| PROJECT: WPB WATER RECLAMATION FACILITY |
| PERMIT#: 14090256 |
| CODE: 2008 EDITION OF THE NEC |
| 2010 EDITION OF THE FBC |
| 2010 WPB AMENDMENTS TO THE FBC, CHAPTER 1, |
| ADMINISTRATION, 2012 FBC SUPPLEMENTS. |
| |
| ELECTRICAL PLAN REVIEW |
| ACTION: DENIED |
| |
| 1) SUBMITTAL DRAWINGS ARE INCOMPLETE AND UNSIGNED. ALL |
| INFORMATION, DRAWINGS, SPECIFICATIONS AND ACCOMPANYING |
| DATA SHALL BEAR THE NAME AND SIGNATURE OF THE PERSON |
| RESPONSIBLE FOR THE DESIGN. WPB AMENDMENTS TO FBC |
| 107.2.1 |
| |
| 2) INDICATE SIZE, TYPE AND BURIAL DEPTH OF GROUND LOOP |
| CONDUCTOR AT DEWATERING BUILDING. NEC 250.50 |
| |
| 3) LIGHTING FOR ALL EXTERIOR APPLICATIONS NOT EXEMPTED |
| IN SECTION 505.1 SHALL HAVE AUTOMATIC CONTROLS CAPABLE |
| OF TURNING OFF EXTERIOR LIGHTING WHEN SUFFICIENT |
| DAYLIGHT IS AVAILABLE OR WHEN THE LIGHTING IS NOT |
| REQUIRED DURING NIGHTTIME HOURS. LIGHTING NOT |
| DESIGNATED FOR DUSK-TO-DAWN OPERATION SHALL BE |
| CONTROLLED BY EITHER A COMBINATION OF A PHOTOSENSOR AND |
| A TIME SWITCH, OR AN ASTRONOMICAL TIME SWITCH. FBC |
| 505.2.4 EXTERIOR LIGHTING CONTROLS. |
| |
| 4) WIND LOADS ON EVERY BUILDING OR STRUCTURE (LIGHT |
| POLES) SHALL BE DETERMINED IN ACCORDANCE WITH CHAPTERS |
| 26 THROUGH 30 OF ASCE 7 OR THE PROVISIONS OF THE |
| ALTERNATE ALL HEIGHTS METHOD IN FBC SECTION 1609.6. |
| WIND SHALL BE ASSUMED TO COME FROM ANY HORIZONTAL |
| DIRECTION AND WIND PRESSURES SHALL BE ASSUMED TO ACT |
| NORMAL TO THE SURFACE CONSIDERED. PROVIDE WIND LOA |
| CALCULATIONS INCLUDING POLE TYPE, LENGTH AND LUMINAIRE |
| TYPE AND QUANTITY. FBC SECTION 1609.6 |
| |
| 5) SEPARATE PERMIT APPLICATIONS ACCOMPANIED BY |
| MANUFACTURERS EQUIPMENT SUBMITTALS, AND SHOP DRAWINGS |
| ARE REQUIRED FOR FIRE ALARM, SECURITY, CCTV, AND |
| DATA/COM SYSTEM CABLING AS APPLICABLE. |
| WPB AMENDMENTS TO FBC 107.2.1 |
| |
| WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| RE-SUBMITTAL FORM. SEE LINK: |
| HTTP://WPB.ORG/DEVELOPMENT/WP-CONTENT/UPLOADS/SITES/33/ |
| 2013/09/APPLICATION_RESUBMITTAL_FORM_04132010.PDF |
| |
| ADDITIONALLY, PLEASE INSERT CORRECTED PAGES INTO |
| SUBMITTAL PACKAGE AND LEAVE THE PREVIOUSLY REVIEWED |
| SHEETS FOR COMPARATIVE REVIEW. |
| |
| DAVID HAYES, ELECTRICAL PLANS EXAMINER, PX3421, |
| 561-805-6717 OR [email protected] |
| |