2014-10-09 07:38:50 | PLAN REVIEW COMMENTS |
| |
| |
| 1ST REVIEW: FBC 2010 |
| ROBERT MCDOUGAL, CBO |
| COMMERCIAL COMBINATION PLANS EXAMINER |
| (561) 805-6714 |
| [email protected] |
| |
| ELECTRICAL |
| |
| PLEASE ADDRESS THE ITEMS NOTED BELOW: |
| |
| 1) NEC 220.40 - SUBMIT ELECTRICAL LOAD CALCULATIONS. |
| |
| 2) FBC 107.3.5.3 - SUBMIT A PANEL SCHEDULE. |
| |
| 3) FBC-R 315.1 - PROVIDE CARBON MONOXIDE ALARMS WITHIN |
| 10 FEET OF EACH SLEEPING ROOM. |
| |
| 4) FBC- 107.3.5.3 - PROVIDE SMOKE ALARMS PURSUANT TO |
| FBC-R 314.3.1 AS REQUIRED FOR NEW DWELLINGS. SMOKE |
| ALARMS ARE ALSO REQUIRED ON EACH ADDITIONAL STORY OF |
| THE DWELLING. |
| R314.3 LOCATION. |
| SMOKE ALARMS SHALL BE INSTALLED IN THE FOLLOWING |
| LOCATIONS: |
| 1. IN EACH SLEEPING ROOM. |
| 2. OUTSIDE EACH SEPARATE SLEEPING AREA IN THE IMMEDIATE |
| VICINITY OF THE BEDROOMS. |
| 3. ON EACH ADDITIONAL STORY OF THE DWELLING, INCLUDING |
| BASEMENTS AND HABITABLE ATTICS BUT NOT INCLUDING CRAWL |
| SPACES AND UNINHABITABLE ATTICS. IN DWELLINGS OR |
| DWELLING UNITS WITH SPLIT LEVELS AND WITHOUT AN |
| INTERVENING DOOR BETWEEN THE ADJACENT LEVELS, A SMOKE |
| ALARM INSTALLED ON THE UPPER LEVEL SHALL SUFFICE FOR |
| THE ADJACENT LOWER LEVEL PROVIDED THAT THE LOWER LEVEL |
| IS LESS THAN ONE FULL STORY BELOW THE UPPER LEVEL. |
| WHEN MORE THAN ONE SMOKE ALARM IS REQUIRED TO BE |
| INSTALLED WITHIN AN INDIVIDUAL DWELLING UNIT THE ALARM |
| DEVICES SHALL BE INTERCONNECTED IN SUCH A MANNER THAT |
| THE ACTUATION OF ONE ALARM WILL ACTIVATE ALL OF THE |
| ALARMS IN THE INDIVIDUAL UNIT. |
| |
| |
| |
| |