 PROJECT: WPB WATER RECLAMATION FACILITY
 PERMIT#: 14090256
 CODE: 2008 EDITION OF THE NEC
 2010 EDITION OF THE FBC
 2010 WPB AMENDMENTS TO THE FBC, CHAPTER 1,
 ADMINISTRATION, 2012 FBC SUPPLEMENTS.
  
 ELECTRICAL PLAN REVIEW
 ACTION: DENIED
  
 1) SUBMITTAL DRAWINGS ARE INCOMPLETE AND UNSIGNED. ALL
 INFORMATION, DRAWINGS, SPECIFICATIONS AND ACCOMPANYING
 DATA SHALL BEAR THE NAME AND SIGNATURE OF THE PERSON
 RESPONSIBLE FOR THE DESIGN. WPB AMENDMENTS TO FBC
 107.2.1
  
 2) INDICATE SIZE, TYPE AND BURIAL DEPTH OF GROUND LOOP
 CONDUCTOR AT DEWATERING BUILDING. NEC 250.50
  
 3) LIGHTING FOR ALL EXTERIOR APPLICATIONS NOT EXEMPTED
 IN SECTION 505.1 SHALL HAVE AUTOMATIC CONTROLS CAPABLE
 OF TURNING OFF EXTERIOR LIGHTING WHEN SUFFICIENT
 DAYLIGHT IS AVAILABLE OR WHEN THE LIGHTING IS NOT
 REQUIRED DURING NIGHTTIME HOURS. LIGHTING NOT
 DESIGNATED FOR DUSK-TO-DAWN OPERATION SHALL BE
 CONTROLLED BY EITHER A COMBINATION OF A PHOTOSENSOR AND
 A TIME SWITCH, OR AN ASTRONOMICAL TIME SWITCH. FBC
 505.2.4 EXTERIOR LIGHTING CONTROLS.
  
 4) WIND LOADS ON EVERY BUILDING OR STRUCTURE (LIGHT
 POLES) SHALL BE DETERMINED IN ACCORDANCE WITH CHAPTERS
 26 THROUGH 30 OF ASCE 7 OR THE PROVISIONS OF THE
 ALTERNATE ALL HEIGHTS METHOD IN FBC SECTION 1609.6.
 WIND SHALL BE ASSUMED TO COME FROM ANY HORIZONTAL
 DIRECTION AND WIND PRESSURES SHALL BE ASSUMED TO ACT
 NORMAL TO THE SURFACE CONSIDERED. PROVIDE WIND LOA
 CALCULATIONS INCLUDING POLE TYPE, LENGTH AND LUMINAIRE
 TYPE AND QUANTITY. FBC SECTION 1609.6
  
 5) SEPARATE PERMIT APPLICATIONS ACCOMPANIED BY
 MANUFACTURERS EQUIPMENT SUBMITTALS, AND SHOP DRAWINGS
 ARE REQUIRED FOR FIRE ALARM, SECURITY, CCTV, AND
 DATA/COM SYSTEM CABLING AS APPLICABLE.
 WPB AMENDMENTS TO FBC 107.2.1
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. SEE LINK:
 HTTP://WPB.ORG/DEVELOPMENT/WP-CONTENT/UPLOADS/SITES/33/
 2013/09/APPLICATION_RESUBMITTAL_FORM_04132010.PDF
  
 ADDITIONALLY, PLEASE INSERT CORRECTED PAGES INTO
 SUBMITTAL PACKAGE AND LEAVE THE PREVIOUSLY REVIEWED
 SHEETS FOR COMPARATIVE REVIEW.
  
 DAVID HAYES, ELECTRICAL PLANS EXAMINER, PX3421,
 561-805-6717 OR [email protected]
  