Plan Review Notes For Permit 14090220 |
Permit Number |
14090220 |
|
Review Stop |
P |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2014-09-24 11:02:31 | WPB AMEND. TO 2010 FBC SEC.107.2.1. | | 1) INDICATE ON THE PLAN IF THE RANGE IN THE KITCHEN IS | | GAS OR ELECTRIC AND IF IT IS EXISTING TO REMAIN, NEW, | | OR EXISTING TO BE REPLACED. | | 2) INDICATE ON THE PLAN IF THE WASHER & DRYER ARE | | EXISTING TO REMAIN, NEW, OR EXISTING TO BE REPLACED. | | INDICATE ON THE PLAN IF THE DRYER IS ELECTRIC OR GAS. | | 3) A YELLOW TRACER WIRE SHALL BE INSTALLED ADJACENT TO | | UNDERGROUND NONMETALLIC PIPING. INSTALLATION SHALL | | COMPLY W/2010FGC SEC.404.15.3, & FBCR, SEC. G2415.15.3. | | 4) THE MAXIMUM ALLOWED BTU'S ON 1 1/2 " PE PIPE IN | | ACCORDANCE WITH GAS TABLE 402.4 (19 ) AND 2010 FBCR | | TABLE G2413.4 ( 7 ) AT 60 FT. IS 721,000 BTU'S. THE BTU | | LOAD SHOWN ON THE PLAN IS 750,000 BTU'S. THEREFORE THE | | GAS SYSTEM AS DESIGNED IS UNDERSIZED INCLUDING THE 3/4" | | LINES. | | 5) SHOW THE LENGTH OF EACH SECTION OF THE SCH.40 STEEL | | PIPE. | | 6) MANUFACTURER'S SPECIFICATION SHEETS SHALL BE | | SUBMITTED FOR ALL GAS APPLIANCES AT THE TIME OF PERMIT | | APPLICATION SUBMITTAL FOR THE GAS PERMIT.ALL EQUIPMENT | | SHALL BE LISTED AND LABELED PER FGC SEC.301.3 & 2010 | | FBCR SEC. G2404.3 | | 7) GAS INSTALLATION SHALL BE UNDER A SEPARATE. | | | | PLUMBING PLAN REVIEW | | TIM LARGE | | CHIEF PLUMBING INSPECTOR | | 561-805-6692 | | [email protected] | | | | | | | | |
|