2014-09-02 15:31:51 | DATE: 9/2/2014 |
| PROJECT: TRUMP PLAZA BATHROOM REMODEL |
| PERMIT#: 14090028 |
| CODE: 2008 EDITION OF THE NEC |
| 2010 EDITION OF THE FBC |
| 2010 WPB AMENDMENTS TO THE FBC, CHAPTER 1, |
| ADMINISTRATION, 2012 FBC SUPPLEMENTS. |
| |
| 1ST ELECTRICAL PLAN REVIEW |
| ACTION: DENIED |
| |
| 1) PROVIDE A FLOOR PLAN INDICATING THE LOCATION OF |
| PANEL "A" WPB, FBC 107.2.1 |
| |
| 2) PROVIDE A PANEL SCHEDULE AND LOAD CALCULATION FOR |
| PANEL "A" MAKING CLEAR ANY EXISTING LOADS TO BE |
| RELOCATED OR REMOVED. INDICATE CLEARLY IS IT A MAIN |
| BREAKER PANEL OR A MLO. THE PANEL ON THE PLAN INDICATES |
| BOTH. |
| |
| 3) PROVIDE A RISER DIAGRAM INDICATING THE "EXISTING |
| PANEL A" AND WHERE IT IS FED FROM INDICATING THE |
| CAPACITY TO FEED THE ADDITIONAL LOAD. |
| |
| 4) INDICATE ON THE PLANS ANY EXISTING AND/OR NEW |
| EMERGENCY LIGHTING PROVIDING A SAFE AND ILLUMINATED |
| MEANS OF EGRESS. NFPA 101 SECTION 7.9 |
| |
| 5) PROVIDE MANUFACTURER PRODUCT SPECIFICATIONS AND |
| INSTALLATION DETAILS FOR SAUNA. INDICATE ACCESS FOR |
| RECEPTACLE FEED FOR SAUNA AFTER THE INSTALLATION OF THE |
| SAUNA. NEC 110.3, 110.26 |
| |
| WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| RE-SUBMITTAL FORM. SEE LINK: |
| HTTP://WPB.ORG/DEVELOPMENT |
| /WP-CONTENT/UPLOADS/SITES/33/2013/09/APPLICATION_RESUBM |
| ITTAL_FORM_04132010.PDF |
| |
| ADDITIONALLY, PLEASE INSERT CORRECTED PAGES INTO |
| SUBMITTAL PACKAGE AND LEAVE THE PREVIOUSLY REVIEWED |
| SHEETS FOR COMPARATIVE REVIEW. |
| |
| DAVID HAYES, ELECTRICAL PLANS EXAMINER, PX3421, |
| 561-805-6717 OR [email protected] |
| |