2014-10-09 06:51:57 | BUILDING PLAN REVIEW |
| PERMIT: 14090256 |
| ADD: 4395 EASLEY DR |
| CONT: TBD |
| TEL: (561)683-3113 JOHN CARNIES |
| |
| 2010 FLORIDA BUILDING CODE W |
| * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA |
| BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION |
| 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013. |
| |
| 2010 EXISTING BUILDING CODE LEVEL II 701.3 |
| COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, |
| SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS |
| OF THE FLORIDA BUILDING CODE, BUILDING. |
| |
| 1ST REVIEW |
| DATE: THURS. OCT. 09/ 2014 |
| ACTION: DENIED |
| |
| NOTE: ALL REVIEWS WILL BE COMPLETED UNDER THIS MASTER/ |
| PRIME PERMIT BUT INDIVIDUAL PERMITS WILL BE REQUIRED |
| FOR EACH STRUCTURE FOR RECORD AND INSPECTION PURPOSES. |
| 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING |
| CODE, CHAPTER 1, ADMINISTRATION 107.2.1.4 THE BUILDING |
| OFFICIAL MAY ESTABLISH THROUGH DEPARTMENTAL POLICY, |
| OTHER STANDARDS FOR PLANS AND SPECIFICATIONS, IN ORDER |
| TO PROVIDE CONFORMITY TO ITS RECORD RETENTION PROGRAM. |
| THIS POLICY MAY INCLUDE SUCH THINGS AS MINIMUM SIZE, |
| SHAPE, CONTRAST, CLARITY, OR OTHER ITEMS RELATED TO |
| RECORDS MANAGEMENT. |
| |
| NOTE THE FIRST (4) COMMENTS ARE COMMON TO ALL |
| STRUCTURES: |
| 1) THE PERMIT APPLICATION STATED VALUE FOR THIS PROJECT |
| IS STATED AS $30,501,872.00 WHICH SEEMS LOW. ONCE A |
| CONTRACTOR IS SIGNED ON THE VALUE OF THE PROJECT WILL |
| BE DECLARED, THE VALUE MAY BE EVALUATED IF NOT A |
| REASONABLE FIGURE. W P B ADMINISTRTIVE CODE 108.2 |
| SCHEDULE OF PERMIT FEES. ON BUILDINGS, STRUCTURES, |
| ELECTRICAL, GAS, MECHANICAL, AND PLUMBING SYSTEMS OR |
| ALTERATIONS REQUIRING A PERMIT, A FEE FOR EACH PERMIT |
| SHALL BE PAID AS REQUIRED, IN ACCORDANCE WITH THE |
| SCHEDULE ESTABLISHED BY THE APPLICABLE GOVERNING |
| AUTHORITY. |
| |
| 108.3* BUILDING PERMIT VALUATION. |
| IF, IN THE OPINION OF THE BUILDING OFFICIAL, THE |
| CLAIMED VALUATION OF BUILDING, ALTERATION, STRUCTURE, |
| ELECTRICAL, GAS, MECHANICAL, OR PLUMBING SYSTEMS |
| APPEARS TO BE UNDER ESTIMATED ON THE APPLICATION, THE |
| PERMIT SHALL BE DENIED. FOR PERMITTING PURPOSES, |
| VALUATION OF BUILDINGS AND SYSTEMS SHALL BE TOTAL |
| REPLACEMENT PURPOSES, VALUATION OF BUILDINGS AND |
| SYSTEMS SHALL BE THE TOTAL REPLACEMENT VALUE TO INCLUDE |
| STRUCTURAL, ELECTRICAL, PLUMBING, MECHANICAL, INTERIOR |
| FINISHES, NORMAL SITE WORK (EXCAVATION AND BACKFILL FOR |
| BUILDINGS), ARCHITECTURAL AND DESIGN FEES, MARKETING |
| COST, OVERHEAD AND PROFIT; EXCLUDING ONLY LAND VALUE. |
| VALUATION REFRENCES MAY INCLUDE THE LATEST PUBLISHED |
| DATA OF NATIONAL CONSTRUCTION COST ANALYSIS SERVICES |
| (MARSHALL-SWIFT, MEANS, ETC) WITH REGIONAL ADJUSTMENTS |
| FOR LOCATION AS PUBLISHED BY THE INTERNATIONAL CODE |
| CONGRESS. |
| |
| 2) VOLUME # 5 STRUCTURAL & ARCHITECTURAL PLANS SHEET |
