Plan Review Notes For Permit 14090214 |
Permit Number |
14090214 |
|
Review Stop |
B |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2014-09-09 11:53:41 | REVISION TO CHANGE FROM SYSTEM W-9 TO SYSTEM W-7 OF THE | | MULE-HIDE MODIFIED BITUMEN ROOF SYSTEM FL10497. | | | | 2010 FBC | | | | DENIED BY BUILDING | | | | 1) THE W-7 SYSTEM HAS PRELIMINARY ATTACHED INSULATION | | AND A BASE SHEET FASTENED WITH OMG, DEKFAST OR TRUFAST | | FASTENERS. 12" OC IN THE 4" LAP AND 12" OC IN TWO | | STAGGERED CENTER ROWS. THIS SYSTEM DOES NOT CORRESPOND | | WITH THE INFORMATION IS THE ENGINEERING THAT WAS | | SUBMITTED FOR ENHANCED FASTENING. | | | | ROBERT MCDOUGAL | | BLDG. PLAN REVIEW | | (561)805-6714 | | [email protected] |
|