2014-09-15 16:33:06DATE: 9/15/2014
 PROJECT: OLD NAVY
 PERMIT#: 14090204
 CODE: 2008 EDITION OF THE NEC
 2010 EDITION OF THE FBC
 2010 WPB AMENDMENTS TO THE FBC, CHAPTER 1,
 ADMINISTRATION, 2012 FBC SUPPLEMENTS.
  
 1ST ELECTRICAL PLAN REVIEW
 ACTION: DENIED
  
 1) FOR THE SAME REASON AS THE FIR INSPECTOR. REVISE
 PLANS FOR OPERATION TO COMPLY WITH ORIGINAL DESIGN.
 ADDITIONALLY, ONCE COMPLETE AND OPERATIONAL IN ADDITION
 TO THE SYSTEM OPERATING AS STATED IN THE FIRE
 INSPECTORS COMMENTS THE PANEL IN THE TENANT SPACE MUST
 BE ABLE TO BE SILENCED AND OR RESET FROM THE MASTER
 CONTROL PANEL.
  
 2) THE DEDICATED 120V ELETRICAL CIRCUIT FEEDING THE
 CONTROL PANEL SHAL BE INSTALLED BY A CERTIFIED
 ELECTRICAL CONTRACTOR LICENSED AND INSURED FOR THE
 SCOPE OF WORK INVOLVED.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. SEE LINK:
 HTTP://WPB.ORG/DEVELOPMENT/WP-CONTENT/UPLOADS/SITES/33/
 2013/09/APPLICATION_RESUBMITTAL_FORM_04132010.PDF
  
 ADDITIONALLY, PLEASE INSERT CORRECTED PAGES INTO
 SUBMITTAL PACKAGE AND LEAVE THE PREVIOUSLY REVIEWED
 SHEETS FOR COMPARATIVE REVIEW.
  
 DAVID HAYES, ELECTRICAL PLANS EXAMINER, PX3421,
 561-805-6717 OR [email protected]
  