Plan Review Notes For Permit 14090204 |
Permit Number |
14090204 |
|
Review Stop |
FIRE |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2014-09-09 18:57:18 | PERMIT # 14090204 | | REVIEW COMMENTS - FIRE DEPARTMENT | | | | PLAN REVIEW FAILED: | | 1) INSUFFICIENT COVERAGE FOR STORE AREA. DEVICES NEED | | TO BE RAISED TO 110CD. ADDITIONAL DEVICES ARE NEEDED | | FOR FITTING ROOM AREA AND FOR STOCK AREA. | | | | 2) PER APPROVED MASTER PLANS: MAIN FACP FOR THIS | | BUILDING IS TO BE THE ONLY PANEL TO NOTIFY THE FIRE | | DEPARMENT. NOTIFICATION WILL DESIGNATE SPECIFIC ADDRESS | | OF TENANT WHERE TROUBLE IS LOCATED. EACH BUILDING SHALL | | ALARM/EVACUATE ONLY THE SPACES IN THAT BUILDING (IE AN | | ALARM IN "B" WILL NOT EVACUATE ANY SPACE IN "A", "BII", | | OR "C". EACH TENANT SPACE FACP SHALL BE CONNECTED TO | | MAIN FACP FOR THIS BUILDING VIA MODULES. TENANT SYSTEM | | SHALL BE COMPATIBLE WITH NOTIFIER OR EQUAL APPROVED | | MAIN FACP/HARDWARE EACH FLOW/TAMPER SHALL BE ZONED SO | | THAT AN ALARM WILL SOUND FOR EACH BUILDING SEPARATELY. | | | | | | SUE ELLEN CALDERON | | FIRE INSPECTOR & INVESTIGATOR | | OFFICE OF THE FIRE MARSHAL | | WEST PALM BEACH FIRE RESCUE | | |
|