Plan Review Notes
Plan Review Notes For Permit 14090076
Permit Number 14090076
Review Stop E
Sequence Number 3
Notes
Date Text
2014-10-03 14:46:163RD REVIEW: FBC 2010
  
 REDLINED PLAN TO REQUIRE PER NEC 210.63 - A GFI SERVICE
 OUTLET FOR WITHIN 25' OF MECHANICAL EQUIPMENT.
  
 STEVEN KENNEDY, CBO
 CHIEF PLANS EXAMINER