Plan Review Notes
Plan Review Notes For Permit 14090220
Permit Number 14090220
Review Stop B
Sequence Number 2
Notes
Date Text
2015-04-13 18:59:43RESIDENTIAL (R3) ADDITION, SECOND BUILDING REVIEW
 COMMENTS .
 CODE: 2010 FBC.
  
 (NOTE: THESE COMMENTS ARE FOR A NEW SET OF CONSTRUCTION
 DRAWINGS SUBMITTED FROM ANOTHER DESIGN PROFESSIONAL).
  
 1- A) ENGINEER OF RECORD TO PROVIDE COMPLETE ENGINEER
 ANALYSIS SHOWING HOW THE PROPOSED SECOND FLOOR TERRACE
 ASSEMBLY WILL MEET THE TERRACE LOADS SPECIFIED ON SHEET
 S-2 (DEAD LOAD 100 LBS PSF AND LIVE LOAD 125 LBS PSF).
 SEC. 107.2.1.3 CITY AMENDMENTS.
  
 B) PROVIDE COMPLETE ENGINEERED TRUSS PACKAGE (2 COPIES)
 SHOWING THE TERRACE DESIGN LOADS SPECIFIED BY THE
 ENGINEER OF RECORD ON THE FLOOR FRAMING PLAN ON SHEET
 S-2 (100 LBS PSF DEAD LOAD AND 125 LBS PSF LIVE LOAD).
 SEC. 107.2.1.3 CITY AMENDMENTS.
 NOTE: PACKAGE TO BE REVIEWED BY THE ENGINEER OF RECORD
 PRIOR TO SUBMITTAL TO THIS OFFICE.
  
 2- SHEET S-1:
 A) ENGINEER TO CLARIFY DESIGN SPECIFICATIONS NOTE #2.
 THESE CONSTRUCTION DOCUMENTS ARE FOR A SECOND FLOOR
 TERRACE. WHY IS THE STRUCTURE CONSIDERED "ENCLOSED
 STRUCTURE". SEC. R301 OF 2010 FBC-RESIDENTIAL.
  
 B) CONCRETE PAD SCHEDULE IS NOT CLEAR: (1) ENGINEER TO
 CLARIFY SIZE OF OF CONCRETE PADS P1 AND P2. PLEASE
 PROVIDE DETAIL SHOWING THE 44"W X 42"D AND 42"W X 42"D
 CONCRETE PADS. (2) CONCRETE PAD P1 SHOWN ON FOUNDATION
 PLAN DOESN'T'T MATCH SIZE SHOWN ON CONCRETE PAD
 SCHEDULE. REVISE AS REQUIRED TO MATCH. SEC. 107.2.1
 CITY AMENDMENTS.
  
 C) AREA CALCULATIONS ARE INCORRECT. REVISE AS REQUIRED.
 SEC. 107.2.1 CITY AMENDMENTS.
  
 D) ALTERATION LEVEL IS INCORRECT. SEE SEC. 401.4 AND
 SEC. 407 OF 2010 FBC-EXISTING BUILDING.
  
 E) ENGINEER TO CLARIFY THE WIND DESIGN LOADS. ENGINEER
 CALLS FOR 2 DIFFERENT WIND LOADS ON THE SAME SHEET.
 ENGINEER CALLS FOR 170 MPH ULTIMATE WIND LOAD AND 175
 MPH ULTIMATE WIND LOAD ON THE SAME SHEET. REVISE AS
 REQUIRED. SEC. 107.2.1 CITY AMENDMENTS.
  
 3- SHEET S-2:
 A) SPECIFY ALL CONNECTORS AT THE ENDS OF ALL LVL'S
 BEAMS SHOWN ON THE FLOOR FRAMING PLAN. SEC. R301.1 OF
 2010 FBC-RESIDENTIAL.
  
 B) PROVIDE COMPLETE SECTION DETAIL THRU (2)2X12 P.T.
 WOOD LEDGER SHOWN ON FLOOR FRAMING PLAN. SPECIFY HOW
 MUCH EMBEDMENT IS REQUIRED TO THE EXISTING STRUCTURE
 AND SPECIFY ANCHOR SPACING. PROVIDE ENGINEER ANALYSIS
 SHOWING THAT 3/4" DIA X 4"L A.B. IS ADEQUATE FOR THE
 SPECIFIED TERRACE LOADS. NOTE: EXISTING STRUCTURE IS
 CONCRETE BLOCK. VERIFY TYPE OF ANCHOR SPECIFIED. SEC.
 R301.1 OF 2010 FBC-RESIDENTIAL.
  
 C) SECOND FLOOR LAYOUT: PROVIDE GUARDRAIL COMPLETE
 CONSTRUCTION DETAILS AND SPECIFICATIONS SHOWING
 COMPLIANCE WITH THE LIVE LOADS REQUIRED BY TABLE R301.5
 OF 2010 FBC-RESIDENTIAL.
  
 D) HEIGHT OF GUARDRAIL IS DIFFERENT IN ALL PLANS AND
 DETAILS ON THIS SHEET. COORDINATE AS REQUIRED. SEC.
 107.2.1 CITY AMENDMENTS.
  
