Date |
Text |
2014-10-02 09:54:12 | RESIDENTIAL (R3) ADDITION, BUILDING REVIEW COMMENTS. |
| CODE: 2010 FBC. |
| |
| 1- PROVIDE PRODUCT APPROVAL (2 COPIES) AS REQUIRED BY |
| DCA RULE 9N-3 FOR: |
| A) DOOR AT NEW STORAGE AREA AS SHOWN ON PLANS. |
| |
| B) NEW DECK HOLLOW CORE PANELS. |
| |
| 2- DESIGNER OF RECORD TO REVIEW AND APPROVE IN WRITING |
| (NOT SIGNING AND SEALING) ALL PRODUCT APPROVALS AS |
| REQUIRED BY SEC. 107.3.4.1 OF CITY AMENDMENTS TO FBC. |
| |
| 3- SHEET A-5.1: PROVIDE COMPLETE DETAILS AND |
| SPECIFICATIONS FOR THE INSTALLATION OF STEEL BEAM B-1 |
| AT THE BEARING POINTS AND HOW ARE THE DECKING HOLLOW |
| CORE PANELS ATTACHED TO THE BEAM. SEC. R301 OF 2010 |
| FBC-RESIDENTIAL. |
| |
| 4- NEW HOLLOW CORE DECK PLAN ON SHEET A-5.1 CALLS FOR |
| 6" THICK HOLLOW CORE PANELS, WHILE WALL SECTIONS ON |
| SHEET A-5.4 AND SHEET A-5.5 CALL FOR 8" THICK HOLLOW |
| CORE PANELS. REVISE/CLARIFY AS REQUIRED TO MATCH AND |
| COORDINATE WITH PRODUCT APPROVAL SUBMITTED. SEC. |
| 107.2.1 CITY AMENDMENTS TO FBC. |
| |
| 5- PROVIDE COMPLETE INFORMATION FOR THE REQUIRED |
| HANDRAIL AT STAIRWAY LEADING TO THE SECOND FLOOR DECK |
| AS REQUIRED BY SEC. R311.7.7 OF 2010 FBC-RESIDENTIAL. |
| |
| 6- PROVIDE COMPLETE INFORMATION FOR THE SECOND FLOOR |
| DECK GUARDRAILS TO SHOW COMPLIANCE WITH THE DESIGN |
| LOADS REQUIRED BY TABLE R301.5 AND THE REQUIREMENTS OF |
| SEC. R312 OF 2010 FBC-RESIDENTIAL. ALSO, PROVIDE |
| COMPLETE DETAILS AND SPECIFICATIONS FOR THE SOLID |
| GUARDRAIL AS SHOWN ON ELEVATIONS. |
| |
| 7- VALUATION DECLARED IN THE PERMIT APPLICATION IS TOO |
| LOW. VALUATION TO INCLUDE ALL LABOR, MATERIALS, |
| CONTRACTOR'S OVERHEAD AND PROFIT AND DESIGN |
| PROFESSIONAL FEES AS REQUIRED BY SEC. 109.3 CITY |
| AMENDMENTS TO FBC. REVISE VALUATION TO INCLUDE ALL THE |
| PAVERS AND STONE VENEER WORK SHOWN ON PLANS, PLUS THE |
| ARCHITECT'S FEES. |
| |
| *** PLEASE PROVIDE RESPONSE LETTER ADDRESSING EACH |
| COMMENT TO EXPEDITE THE REVIEW PROCESS. |
| *** PLEASE REMOVE AND REPLACE ALL REVISED SHEETS. |
| |
| IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT |
| JULIO GOMEZ |
| COMMERCIAL COMBINATION PLANS EXAMINER |
| DEVELOPMENT SERVICE DEPARTMENT |
| (561)805-6712 |
| [email protected] |
2014-09-24 11:44:53 | I MISTAKENLY PLACED MY NAME IN THE REVIEWER COLUMN FOR |
| BUILDING. THIS PLAN NEEDS A STRUCTURAL PLAN REVIEW.TKL |