| S-GEN-01 / GENERAL NOTES G-3, CORRECT TO 2010 WEST PALM |
| BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER |
| 1, ADMINISTRATION, 2010 NOT PALM BEACH COUNTY, THE CITY |
| OF WEST PALM BEACH IS UNDER HOME RULE, CHAPTER 1 |
| ADMINISTRATIVE CODE. |
| |
| 3A) FBC* 110.3.9 RESIDENT INSPECTOR WILL BE REQUIRED. |
| SUBMIT INSPECTOR RESUME', RESIDENT INSPECTOR AGREEMENT |
| AND LICENSE DOCUMENTS TO KEN CONRAD, MANAGER OF THE |
| RESIDENT INSPECTOR PROGRAM. A RESIDENT INSPECTOR |
| PROGRAM IS REQUIRED, ON THIS PROJECT, DUE TO ONE OR |
| MORE OF THE FOLLOWING: |
| - BUILDINGS/ADDITIONS OF TYPE I OR II CONSTRUCTION |
| - ANY MAJOR STRUCTURAL ALTERATIONS |
| - STRUCTURES IN WHICH THE CONCRETE DESIGN IS BASED ON |
| COMPRESSIVE STRENGTH (F'C) IN EXCESS OF 3000 PSI |
| - PILE DRIVING |
| - BUILDINGS OVER 20,000 SQ FT IN AREA |
| - BUILDINGS OVER 2 STORIES IN HEIGHT |
| - BUILDING/STRUCTURES OF UNUSUAL DESIGN OR METHODS OF |
| CONSTRUCTION |
| |
| KEN CONRAD CONTACT INFORMATION: |
| TEL: 561-805-6666 |
| E-MAIL: [email protected] |
| |
| 3B) SINCE THERE WILL BE REQUIRED A RESIDENT INSPECTOR, |
| (3) SETS OF PLANS, DOCUMENTS AND PRODUCT APPROVALS WILL |
| BE REQIRED. |
| |
| 3C) NOTE: 10/09/2014 E-MAILED REQUIRED DOCUMENTS TO |
| [email protected]. |
| |
| 4A) NO SOILS REPORTS WERE SUBMITTED: 2010 FBC-B 1803.5 |
| INVESTIGATED CONDITIONS. GEOTECHNICAL INVESTIGATIONS |
| SHALL BE CONDUCTED AS INDICATED IN SECTIONS 1803.5.1 |
| THROUGH 1803.5.12. |
| |
| 4B) SITE PLAN WITH LOCATION OF ALL MAIN STRUCTURES & |
| DISTANCE APART. 2010 WEST PALM BEACH AMENDMENTS TO THE |
| FLORIDA BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 |
| WEST PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING |
| CODE, CHAPTER 1, ADMINISTRATION, 107.3.5.1.1 COMMERCIAL |
| BUILDINGS: |
| SITE REQUIREMENTS: |
| PARKING |
| FIRE ACCESS |
| VEHICLE LOADING |
| DRIVING/TURNING RADIUS |
| FIRE HYDRANT/WATER SUPPLY/POST INDICATOR VALVE (PIV) |
| SET BACK/SEPARATION (ASSUMED PROPERTY LINES) |
| LOCATION OF SPECIFIC TANKS, WATER LINES AND SEWER LINES |
| FLOOD HAZARD AREAS, FLOOD ZONES, AND DESIGN FLOOD |
| ELEVATIONS |
| |
| |
| VOLUME ROLL # 5 |
| |
| MAIN ELECTRIC BUILDING: |
| 5) SHEET A-MEB-02 SHOWS WALL IDENTIFICATION TAGS AND |
| DOOR AND WINDOW IDENTIFICATION TAGS THE MAIN ELECTRIC |
| BUILDING PLANS DO NOT HAVE SCHEDULES LISTED WITHIN THE |
| 5 SHEETS OF THE ARCHITECTURAL SHEETS. |
| 107.3.5 MINIMUM PLAN REVIEW CRITERIA FOR BUILDINGS. T |
| 107.3.5.1 COMMERCIAL BUILDINGS: |
| FIRE-RESISTANT CONSTRUCTION REQUIREMENTS SHALL INCLUDE |
| THE FOLLOWING COMPONENTS: |
| FIRE-RESISTANT SEPARATIONS WALLS, DOORS & WINDOWS |
| |
| 6) SHEET A-MEB-02 DOES NOT SHOWN NATURAL VENTILATION, |
| WILL NEED TO SHOW COMPLIANCE WITH 2010 FBC-B 1203.4 |
| NATURAL VENTILATION OR MECHANICAL |
| VENTILATION. |
| |
| 7) MISSING INFORMATION ENERGY FORMS 2010 FBC-ENERGY |