 E) STAIRS DETAILS: (1) SIZE OF TREAD DOESN'T COMPLY
 WITH SEC. R311.7.4.1 OF 2010 FBC-RESIDENTIAL. (2)
 NOSING DETAIL DOESN'T COMPLY WITH SEC. R311.7.4.3 OF
 2010 FBC-RESIDENTIAL. (3) WHERE IS SECTION "A" TAKEN
 AT?. SEC. 107.2.1 CITY AMENDMENTS. (4) SPECIFY BEAM.
 SEC. 107.2.1 CITY AMENDMENTS. (5)SPECIFY ALL
 CONNECTORS. SEC. 107.2.1 CITY AMENDMENTS. SPECIFY SIZE
 AND LOCATION OF HANDRAIL. SEC R311.7.7 FBC-RESIDENTIAL.
  
 F) KNEE WALL/STAIRS SECTION: (1) WHERE IS THIS SECTION
 TAKEN AT?. INFORMATION DOESN'T MATCH FLOOR FRAMING
 PLAN. SEC. 107.2.1 CITY AMENDMENTS. (2) PROVIDE
 COMPLETE FRAMING DETAILS AND SPECIFICATIONS FOR THE
 STAIRWAY CONSTRUCTION. IT'S NOT CLEAR IF THE STAIRWAY
 IS GOING TO-BE OPEN ON ONE SIDE?. SEC. 107.2.1 CITY
 AMENDMENTS. (3) PROVIDE COMPLETE FASTENING
 SPECIFICATIONS FOR THE INSTALLATION OF THE 1 X 6 WOOD
 DECKING AND 1 X 6 CYPRESS CEILING. SEC. R301 OF 2010
 FBC-RESIDENTIAL. (4) WHERE IS THE SCHLUTER-DITRA150 AND
 SELF ADHERING-BASE SHEET INSTALLED IF THERE IS NOT
 SUBSTRATE BELOW?. SEC. 107.2.1 CITY AMENDMENTS. (5)
 FOOTING SIZE DOESN' MATCH FOUNDATION PLAN. SEC. 107.2.1
 CITY AMENDMENTS. (6) PROVIDE COMPLETE DETAILS AND
 SPECIFICATIONS FOR THE CONSTRUCTION AND INSTALLATION OF
 THE DECORATIVE WOOD LOUVER, INCLUDING LOCATION OF
 PROPOSED LOUVER. SEC. R301. (7) PROVIDE COMPLETE
 DETAILS AND SPECIFICATIONS FOR THE INSTALLATION OF
 "STUCCO CROWN MOLDING" AS SHOWN. SEC. 107.2.1 CITY
 AMENDMENTS.
  
 G) POST COLUMN CONNECTION DETAIL: (1) PROVIDE
 MANUFACTURER SPECS FOR POST AND BEAM CONNECTORS
 SPECIFIED TO VERIFY COMPLIANCE WITH-THE PROPOSED
 INSTALLATION. NOTE: PRODUCT APPROVAL IS ALSO REQUIRED
 FOR EACH STRUCTURAL CONNECTOR. DCA RULE 9N-3. (2) POST
 SIZE DOESN'T MATCH SIZE SHOWN ON 2ND FLOOR LAYOUT. SEC.
 107.2.1 CITY AMENDMENTS.
  
 H) GUARDRAIL SECTION REFERENCED ON THE 2ND FLOOR LAYOUT
 AND KNEE WALL SECTION IS INCORRECT. SEE THE 2010
 FBC-RESIDENTIAL CODE FOR CORRECT REFERENCE AND REVISE
 AS REQUIRED.
  
 4-PROVIDE PRODUCT APPROVAL (2 COPIES) AS REQUIRED BY
 DCA RULE 9N-3 FOR :
 A) ALL SIMPSON STRUCTURAL CONNECTORS SPECIFIED ON ALL
 FRAMING PLANS AND DETAILS. PROVIDE FLORIDA PRODUCT
 APPROVAL COVER PAGE OR ENGINEER TO LIST FLORIDA PRODUCT
 APPROVAL NEXT TO THE SPECIFIED CONNECTOR.
  
 5- ENGINEER IS USING OLD SEAL. NEED TO USE CURRENT SEAL
 WITH THE WORDING "LICENSE" NOT "CERTIFICATE". SEC.
 61G15-23.001. F.A.C.
  
 6- IT'S NOT CLEAR WHY SUBMITTING PRODUCT APPROVALS FOR
 SINGLE HUNG WINDOWS, WINDOW MULLIONS. THE PLANS WERE
 REVISED AND THEY DON'T SHOW ANY SCOPE OF WORK OF NEW
 WINDOWS OR WINDOW REPLACEMENT. IF THERE IS GOING TO BE
 WINDOW REPLACEMENT, THEN REVISE PLANS AS REQUIRED
 SHOWING AREAS OF WORK. SPECIFY SIZE SIZE AND TYPE OF
 EXISTING WINDOWS AND PROPOSED WINDOWS. SEC. 604 OF 2010
 FBC-EXISTING BUILDING. REVISE VALUATION DECLARED IN THE
 PERMIT APPLICATION ACCORDINGLY.
  
 7- VALUATION DECLARED IN THE PERMIT APPLICATION IS TOO
 LOW. VALUATION TO INCLUDE ALL LABOR, MATERIALS,
 CONTRACTOR'S OVERHEAD AND PROFIT AND DESIGN
 PROFESSIONAL FEES AS REQUIRED BY SEC. 109.3 CITY
 AMENDMENTS TO FBC. PROVIDE COPY OF SIGNED CONTRACT.
  
 *** PLEASE PROVIDE RESPONSE LETTER ADDRESSING EACH
 COMMENT TO EXPEDITE THE REVIEW PROCESS.
  
  