |
| CAN BE ACCOUNTED FOR IN THE SPRINKLER SYSTEM HYDRAULIC |
| CALCULATIONS. |
| |
| VOLUME 5 REVIEW: |
| UPDATE THE CODE LIST TO REFERENCE THE 2010 EDITION OF |
| THE FLORIDA FIRE PREVENTION CODE WHICH CONTAINS THE |
| 2009 EDITION OF BOTH NFPA 1 AND NFPA 101 WITH FLORIDA |
| AMENDMENTS. |
| |
| SHEET A-DEW-05: FIRE RATED WALL INDICATORS ARE MISSING |
| FROM STAIR #306, ELEVATOR, AND WALL ADJACENT TO |
| EXTERIOR STAIR. |
| |
| SHEET A-DEW-28: OUTSIDE STAIRS MORE THAN 36 FEET ABOVE |
| FINISHED GROUND LEVEL SHALL BE PROVIDED WITH OPAQUE |
| VISUAL OBSTRUCTION NOT LESS THAN 48-INCHES IN HEIGHT TO |
| ACCOMODATE PERSONS HAVING A FEAR OF HIGH PLACES PER |
| NFPA 101 SECTION 7.2.2.6.2. |
| |
| SHEET A-DEW-25: DOOR #300 REFERENCES A NOTE #4 WHICH |
| DOES NOT EXIST. |
| |
| GENERAL: PER NFPA 101 SECTION 8.3.2.4, EACH FIRE |
| BARRIER SHALL BE PERMANENTLY IDENTIFIED WITH SIGNS OR |
| STENCILING READING FIRE BARRIER-PROTECT ALL OPENINGS. |
| CHARACTERS SHALL BE AT LEAST 4-INCHES IN HEIGHT AND |
| HALF-INCH IN WIDTH. IDENTIFICATION SHALL BE SPACED NOT |
| MORE THAN 15 FEET ON CENTER. |
| |
| GENERAL: PROVIDE TACTILE SIGNAGE AT ALL REQUIRED EXIT |
| DOORS WITH EXIT SIGNS. |
| |
| GENERAL: PER SECTION 10.12.1.2 (NFPA 1), PROVIDE |
| BUILDING ADDRESSES OR NAMES THAT ARE VISIBLE FROM THE |
| STREET. NUMBERS/LETTERS SHALL BE ATTACHED TO THE |
| BUILDING AND BE AT LEAST SIX-INCHES IN HEIGHT WITH |
| 1-INCH STROKE AND SHALL CONTRAST THE BACKGROUND. |
| |
| GENERAL: PROVIDE A PERMANENT WEATHERPROOF DIAMOND |
| PLACARD PER NFPA 704 INDICATING THE HEALTH, |
| FLAMMABILITY AND REACTIVITY RATING OF THE HAZARDOUS |
| MATERIALS. |
| |
| ELECTRICAL ROOMS: PER NFPA 70 ARTICLE 110.26(C)(3) |
| PERSONNEL DOORS. WHERE CONDUCTORS AND EQUIPMENT USED ON |
| CIRCUITS ARE OVER 600 VOLTS OR EQUIPMENT IS RATED 1200 |
| A OR MORE THAT CONTAINS OVERCURRENT DEVICES, SWITCHING |
| DEVICES, OR CONTROL DEVICES IS INSTALLED AND THERE IS A |
| PERSONNEL DOOR(S) INTENDED FOR ENTRANCE TO AND EGRESS |
| FROM THE WORKING SPACE LESS THAN 25 FEET FROM THE |
| NEAREST EDGE OF THE WORKING SPACE, THE DOOR(S) SHALL |
| OPEN IN THE DIRECTION OF EGRESS AND BE EQUIPPED WITH |
| PANIC BARS, PRESSURE PLATES, OR OTHER DEVICES THAT ARE |
| NORMALLY LATCHED BUT OPEN UNDER SIMPLE PRESSURE. |
| CONFIRM CIRCUITS ARE NOT OVER 600 VOLTS AND EQUIPMENT |
| IS NOT RATED 1200 A OR MORE. |
| |
| TOXIC FUMES: MOTOR VEHICLES WILL BE OPERATED IN THE |
| ENCLOSED TRUCK BAYS. HOW WILL CARBON MONOXIDE LEVELS BE |
| MAINTAINED BELOW ACCEPTABLE THRESHOLDS PER 502.14 M? |
| |
| VOLUME 6 REVIEW: |
| |
| VOLUME 7 REVIEW: |
| SHEET FP-DEW-04: PER FBC SECTION 905.1, A CLASS I |
| STANDPIPE SYSTEM SHALL BE PROVIDED IN ALL NEW BUILDINGS |
| IN WHICH THE HIGHEST FLOOR IS MORE THAN 30 FEET ABOVE |
| FIRE DEPARTMENT VEHICLE ACCESS. |
| |
| WESLEY JOLIN |
| ASSISTANT FIRE MARSHAL |
| FIRE INVESTIGATOR & INSPECTOR |
| WEST PALM BEACH FIRE RESCUE |
| [email protected] |
| (561) 805-6730 |
| |