2014-09-08 07:54:05PLAN REVIEW COMMENTS
  
  
 1ST REVIEW: FBC 2010
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 BUILDING
  
 1) FBC-107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS.
 ALL INFORMATION, DRAWINGS, SPECIFICATIONS AND
 ACCOMPANYING DATA SHALL BEAR THE NAME AND SIGNATURE OF
 THE PERSON RESPONSIBLE FOR THE DESIGN.
  
 2) THE WIND SPEED DESIGN IS NOT CONSISTENT WITH THE
 ADOPTED MAP FBC 119, CITY AMENDMENTS. THE DEFAULT
 WINDSPEED FOR THE CITY OF WEST PALM BEACH IS 170 MPH
 VULT AND 132 VASD (NOMINAL). IF YOU WISH TO USE LINEAR
 INTERPOLATION TO DETERMINE THE WIND SPEED BETWEEN THE
 WIND SPEED CONTOUR LINES, SUBMIT TWO COPIES OF THE DATA
 AND CALCULATIONS THAT WERE USED. THE REQUESTED
 INFORMATION IS REQUIRED TO BEAR THE NAME AND SIGNATURE
 OF THE PERSON RESPONSIBLE FOR IT.
  
 3) THE INSTALLATION DRAWINGS FOR THE WINDOW PRODUCT
 APPROVALS (NOA NO. 12-0127.16 & NOA NO. 12-0127.08)
 REQUIRED BY DCA RULE 9N-3 ARE MISSING INFORMATION. WHEN
 PRINTED THE DRAWINGS WERE NOT SHRUNK TO FIT ON THE 8.5
 X 11 INCH PAPER THAT WAS USED. FBC 107.2.1.4
  
 4) SUBMIT TWO COPIES OF PRODUCT APPROVALS FOR THE
 STRUCTURAL WINDOW MULLIONS (LIVING ROOM WINDOWS) AND
 THE SIMPSON COLUMN BASE AND CAP CONNECTORS AS REQUIRED
 BY DCA RULE 9N-3
  
 5) THE PLANS SPECIFY A SIMPSON EPS 4Z COLUMN BASE FOR
 THE 4 X 4 REPLACEMENT COLUMNS AT THE FRONT PORCH. THIS
 CONNECTOR IS REQUIRED TO BE EMBEDDED INTO CONCRETE AND
 THE PORCH SLAB IS EXISTING. PLEASE CLARIFY THE
 INSTALLATION. FBC 107.2.1
  
 6) R319.1.4 WOOD COLUMNS. WOOD COLUMNS SHALL BE
 APPROVED WOOD OF NATURAL DECAY RESISTANCE OR APPROVED
 PRESSURE-PRESERVATIVE-TREATED WOOD.
  
  
  
  