2014-10-09 07:38:50PLAN REVIEW COMMENTS
  
  
 1ST REVIEW: FBC 2010
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 ELECTRICAL
  
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) NEC 220.40 - SUBMIT ELECTRICAL LOAD CALCULATIONS.
  
 2) FBC 107.3.5.3 - SUBMIT A PANEL SCHEDULE.
  
 3) FBC-R 315.1 - PROVIDE CARBON MONOXIDE ALARMS WITHIN
 10 FEET OF EACH SLEEPING ROOM.
  
 4) FBC- 107.3.5.3 - PROVIDE SMOKE ALARMS PURSUANT TO
 FBC-R 314.3.1 AS REQUIRED FOR NEW DWELLINGS. SMOKE
 ALARMS ARE ALSO REQUIRED ON EACH ADDITIONAL STORY OF
 THE DWELLING.
 R314.3 LOCATION.
 SMOKE ALARMS SHALL BE INSTALLED IN THE FOLLOWING
 LOCATIONS:
 1. IN EACH SLEEPING ROOM.
 2. OUTSIDE EACH SEPARATE SLEEPING AREA IN THE IMMEDIATE
 VICINITY OF THE BEDROOMS.
 3. ON EACH ADDITIONAL STORY OF THE DWELLING, INCLUDING
 BASEMENTS AND HABITABLE ATTICS BUT NOT INCLUDING CRAWL
 SPACES AND UNINHABITABLE ATTICS. IN DWELLINGS OR
 DWELLING UNITS WITH SPLIT LEVELS AND WITHOUT AN
 INTERVENING DOOR BETWEEN THE ADJACENT LEVELS, A SMOKE
 ALARM INSTALLED ON THE UPPER LEVEL SHALL SUFFICE FOR
 THE ADJACENT LOWER LEVEL PROVIDED THAT THE LOWER LEVEL
 IS LESS THAN ONE FULL STORY BELOW THE UPPER LEVEL.
 WHEN MORE THAN ONE SMOKE ALARM IS REQUIRED TO BE
 INSTALLED WITHIN AN INDIVIDUAL DWELLING UNIT THE ALARM
 DEVICES SHALL BE INTERCONNECTED IN SUCH A MANNER THAT
 THE ACTUATION OF ONE ALARM WILL ACTIVATE ALL OF THE
 ALARMS IN THE INDIVIDUAL UNIT.
  
  
  
  