| 103.2 ENERGY REPORTING FORMS. INFORMATION ON |
| CONSTRUCTION DOCUMENTS. 103.2.1 CODE DEMONSTRATION |
| FORMS. SEE TABLE 103.2.1. |
| |
| 8) PLANS ARE MISSING THE REQUIRED INSULATION BY THE |
| 2010 FBC-ENERGY 502 BUILDING ENVELOPE REQUIREMENTS OR |
| 506 TOTAL BUILDING PERFORMANCE. |
| |
| 9) PLANS ARE MISSING 2010 FBC-B 1609.1.2 PROTECTION OF |
| OPENINGS, 1609.6.4.41 COMPONENTS & CLADDING. FLORIDA |
| DEPARTMENT OF COMMUNITY AFFAIRS RULE 9N-3 NOV. 01/ 2010 |
| (31) SUB-CATEGORY OF PRODUCTS OR CONSTRUCTION SYSTEMS |
| THAT WILL REQUIRE PRODUCT APPROVALS: |
| (31)(A) EXTERIOR DOORS. |
| (B), WALL LOUVERS, |
| (C) ROOFING PRODUCTS AND ASSEMBLIES |
| (D) PRE-ENGINEERED A/C STANDS IF ROOF TOP |
| |
| 10) 2010 FBC 107.3.4.1 PRODUCT APPROVALS. THOSE |
| PRODUCTS WHICH ARE REGULATED BY THE DCA RULE 9N-03 |
| SHALL BE REVIEWED AND APPROVED IN WRITING BY THE |
| DESIGNER OF RECORD PRIOR TO SUBMITTAL FOR |
| JURISDICTIONAL APPROVAL. FL 61G1-23.015 (2) THE |
| ARCHITECT IS RESPONSIBLE FOR SUPERVISING AND REVIEWING |
| ALL PROJECT DATA, REPORTS, SHOP DRAWINGS ETC.. |
| |
| 11A) SHEET S-MEB-02 PRESSURES FOR COMPONENTS AND |
| CLADDING EXPOSURE "C" @ 180 MPH, 22 FT ABOVE GRADE, |
| VASD FOR ROOF ZONE 2 ARE LOW, WE TAKE THE PRESSURES AT |
| 10 SQ. FT. FOR ROOF TOP FASTENERS. 2010 FBC-B 1609.1.2 |
| PROTECTION OF OPENINGS, 2010 FBC-B 1609.6.4.41 |
| COMPONENTS & CLADDING |
| |
| 11B) SHEET S-GEN-01 INDICATES THE MAIN ELECTRIC |
| BUILDING, PRESSURE COEFFICIENT AS +/- 0.55. THIS |
| COEFFICIENT IS FOR PARTIALLY ENCLOSED BUILDINGS, THIS |
| BUILDING IS TOTALLY ENCLOSED. |
| |
| 11C) SHEET S-MEB-02 NOR -03 PRESSURES FOR THE DOOR |
| OPENINGS ARE NOT PROVIDED FOR THIS BUILDING. 2010 FBC-B |
| 2010 FBC-B 1609.1.2 PROTECTION OF OPENINGS, 1609.6.4.41 |
| COMPONENTS & CLADDING. |
| |
| 12) SHEET A-MEB-03 NOTE 4 IS ROOF ROOF TOP LADDER. SEE |
| DETAIL 5A-GEN-04. THIS PAGE IS A INDEX SHEET? 107.2.1.3 |
| ADDITIONAL INFORMATION IS REQUIRED. |
| |
| 13) SHEET A-MEB-03 NOTES 2 & 3 DO NOT INDICATE THE |
| SIZING METHOD USED. |
| 2010 FBC-B 1503.4.2 SCUPPERS. |
| 2010 FBC-B 1503.4.2.1 OVERFLOW SCUPPERS. |
| WHEN OTHER MEANS OF DRAINAGE OF OVERFLOW WATER IS NOT |
| PROVIDED, OVERFLOW SCUPPERS SHALL BE PLACED IN WALLS OR |
| PARAPETS NOT LESS THAN 2 INCHES (51 MM) NOR MORE THAN 4 |
| INCHES (102 MM) ABOVE THE FINISHED ROOF COVERING AND |
| SHALL BE LOCATED AS CLOSE AS PRACTICAL TO REQUIRED |
| VERTICAL LEADERS OR DOWNSPOUTS OR WALL AND PARAPET |
| SCUPPERS. AN OVERFLOW SCUPPER SHALL BE SIZED IN |
| ACCORDANCE WITH THE FLORIDA BUILDING CODE, PLUMBING. |
| |
| 14) SHEET A-MEB-03 SHOWS THE LOCATION OF THE SCUPPERS |
| BUT IT DOES NOT SHOW THEY ARRE DIRECTLY IN FRONT OF THE |
| 16X16 INCH COLUMN AND HOW IS THE STEEL RE-INFORCEMENT |
| AND THE SCUPPER GOING TO FIT INTO THE SAME COLUMN. SEE |
| 2010 FBC-B 1906.3 CONDUITS AND PIPES EMBEDDED IN |
| CONCRETE. |
