2014-09-06 13:24:14 | DATE: 9/6/2014 |
| PROJECT: AVACODO GRILL |
| PERMIT#: 14060973 REVISION #14090187 |
| CODE: 2008 EDITION OF THE NEC |
| 2010 EDITION OF THE FBC |
| 2010 WPB AMENDMENTS TO THE FBC, CHAPTER 1, |
| ADMINISTRATION, 2012 FBC SUPPLEMENTS. |
| |
| 1ST ELECTRICAL PLAN REVIEW ON REVISION #14090187 |
| ACTION: DENIED |
| |
| 1) ALL INFORMATION, DRAWINGS, SPECIFICATIONS AND |
| ACCOMPANYING DATA SHALL BEAR THE NAME AND SIGNATURE OF |
| THE PERSON RESPONSIBLE FOR THE DESIGN. WPB AMENDMENTS |
| TO FBC 107.2.1 THE PLAN IS NOT SIGNED BY THE DESIGNER |
| OF RECORD. |
| |
| 2) THE SHEET NUMBER DOES NO COINCIDE WITH THE SHEET |
| NUMBER ON THE PERMIT SET. THE SHEET #A5 ON THE PERMIT |
| SET IS THE PLUMBING PLAN. THE ELECTRICAL PLAN IS ON |
| SHEET #A4. REVISE THE SHEET NUMBER TO COINCIDE WITH THE |
| APPROVED PERMIT SET. |
| |
| 3) THERE IS NO LOW VOLTAGE DATA CABLING SHOWN ON THE |
| MASTER PERMIT SET. A SEPARATE PERMIT APPLICATION |
| ACCOMPANIED BY MANUFACTURERS EQUIPMENT SUBMITTALS, AND |
| SHOP DRAWINGS FOR ANY AND ALL OF THE FOLLOWING: POS |
| SYSTEM, FIRE ALARM, SECURITY, CCTV, DATA/COM, NETWORK, |
| STRUCTURED CABLING, AUDIO(SPEAKERS)/VIDEO, AND SIGNAGE. |
| |
| WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| RE-SUBMITTAL FORM. SEE LINK: |
| HTTP://WPB.ORG/DEVELOPMENT/WP-CONTENT/UPLOADS/SITES/33/ |
| 2013/09/APPLICATION_RESUBMITTAL_FORM_04132010.PDF |
| |
| ADDITIONALLY, PLEASE INSERT CORRECTED PAGES INTO |
| SUBMITTAL PACKAGE AND LEAVE THE PREVIOUSLY REVIEWED |
| SHEETS FOR COMPARATIVE REVIEW. |
| |
| DAVID HAYES, ELECTRICAL PLANS EXAMINER, PX3421, |
| 561-805-6717 OR [email protected] |
| |