Plan Review Notes
Plan Review Notes For Permit 14090037
Permit Number 14090037
Review Stop B
Sequence Number 2
Notes
Date Text
2014-09-18 08:13:50BUILDING PLAN REVIEW
 REVISION: 14090037
 PERMIT: 13030782
 ADD: 326 FERN ST
 CONT: STRATICON
 TEL: (561)436-4733
  
 2010 FLORIDA BUILDING CODE W
 * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION
 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013.
  
 2010 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 2ND REVIEW
 DATE: THURS. SEPT. 18/2014
 ACTION: DENIED
  
 1) COMPLIED. THRESHOLD BUILDING (3) SETS OF DOCUMENTS.
  
 2) THE HAND DRAWN SKETCH FOR UNIT # 12331 HAS A PARTIAL
 SHOP DRAWING STAMP, IT DOES NOT INDICATE IF APPROVED OR
 NOT.2010 FBC-B 1609.1.2 PROTECTION OF OPENINGS,
 1609.6.4.41 COMPONENTS & CLADDING
  
  
 3) NOA # 11-1031.06 CGI WINDOWS SERIES 130 SENTENEL.
 SHEET 2 OF 6 HAS HIGHLIGHTED 60 X 60 INCH WINDOWS WITH
 GLASS TYPE "C" & "C1" WITH A +/- 48.8. THE VASD
 PRESSURES ZONE # 4 ARE =/- 50.1 AND FOR ZONE # 5 ARE
 +50.1 & -91.3. THE VASD PRESSURES ARE LOW FOR THIS
 WINDOW SIZE.2010 FBC-B 1609.1.2 PROTECTION OF OPENINGS,
 1609.6.4.41 COMPONENTS & CLADDING
  
  
 4A) NOA # 12-0706.03 CGI DOOR SERIES "450" OUTSWING
 GLAZED W/WO SIDELITES. WINDOW NOA # 11-1031.06
 INDICATES HAND WRITTEN 1ST FLOOR ONLY SECTION OF
 STOREFRONT WITHIN 8.2 FT OF EDGE OF BUILDING (ZONE # 5)
 PRESSURES +50.1/ -91.3 VASD. NOTE THIS SHEET
 INDICATESTHE STANDARD HARDWARE IS ONLY GOOD FOR +/-
 70.2. 2010 FBC-B 1609.1.2 PROTECTION OF OPENINGS,
 1609.6.4.41 COMPONENTS & CLADDING
  
  
 4B) NOA # 12-0706.03 CGI DOOR SERIES "450" OUTSWING
 GLAZED W/WO SIDELITES. SHEET 1.1 OF 7 INDICATES
 (HIGHLIGHTED BOTH 10A & 10AA DOOR HEIGHT OF 96 3/4 IN.
 THE PRESSURES FOR 10A ARE +/- 90.0. LOW REQUIRED 91.3
 VASD. 2010 FBC-B 1609.1.2 PROTECTION OF OPENINGS,
 1609.6.4.41 COMPONENTS & CLADDING
  
  
 4C) NOA # 12-0706.03 CGI DOOR SERIES "450" OUTSWING
 GLAZED W/WO SIDELITES. SHEET 7 OF 7 MULLION ANCHORS NOT
 PROVIDED (HIGHLIGHTED) ON
 THE PLANS.
  
 5) NOA # 12-0203.13 CGI WINDOW & DOOR, CLIPPED EXTRUDED
 ALUMINUM MULLION. MULLION SIZES, RE-INFORCED OR NOT,
 NOR ANCHORS ARE IDENTIFIED NOR THE PRESSURES. 2010
 FBC-B 1609.1.2 PROTECTION OF OPENINGS, 1609.6.4.41
 COMPONENTS & CLADDING.
  
 NOTE THE 1ST HISTORIC REVIEW NOT SHOWN AS REVIEWED WILL
 NEED TO SEND THE 2ND PACKAGE TO HISTORICS FOR REVIEW.
 NOTE THE NOA # 11-1031.06 CGI WINDOWS SERIES 130
 SENTENEL SHOWS THE MUTTINS AS A OPTION, THIS MAY BE A
 ISSUE WITH HISTORICS, TO KEEP THE HISTORICAL FEATURES
 OF THE BUILDING, HISTORIC REVIEW IS REQUIRED.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION &
 REMOVE & REPLACE ANY PAGES AS NECESSARY. A TRANSMITTAL
 LETTER LISTING THE ORIGINAL REVIEW COMMENT NUMBER, WITH
 A DESCRIPTION OF THE REVISION MADE, IDENTIFYING THE
 SHEET OR SPECIFICATION PAGE WHERE THE CHANGES CAN BE
 FOUND WILL HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR
 YOUR ANTICIPATED COOPERATION.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  
  