| CONDUITS, PIPES AND SLEEVES OF ANY MATERIAL NOT HARMFUL |
| TO CONCRETE AND WITHIN THE LIMITATIONS OF ACI 318, |
| SECTION 6.3, ARE PERMITTED TO BE EMBEDDED IN CONCRETE |
| WITH APPROVAL OF THE REGISTERED DESIGN PROFESSIONAL. |
| |
| 15A) SHEET A-MEB-01 BUILDING IS 2,572 SQ. FT./ 100= 26 |
| OCCUPANTS, PLEASE INDICATE HOW 9 OCCUPANTS WAS DERIVED. |
| 2010 FBC-B TABLE 1004.1.1. |
| |
| 15B) NOTE THE A-MEB BUILDING, MAIN ELECTRIC BUILDING |
| MAY NEED TO COMPLY WITH 2010 FBC-B 1008.1.10 WHEN: |
| ELECTRICAL ROOMS WITH EQUIPMENT RATED 1,200 AMPERES OR |
| MORE AND OVER 6 FEET (1829 MM) WIDE THAT CONTAIN |
| OVERCURRENT DEVICES, SWITCHING DEVICES OR CONTROL |
| DEVICES WITH EXIT OR EXIT ACCESS DOORS SHALL BE |
| EQUIPPED WITH PANIC HARDWARE OR FIRE EXIT HARDWARE. THE |
| DOORS SHALL SWING IN THE DIRECTION OF EGRESS TRAVEL. |
| |
| 16) S-WAS-05 VERSES S-WAS-08 DECANT STORAGE TANKS |
| VERSES WAS STORAGE TANKS. 2010 FLORIDA BUILDING CODE W |
| * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA |
| BUILDING CODE, CHAPTER 1, ADMINISTRATION 107.2.1.3 |
| ADDITIONAL INFORMATION IS REQUIRED. THERE IS NO |
| ARCHITECTURAL SHEETS THAT CORELATE TO THE PLANS |
| REFERENCED ABOVE. IT IS NOT CLEAR IF THE PROCESS IS |
| CHANGING AND THE DECANT STORAGE TANKS ARE NO LONGER |
| GOING TO BE USED AND CONVERTED IN TO THE WAS STORAGE |
| TANKS. A PRE-CON MEETING WOULD HAVE BEEN VERY HELPFULL |
| TO UNDERSTAND WHAT IS BEING PRESENTED IN THE PLANS. |
| |
| |
| 17) SHEETS S-WAS-13 & S-WAS-14 CENTRATE PUMP STATION: |
| PLEASE PROVIDE COMPLIANCE WITH 2010 FBC-B 1009.12 |
| HANDRAILS. STAIRWAYS SHALL HAVE HANDRAILS ON EACH SIDE |
| AND SHALL COMPLY WITH SECTION 1012. |
| |
| |
| WAS STORAGE & BLOWER BUILDING |
| 18) SHEET A-WAS-01 INDICATES THE BUILDING IS 1,861 SQ. |
| FT./ 100= 19 OCCUPANTS, PLEASE INDICATE HOW 7 OCCUPANTS |
| WAS DERIVED? 2010 FBC-B TABLE 1004.1.1. |
| |
| 19) SHEET A-WAS-02 THE WALL BETWEEN THE BLOWER ROOM & |
| ELECTRIC ROOM IS IDENTIFIED WITH WALL TAG P-1, THIS |
| WALL TYPE IS NOT FOUND IN ANY OF THE SHEETS A-GEN-01 |
| THRO -05. ADDITIONAL INFORMATION REQUIRED. 107.2.1.3, |
| |
| 20) MISSING INFORMATION ENERGY FORMS 2010 FBC-ENERGY |
| 103.2 ENERGY REPORTING FORMS. INFORMATION ON |
| CONSTRUCTION DOCUMENTS. 103.2.1 CODE DEMONSTRATION |
| FORMS. SEE TABLE 103.2.1. |
| |
| 21) PLANS ARE MISSING THE REQUIRED INSULATION BY THE |
| 2010 FBC-ENERGY 502 BUILDING ENVELOPE REQUIREMENTS OR |
| 506 TOTAL BUILDING PERFORMANCE. |
| |
| 22 PLANS ARE MISSING 2010 FBC-B 1609.1.2 PROTECTION OF |
| OPENINGS, 1609.6.4.41 COMPONENTS & CLADDING. FLORIDA |
| DEPARTMENT OF COMMUNITY AFFAIRS RULE 9N-3 NOV. 01/ 2010 |
| (31) SUB-CATEGORY OF PRODUCTS OR CONSTRUCTION SYSTEMS |
| THAT WILL REQUIRE PRODUCT APPROVALS: |
| (31)(A) EXTERIOR DOORS. |
| (B), WALL LOUVERS, EFIS SYSTEMS |
| (C) ROOFING PRODUCTS AND ASSEMBLIES |
| (D) PRE-ENGINEERED A/C STANDS IF ROOF TOP |
| |
| 23) 2010 FBC 107.3.4.1 PRODUCT APPROVALS. THOSE |
