2014-11-08 16:03:55****CORRECTIONS****
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 FROM PREVIOUS LIST:
  
 1. CLEAR OPENINGS FOR THE PROPOSED WINDOWS STATED ARE
 NOT POSSIBLE. CLEAR OPENING PROPOSED IS OVER HALF OF
 THE WINDOW HEIGHT. PROVIDE CLEAR OPENING FROM THE
 MANUFACTURER. FBC R310, FBC EB 604.1
  
 2ND REVIEW:
  
 BASED ON JELD-WEN'S WEBSITE, FOR A FIN INSTALLATION,
 THE MEETING RAIL (1.25") AND FRAME (1.25"+.75"+1 3/16"
 = 3 3/16"), APPROXIMATELY 4" SHOULD BE DEDUCTED FROM
 HALF THE WINDOW SIZE, GIVING AN APPROXIMATE CLEAR
 OPENING (AKA "DAYLIGHT OPENING") OF 20" HIGH. THIS
 EXCEEDS THE 5% CLEAR OPENING REDUCTION PERMITTED.
  
 HTTP://WWW.JELD-WEN.COM/CATALOG/WINDOWS/PREMIUM-ATLANTI
 C/ALUMINUM/SINGLE-HUNG
  
 FOR THE 48" HIGH WINDOW, NEW DIMENSION FOR CLEAR
 OPENING NOT PROVIDED. HOWEVER, USING THE DIMENSIONS
 FROM THEIR WEBSITE FOR A FIN WINDOW (FLANGE FRAME IS
 LARGER, SO AN EVEN SMALLER CLEAR OPENING WOULD RESULT),
 THE PROPOSED WINDOW EXCEEDS THE 5% REDUCTION.
  
 11/12 - SPOKE WITH APPLICANT; SUGGESTED A CASEMENT
 WINDOW FOR THIS OPENING
  
  
  
  
  
  
  
  