2014-09-08 10:19:52 | PLAN REVIEW COMMENTS |
| |
| |
| 1ST REVIEW: FBC 2010 |
| ROBERT MCDOUGAL, CBO |
| COMMERCIAL COMBINATION PLANS EXAMINER |
| (561) 805-6714 |
| [email protected] |
| |
| ELECTRICAL |
| |
| PLEASE ADDRESS THE ITEMS NOTED BELOW: |
| |
| 1) SUBMIT TWO COPIES OF THE SPECIFICATIONS AND |
| ELECTRICAL REQUIREMENTS FOR THE RTE - 7 TANKLESS WATER |
| HEATER. FBC 107.2.1 |
| |
| 2) THE PANEL SCHEDULE SPECIFIES A 2 POLE 30 AMP BREAKER |
| FOR THE WATER HEATER. BASED ON PAST EXPERIENCE THIS MAY |
| BE TOO SMALL FOR A WHOLE HOUSE ELECTRIC WATER HEATER. |
| PLEASE REVIEW THE MANUFACTURER'S SPECS. FOR |
| REQUIREMENTS. NEC 422.11 |
| |
| 3) SHOW COMPLIANCE WITH NEC 440.11 AND 440.14 FOR A/C |
| EQUIPMENT DISCONNECT. |
| |
| 4) NEC 210.63 - PROVIDE A GFCI PROTECTED SERVICE OUTLET |
| FOR WITHIN 25' OF MECHANICAL EQUIPMENT. |
| |
| 5) SHOW THE LOCATION OF THE ELECTRIC METER ON THE |
| PLANS. |
| |
| 6) NEC 210.11 (C) (3) AT LEAST ONE 20 - AMP BRANCH |
| CIRCUIT SHALL BE PROVIDED TO SUPPLY BATHROOM RECEPTACLE |
| OUTLETS. |
| |
| 7) NEC 210.8 GROUND - FAULT CIRCUIT - INTERRUPTER |
| PROTECTION (A) (1) - (8) THE NEW RECEPTACLES SHOWN ON |
| THE PLAN FOR THE BATHROOM AND THE KITCHEN (WHERE THE |
| RECEPTACLES ARE INSTALLED TO SERVE THE COUNTER-TOP |
| SURFACES) ARE REQUIRED TO BE GFCI PROTECTED. |
| |
| 8) IF THE ELECTRIC SERVICE WILL BE CHANGED, IN ADDITION |
| TO THE 150 AMP PANEL, PROVIDE AN ELECTRIC SERVICE RISER |
| WITH WIRE SIZES, CONDUIT DETAIL AND GROUNDING DETAIL. |
| FBC- 107.3.5.3 |
| |
| IN ORDER TO REDUCE PLAN REVIEW TIMES, PLEASE SUBMIT A |
| RESPONSE LETTER INDICATING HOW EACH OF THE REVIEW |
| COMMENTS HAS BEEN ADDRESSED. |
| |
| |
| |