| PRODUCTS WHICH ARE REGULATED BY THE DCA RULE 9N-03 |
| SHALL BE REVIEWED AND APPROVED IN WRITING BY THE |
| DESIGNER OF RECORD PRIOR TO SUBMITTAL FOR |
| JURISDICTIONAL APPROVAL. FL 61G1-23.015 (2) THE |
| ARCHITECT IS RESPONSIBLE FOR SUPERVISING AND REVIEWING |
| ALL PROJECT DATA, REPORTS, SHOP DRAWINGS ETC.. |
| |
| 24A) SHEET S-WAS--11 PRESSURES FOR COMPONENTS AND |
| CLADDING EXPOSURE "C" @ 180 MPH, 20 FT ABOVE GRADE, |
| VASD FOR ROOF ZONE 2 ARE LOW, WE TAKE THE PRESSURES AT |
| 10 SQ. FT. FOR ROOF TOP FASTENERS. 2010 FBC-B 1609.1.2 |
| PROTECTION OF OPENINGS, 2010 FBC-B 1609.6.4.41 |
| COMPONENTS & CLADDING |
| |
| 25B) SHEET S-WAS-01 THRU -05 NO PRESSURES FOR THE DOOR |
| OPENINGS ARE NOT PROVIDED FOR THIS BUILDING. 2010 FBC-B |
| 2010 FBC-B 1609.1.2 PROTECTION OF OPENINGS, 1609.6.4.41 |
| COMPONENTS & CLADDING. |
| |
| |
| ADF ANAEROBIC DIGETION FACILITY |
| 26) SHEET A-ADF-04 GAS HANDLING ROOM. PLEASE PROVIDE |
| THE TYPE OF GAS TO BE HANDLED IN THIS ROOM, QUANITIES |
| OF GAS TO BE USED & STORED IN THIS ROOM. |
| MSDS SHEETS WERE SUBMITTED BUT NO INFORMATION WAS |
| SUBMITTED WHERE THESE CHEMICALS WILL BE USED NOR |
| STORED. IF QUANITIES OF CHEMICALS EXCEEDS THE AMOUNT IN |
| 2010 FBC-B TABLE 307.1(1) MAXIMUM ALLOWABLE QUANTITY |
| PER CONTROL AREA OF HAZARDOUS MATERIALS POSING A |
| PHYSICAL HAZARDA, J, M, N, P. IF AMOUNTS OF CHEMICALS |
| EXCEEDS THE ALLOWABLE AMOUNT IN TABLE 307.1(1) THEN |
| EITHER ADDITIONAL CONTROL AREAS WOULD BE REQUIRED OR |
| THIS PORTION OF THE BUILDING WILL NEED TO MEET THE |
| REQUIREMENTS OF CHAPTER 414. |
| |
| 27) MISSING INFORMATION ENERGY FORMS 2010 FBC-ENERGY |
| 103.2 ENERGY REPORTING FORMS. INFORMATION ON |
| CONSTRUCTION DOCUMENTS. 103.2.1 CODE DEMONSTRATION |
| FORMS. SEE TABLE 103.2.1. |
| |
| 28) PLANS ARE MISSING THE REQUIRED INSULATION BY THE |
| 2010 FBC-ENERGY 502 BUILDING ENVELOPE REQUIREMENTS OR |
| 506 TOTAL BUILDING PERFORMANCE. |
| |
| 29 PLANS ARE MISSING 2010 FBC-B 1609.1.2 PROTECTION OF |
| OPENINGS, 1609.6.4.41 COMPONENTS & CLADDING. FLORIDA |
| DEPARTMENT OF COMMUNITY AFFAIRS RULE 9N-3 NOV. 01/ 2010 |
| (31) SUB-CATEGORY OF PRODUCTS OR CONSTRUCTION SYSTEMS |
| THAT WILL REQUIRE PRODUCT APPROVALS: |
| (31)(A) EXTERIOR DOORS. |
| (B), WALL LOUVERS, EFIS SYSTEMS |
| (C) ROOFING PRODUCTS AND ASSEMBLIES |
| (D) PRE-ENGINEERED A/C STANDS IF ROOF TOP |
| |
| 30) 2010 FBC 107.3.4.1 PRODUCT APPROVALS. THOSE |
| PRODUCTS WHICH ARE REGULATED BY THE DCA RULE 9N-03 |
| SHALL BE REVIEWED AND APPROVED IN WRITING BY THE |
| DESIGNER OF RECORD PRIOR TO SUBMITTAL FOR |
| JURISDICTIONAL APPROVAL. FL 61G1-23.015 (2) THE |
| ARCHITECT IS RESPONSIBLE FOR SUPERVISING AND REVIEWING |
| ALL PROJECT DATA, REPORTS, SHOP DRAWINGS ETC.. |
| |
| 31A) SHEET S-ADF-18 PRESSURES FOR COMPONENTS AND |
| CLADDING EXPOSURE "C" @ 180 MPH, 20 FT ABOVE GRADE, |
| VASD FOR ROOF ZONE 2 ARE LOW, WE TAKE THE PRESSURES AT |
