2014-09-08 10:19:52PLAN REVIEW COMMENTS
  
  
 1ST REVIEW: FBC 2010
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 ELECTRICAL
  
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) SUBMIT TWO COPIES OF THE SPECIFICATIONS AND
 ELECTRICAL REQUIREMENTS FOR THE RTE - 7 TANKLESS WATER
 HEATER. FBC 107.2.1
  
 2) THE PANEL SCHEDULE SPECIFIES A 2 POLE 30 AMP BREAKER
 FOR THE WATER HEATER. BASED ON PAST EXPERIENCE THIS MAY
 BE TOO SMALL FOR A WHOLE HOUSE ELECTRIC WATER HEATER.
 PLEASE REVIEW THE MANUFACTURER'S SPECS. FOR
 REQUIREMENTS. NEC 422.11
  
 3) SHOW COMPLIANCE WITH NEC 440.11 AND 440.14 FOR A/C
 EQUIPMENT DISCONNECT.
  
 4) NEC 210.63 - PROVIDE A GFCI PROTECTED SERVICE OUTLET
 FOR WITHIN 25' OF MECHANICAL EQUIPMENT.
  
 5) SHOW THE LOCATION OF THE ELECTRIC METER ON THE
 PLANS.
  
 6) NEC 210.11 (C) (3) AT LEAST ONE 20 - AMP BRANCH
 CIRCUIT SHALL BE PROVIDED TO SUPPLY BATHROOM RECEPTACLE
 OUTLETS.
  
 7) NEC 210.8 GROUND - FAULT CIRCUIT - INTERRUPTER
 PROTECTION (A) (1) - (8) THE NEW RECEPTACLES SHOWN ON
 THE PLAN FOR THE BATHROOM AND THE KITCHEN (WHERE THE
 RECEPTACLES ARE INSTALLED TO SERVE THE COUNTER-TOP
 SURFACES) ARE REQUIRED TO BE GFCI PROTECTED.
  
 8) IF THE ELECTRIC SERVICE WILL BE CHANGED, IN ADDITION
 TO THE 150 AMP PANEL, PROVIDE AN ELECTRIC SERVICE RISER
 WITH WIRE SIZES, CONDUIT DETAIL AND GROUNDING DETAIL.
 FBC- 107.3.5.3
  
 IN ORDER TO REDUCE PLAN REVIEW TIMES, PLEASE SUBMIT A
 RESPONSE LETTER INDICATING HOW EACH OF THE REVIEW
 COMMENTS HAS BEEN ADDRESSED.
  
  
  