Notes
Date Text
2014-09-13 05:59:25CITY OF WPB ADMIN. AMEND. TO 2010 FBC SEC. 107.2.1.
 1) SUBMIT A GAS PIPING RISER THAT CLEARLY REFLECTS THE
 SCOPE OF WORK TO BE DONE.
 2) SHOW THE LOCATION OF EACH APPLIANCE ON THE PIPING
 PLAN AND SHOW THE BTU LOAD FOR EACH APPLIANCE. YOU LIST
 ELEVEN APPLIANCES BUT THE PIPING PLAN SHOWS 3 SHUTOFF
 VALVES.
 3) SHOW THE TOTAL DISTANCE FROM THE GAS POINT OF
 DELIVERY TO THE MOST REMOTE OUTLET.
 4) IDENTIFY THE TYPE OF PIPE AT EACH PIPE SECTION ON
 THE GAS RISER.
 5) SUBMIT THE SIZING TABLES FROM THE THE 2010 FLORIDA
 GAS CODE FOR THE SPECIFIC TYPE OF PIPE USED.