| 10 SQ. FT. FOR ROOF TOP FASTENERS. 2010 FBC-B 1609.1.2 |
| PROTECTION OF OPENINGS, 2010 FBC-B 1609.6.4.41 |
| COMPONENTS & CLADDING |
| |
| 32B) SHEET S-ADF-01 THRU -S-ADF- 40 NO PRESSURES FOR |
| THE DOOR OPENINGS ARE NOT PROVIDED FOR THIS BUILDING. |
| 2010 FBC-B 2010 FBC-B 1609.1.2 PROTECTION OF OPENINGS, |
| 1609.6.4.41 COMPONENTS & CLADDING. |
| |
| 33) SHEET S-ADF-01 INDICATES THE ANAEROBIS DIGESTION |
| FACILITY AND THE ANAEROBIS DIGESTION ELECTRIC BUILDING |
| ARE WITHIN 10'=0" OF EACH OTHER. PLEASE PROVIDE ON THE |
| ARCHITECTURAL SHEETS THE 2 BUILDING LOCATIONS AND AN |
| ASSUMED PROPERTY LINE BETWEEN THE 2 BUILDINGS, PLEASE |
| SHOW COMPLIANCE WITH 2010 FBC-B TABLE 602 |
| FIRE-RESISTANCE RATING REQUIREMENTS FOR EXTERIOR WALLS |
| BASED ON FIRE SEPARATION DISTANCE. |
| TABLE 705.8 MAXIMUM AREA OF EXTERIOR WALL OPENINGS |
| BASED ON FIRE SEPARATION DISTANCE AND DEGREE OF OPENING |
| PROTECTION |
| |
| |
| A-DEW-01 DEWATERING BUILDING. |
| 34) MISSING INFORMATION ENERGY FORMS 2010 FBC-ENERGY |
| 103.2 ENERGY REPORTING FORMS. INFORMATION ON |
| CONSTRUCTION DOCUMENTS. 103.2.1 CODE DEMONSTRATION |
| FORMS. SEE TABLE 103.2.1. |
| |
| 35) PLANS ARE MISSING THE REQUIRED INSULATION BY THE |
| 2010 FBC-ENERGY 502 BUILDING ENVELOPE REQUIREMENTS OR |
| 506 TOTAL BUILDING PERFORMANCE. |
| |
| 36) PLANS ARE MISSING 2010 FBC-B 1609.1.2 PROTECTION OF |
| OPENINGS, 1609.6.4.41 COMPONENTS & CLADDING. FLORIDA |
| DEPARTMENT OF COMMUNITY AFFAIRS RULE 9N-3 NOV. 01/ 2010 |
| (31) SUB-CATEGORY OF PRODUCTS OR CONSTRUCTION SYSTEMS |
| THAT WILL REQUIRE PRODUCT APPROVALS: |
| (31)(A) EXTERIOR DOORS & ROOF HATCH. |
| (B) WINDOWD |
| (C), WALL LOUVERS, EFIS SYSTEMS |
| (D) ROOFING PRODUCTS AND ASSEMBLIES |
| (E) PRE-ENGINEERED A/C STANDS IF ROOF TOP |
| |
| 37) 2010 FBC 107.3.4.1 PRODUCT APPROVALS. THOSE |
| PRODUCTS WHICH ARE REGULATED BY THE DCA RULE 9N-03 |
| SHALL BE REVIEWED AND APPROVED IN WRITING BY THE |
| DESIGNER OF RECORD PRIOR TO SUBMITTAL FOR |
| JURISDICTIONAL APPROVAL. FL 61G1-23.015 (2) THE |
| ARCHITECT IS RESPONSIBLE FOR SUPERVISING AND REVIEWING |
| ALL PROJECT DATA, REPORTS, SHOP DRAWINGS ETC.. |
| |
| 38) SHEET S-DEW-06 PRESSURES FOR COMPONENTS AND |
| CLADDING EXPOSURE "C" @ 180 MPH, 71 FT ABOVE GRADE,ARE |
| LOW FOR BOTH THE ROOF ZONES AND WALL ZONES. MULTIPLIER |
| OF 1.62 FOR HEIGHT. |
| |
| 39) SHEET A-DEW- 03/05/06 HARDWARE SCHEDULE IS BLANK. |
| NOTE THE ELECTRIC ROOMS 105, 206 & 305 MUST MEET THE |
| REQUIREMENTS OF THE 2010 FBC-B 1008.1.10 PANIC AND FIRE |
| EXIT HARDWARE. |
| ELECTRICAL ROOMS WITH EQUIPMENT RATED 1,200 AMPERES OR |
| MORE AND OVER 6 FEET (1829 MM) WIDE THAT CONTAIN |
| OVERCURRENT DEVICES, SWITCHING DEVICES OR CONTROL |
| DEVICES WITH EXIT OR EXIT ACCESS DOORS SHALL BE |
| EQUIPPED WITH PANIC HARDWARE OR FIRE EXIT HARDWARE. THE |
| DOORS SHALL SWING IN THE DIRECTION OF EGRESS TRAVEL. |
| |
