Plan Review Notes For Permit 14090220 |
Permit Number |
14090220 |
|
Review Stop |
G |
Sequence Number |
2 |
|
Notes |
Date |
Text |
2015-04-12 09:05:13 | 1) SIZE THE SECTION OF THE GAS PIPING DOWNSTREAM OF THE | | BBQ GRILL. | | 2) THE NEW SHEET P2.0 APPEARS TO SHOW PE PIPING UNDER A | | SLAB. PE PIPING CAN ONLY BE USED OUTDOORS UNDERGROUND | | PER THE 2010 FBCR SEC.G2415.15.1. | | 3) SUBMIT MANUF. SPECIFICATIONS FOR ALL NEW GAS | | APPLIANCES. ALL APPLIANCES SHALL BE LISTED AND LABELED. | | G2404.3. | | 4) THERE IS ONLY ONE SET OF REVISED PLANS IN THE | | FOLDER.SUBMIT TWO SETS OF PLANS. WPB AMEND. TO 2010 FBC | | SEC. 107.1. | | | | | | PLUMBING PLAN REVIEW | | TIM LARGE | | CHIEF PLUMBING INSPECTOR | | 561-805-6692 | | [email protected] | | | | |
|