Plan Review Notes For Permit 14090204 |
Permit Number |
14090204 |
|
Review Stop |
E |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2014-09-15 16:33:06 | DATE: 9/15/2014 | | PROJECT: OLD NAVY | | PERMIT#: 14090204 | | CODE: 2008 EDITION OF THE NEC | | 2010 EDITION OF THE FBC | | 2010 WPB AMENDMENTS TO THE FBC, CHAPTER 1, | | ADMINISTRATION, 2012 FBC SUPPLEMENTS. | | | | 1ST ELECTRICAL PLAN REVIEW | | ACTION: DENIED | | | | 1) FOR THE SAME REASON AS THE FIR INSPECTOR. REVISE | | PLANS FOR OPERATION TO COMPLY WITH ORIGINAL DESIGN. | | ADDITIONALLY, ONCE COMPLETE AND OPERATIONAL IN ADDITION | | TO THE SYSTEM OPERATING AS STATED IN THE FIRE | | INSPECTORS COMMENTS THE PANEL IN THE TENANT SPACE MUST | | BE ABLE TO BE SILENCED AND OR RESET FROM THE MASTER | | CONTROL PANEL. | | | | 2) THE DEDICATED 120V ELETRICAL CIRCUIT FEEDING THE | | CONTROL PANEL SHAL BE INSTALLED BY A CERTIFIED | | ELECTRICAL CONTRACTOR LICENSED AND INSURED FOR THE | | SCOPE OF WORK INVOLVED. | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | RE-SUBMITTAL FORM. SEE LINK: | | HTTP://WPB.ORG/DEVELOPMENT/WP-CONTENT/UPLOADS/SITES/33/ | | 2013/09/APPLICATION_RESUBMITTAL_FORM_04132010.PDF | | | | ADDITIONALLY, PLEASE INSERT CORRECTED PAGES INTO | | SUBMITTAL PACKAGE AND LEAVE THE PREVIOUSLY REVIEWED | | SHEETS FOR COMPARATIVE REVIEW. | | | | DAVID HAYES, ELECTRICAL PLANS EXAMINER, PX3421, | | 561-805-6717 OR [email protected] | | |
|