| 40A) SHEET A-DEW-05 IS MISSING THE ONE HOUR FIRE RATING |
| ON THE FOLLOWING: |
| INTERIOR VERTICAL EXIT ENCLOSURE FBC-B 1022.1. |
| ELEVATOR MACHINE ROOM FBC-B 3006.4 |
| THIRD FLOOR EXTERIOR WALL AT EXTERIOR STAIR FBC-B |
| 1026.6 PROTECTION OF EXTERIOR STAIR PROTECTION. |
| |
| 40B) PROVIDE CODE COMPLIANCE WITH: 2010 FBC-B 713.6 |
| FIRE WALLS, FIRE BARRIERS, FIRE PARTITIONS, SMOKE |
| BARRIERS AND SMOKE PARTITIONS OR ANY OTHER WALL |
| REQUIRED TO HAVE PROTECTED OPENINGS SHALL BE |
| EFFECTIVELY AND PERMANENTLY IDENTIFIED WITH SIGNS OR |
| STENCILING IN A MANNER ACCEPTABLE TO THE AUTHORITY |
| HAVING JURISDICTION. SUCH IDENTIFICATION SHALL BE ABOVE |
| ANY DECORATIVE CEILING AND IN CONCEALED SPACES. |
| SUGGESTED WORDING FOR FIRE AND SMOKE BARRIERS: ?FIRE |
| AND SMOKE BARRIER ? PROTECT ALL OPENINGS.? |
| |
| 41) SHEETS A-DEW- 17 SHOWS FLOOR OPENINGS ON THE 2ND & |
| 3RD FLOOR THAT ALLOW THE 3 FLOORS TO COMMUNICATE |
| WITHOUT AND WITHOUT A SHAFT ENCLOSURE, PLEASE SHOW |
| COMPLIANCE WITH 2010FBC-B 708.2 OR AN EXCEPTION. |
| |
| 42) SHEET A-DEW- 22 SHOWS A INSTALLATION OF A HYDROLIC |
| ELEVATOR, PLEASE PROVIDE COMPLIANCE WITH 2010 FBC-B |
| 3011.1 ELECTROLYSIS PROTECTION FOR UNDERGROUND |
| HYDRAULIC ELEVATOR CYLINDERS. |
| ALL NEWLY INSTALLED UNDERGROUND HYDRAULIC PRESSURE |
| CYLINDERS SHALL BE ENCASED IN OUTER PLASTIC CONTAINMENT |
| TO MINIMIZE ELECTROLYTIC CORROSION BETWEEN THE METAL |
| CYLINDER AND GROUND CATHODE. |
| 3011.1.1 THE PLASTIC CASING SHALL BE CAPPED AT THE |
| BOTTOM, AND ALL JOINTS MUST BE SOLVENT OR HEAT WELDED |
| TO ENSURE WATER TIGHTNESS. |
| 3011.1.2 THE PLASTIC CASING SHALL BE CONSTRUCTED OF |
| POLYETHYLENE OR POLYVINYL CHLORIDE (PVC). THE PLASTIC |
| PIPE WALL THICKNESS MUST NOT BE LESS THAN 0.125 INCH |
| (3.175 MM). |
| |
| 43) SHEET A-DEW- 05 BREAK ROOM INDICATES THE USE OF A |
| MICROWAVE SEE DETAIL 4/ A-DEW-27, MICROWAVE IS NOT |
| SHOWN IN THIS DETAIL PLEASE SHOW COMPLIANCE WITH THE |
| 2010 FL ACCESSIBILITY CODE REACH RANGES 308.2 & 308.3. |
| |
| 44) SHEET A-DEW-05 OR 06 NEITHER FLOOR SHOWS AN |
| ACCESSIBLE RESTROOM, THE 2010 FL PLUMBING CODE DOES |
| ALLOW TRAVEL DISTANCE OF ONE FLOOR TO REACH A RESTROOM |
| AND OR BATHROOMS. 2010 FL ACCESS. 213.2 TOILET ROOMS |
| AND BATHING ROOMS. WHERE TOILET ROOMS ARE PROVIDED, |
| EACH TOILET ROOM SHALL COMPLY WITH 603. WHERE BATHING |
| ROOMS ARE PROVIDED, EACH BATHING ROOM SHALL COMPLY WITH |
| 603. |
| |
| 45) SHEET A-DEW-05 WOMENS AND MENS SHOWERS: MISSING AN |
| ACCESSIBLE SHOWER IN EACH BATHROOM GROUP. SEE 2010 |
| FBC-ACCESS. 608.2- 608.8. |
| |
| 46) SHEET A-DEW- 03/05 OR 06 DO NOT PROVIDE A DRINKING |
| AN ACCESSIBLE DRINKING FOUNTAIN. 2010 FBC-ACCESS. 211.2 |
| MINIMUM NUMBER. |
| NO FEWER THAN TWO DRINKING FOUNTAINS SHALL BE PROVIDED. |
| ONE DRINKING FOUNTAIN SHALL COMPLY WITH 602.1 THROUGH |
| 602.6 AND ONE DRINKING FOUNTAIN SHALL COMPLY WITH |
| 602.7. |
| |
