2014-09-08 17:30:56PLAN REVIEW COMMENTS
  
 1ST REVIEW: FBC 2010
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 MECHANICAL
  
 1) THE ENERGY FORM 402-2010 THAT WAS SUBMITTED APPEARS
 TO CONTAIN SO ERRORS. PLEASE CORRECT.
 - THE CONDITIONED AREA IS LISTED AS 1040 SQFT AND THE
 CEILING AREA IS LISTED AS 537 SQFT.
 - THE AIR HANDLER UNIT LOCATION IS SPECIFIED AS THE
 GARAGE. THIS PLANS SHOWS THE UNIT IN A HALL CLOSET. THE
 PLAN DOES NOT SHOW A GARAGE.
 - THE SEER IS LISTED AS 16 ON THE FORM AND THE AHRI
 CERTIFICATION THAT WAS SUBMITTED HAS A SEER RATING OF
 13.
  
 2) THE EQUIPMENT SIZING CALCULATIONS SPECIFY THE TOTAL
 COOLING REQUIRED IS 27,082 BTUH OR 2.26 TONS. THE A/C
 CHANGE OUT FORM AND THE AHRI CERTIFICATION FORM ARE FOR
 A 3 TON SYSTEM. BASED ON THE SIZING CALCULATIONS AND
 FBC ENERGY CONSERVATION SEC. 403.6.1.1, THE MAXIMUM
 COOLING EQUIPMENT SIZE IS
 403.6.1.1 COOLING EQUIPMENT CAPACITY.
 COOLING ONLY EQUIPMENT SHALL BE SELECTED SO THAT ITS
 TOTAL CAPACITY IS NOT LESS THAN THE CALCULATED TOTAL
 LOAD BUT NOT MORE THAN 1.15 TIMES GREATER THAN THE
 TOTAL LOAD CALCULATED ACCORDING TO THE PROCEDURE
 SELECTED IN SECTION 403.6, OR THE CLOSEST AVAILABLE
 SIZE PROVIDED BY THE MANUFACTURER?S PRODUCT LINES. THE
 CORRESPONDING LATENT CAPACITY OF THE EQUIPMENT SHALL
 NOT BE LESS THAN THE CALCULATED LATENT LOAD.
  
 IN ORDER TO REDUCE PLAN REVIEW TIMES, PLEASE SUBMIT A
 RESPONSE LETTER INDICATING HOW EACH OF THE REVIEW
 COMMENTS HAS BEEN ADDRESSED.