Plan Review Notes
Plan Review Notes For Permit 14090187
Permit Number 14090187
Review Stop E
Sequence Number 1
Notes
Date Text
2014-09-06 13:24:14DATE: 9/6/2014
 PROJECT: AVACODO GRILL
 PERMIT#: 14060973 REVISION #14090187
 CODE: 2008 EDITION OF THE NEC
 2010 EDITION OF THE FBC
 2010 WPB AMENDMENTS TO THE FBC, CHAPTER 1,
 ADMINISTRATION, 2012 FBC SUPPLEMENTS.
  
 1ST ELECTRICAL PLAN REVIEW ON REVISION #14090187
 ACTION: DENIED
  
 1) ALL INFORMATION, DRAWINGS, SPECIFICATIONS AND
 ACCOMPANYING DATA SHALL BEAR THE NAME AND SIGNATURE OF
 THE PERSON RESPONSIBLE FOR THE DESIGN. WPB AMENDMENTS
 TO FBC 107.2.1 THE PLAN IS NOT SIGNED BY THE DESIGNER
 OF RECORD.
  
 2) THE SHEET NUMBER DOES NO COINCIDE WITH THE SHEET
 NUMBER ON THE PERMIT SET. THE SHEET #A5 ON THE PERMIT
 SET IS THE PLUMBING PLAN. THE ELECTRICAL PLAN IS ON
 SHEET #A4. REVISE THE SHEET NUMBER TO COINCIDE WITH THE
 APPROVED PERMIT SET.
  
 3) THERE IS NO LOW VOLTAGE DATA CABLING SHOWN ON THE
 MASTER PERMIT SET. A SEPARATE PERMIT APPLICATION
 ACCOMPANIED BY MANUFACTURERS EQUIPMENT SUBMITTALS, AND
 SHOP DRAWINGS FOR ANY AND ALL OF THE FOLLOWING: POS
 SYSTEM, FIRE ALARM, SECURITY, CCTV, DATA/COM, NETWORK,
 STRUCTURED CABLING, AUDIO(SPEAKERS)/VIDEO, AND SIGNAGE.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. SEE LINK:
 HTTP://WPB.ORG/DEVELOPMENT/WP-CONTENT/UPLOADS/SITES/33/
 2013/09/APPLICATION_RESUBMITTAL_FORM_04132010.PDF
  
 ADDITIONALLY, PLEASE INSERT CORRECTED PAGES INTO
 SUBMITTAL PACKAGE AND LEAVE THE PREVIOUSLY REVIEWED
 SHEETS FOR COMPARATIVE REVIEW.
  
 DAVID HAYES, ELECTRICAL PLANS EXAMINER, PX3421,
 561-805-6717 OR [email protected]
  