| 47) NOTE: SHEET A-DEW-14 NOTES THAT INDICATE THESE |
| COMPONENTS TO BE COMPLETED BY DELEGATE ENGINEER: |
| EXTERIOR PRE-FABRICATED STAIRS, HANDRAIL & GUARDRAIL |
| PRE-FABRICATED METAL CANOPY |
| PRE-ENGINEERED METAL BUILDING SYSTEM |
| INTERIOR PRE-FABRICATED METAL STAIRS, HANDRAIL & |
| GUARDRAIL A-DEW- 16 |
| FL 61G1-23.015 (2) THE ARCHITECT IS RESPONSIBLE FOR |
| SUPERVISING AND REVIEWING ALL PROJECT DATA, REPORTS, |
| SHOP |
| DRAWINGS ETC... |
| 61G1-23.015 RESPONSIBLE SUPERVISING CONTROL OVER |
| ARCHITECTURAL PRACTICE OUTSIDE OF THE ARCHITEC'S |
| OFFICE. |
| |
| A-FOG-01 SEPTAGE FOG ATENDANT BUILDING |
| 48) MISSING INFORMATION ENERGY FORMS 2010 FBC-ENERGY |
| 103.2 ENERGY REPORTING FORMS. INFORMATION ON |
| CONSTRUCTION DOCUMENTS. 103.2.1 CODE DEMONSTRATION |
| FORMS. SEE TABLE 103.2.1. |
| |
| 49) PLANS ARE MISSING THE REQUIRED INSULATION BY THE |
| 2010 FBC-ENERGY 502 BUILDING ENVELOPE REQUIREMENTS OR |
| 506 TOTAL BUILDING PERFORMANCE. |
| |
| 50) PLANS ARE MISSING 2010 FBC-B 1609.1.2 PROTECTION OF |
| OPENINGS, 1609.6.4.41 COMPONENTS & CLADDING. FLORIDA |
| DEPARTMENT OF COMMUNITY AFFAIRS RULE 9N-3 NOV. 01/ 2010 |
| (31) SUB-CATEGORY OF PRODUCTS OR CONSTRUCTION SYSTEMS |
| THAT WILL REQUIRE PRODUCT APPROVALS: |
| (31)(A) EXTERIOR DOORS . |
| (B) WINDOW |
| (C), WALL LOUVERS, EFIS SYSTEMS |
| (D) ROOFING PRODUCTS AND ASSEMBLIES |
| (E) PRE-ENGINEERED A/C STANDS IF ROOF TOP |
| |
| 51) 2010 FBC 107.3.4.1 PRODUCT APPROVALS. THOSE |
| PRODUCTS WHICH ARE REGULATED BY THE DCA RULE 9N-03 |
| SHALL BE REVIEWED AND APPROVED IN WRITING BY THE |
| DESIGNER OF RECORD PRIOR TO SUBMITTAL FOR |
| JURISDICTIONAL APPROVAL. FL 61G1-23.015 (2) THE |
| ARCHITECT IS RESPONSIBLE FOR SUPERVISING AND REVIEWING |
| ALL PROJECT DATA, REPORTS, SHOP DRAWINGS ETC.. |
| |
| 52) SHEET S-FOG-05 PRESSURES FOR COMPONENTS AND |
| CLADDING EXPOSURE "C" @ 180 MPH, 17 FT ABOVE GRADE,ARE |
| LOW FOR BOTH THE ROOF ZONES AND WALL ZONES. MULTIPLIER |
| OF 1.29 FOR HEIGHT. |
| |
| |
| S-AFD DIGESTER TANKS |
| 53) S-AFD-09 STAIRS, LANDINGS, HANDRAIL, GUARDRAIL AND |
| TANK STEEL TOP AND ANCHORS, SHOP DRAWINGS TO BE |
| COMPLETED BY DELEGATE ENGINEER: |
| FL 61G1-23.015 (2) THE ARCHITECT IS RESPONSIBLE FOR |
| SUPERVISING AND REVIEWING ALL PROJECT DATA, REPORTS, |
| SHOP |
| DRAWINGS ETC... |
| 61G1-23.015 RESPONSIBLE SUPERVISING CONTROL OVER |
| ARCHITECTURAL PRACTICE OUTSIDE OF THE ARCHITEC'S |
| OFFICE. |
| |
| |
| VOLUME # 6 NO COMMENT. |
| |
| VOLUME # 7 NO COMMENT. |
| |
| WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION & |
| REMOVE & REPLACE ANY PAGES AS NECESSARY. A TRANSMITTAL |
| LETTER LISTING THE ORIGINAL REVIEW COMMENT NUMBER, WITH |
| A DESCRIPTION OF THE REVISION MADE, IDENTIFYING THE |
| SHEET OR SPECIFICATION PAGE WHERE THE CHANGES CAN BE |
| FOUND WILL HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR |
| YOUR ANTICIPATED COOPERATION. |
| |