2014-09-08 07:54:05 | PLAN REVIEW COMMENTS |
| |
| |
| 1ST REVIEW: FBC 2010 |
| ROBERT MCDOUGAL, CBO |
| COMMERCIAL COMBINATION PLANS EXAMINER |
| (561) 805-6714 |
| [email protected] |
| |
| PLEASE ADDRESS THE ITEMS NOTED BELOW: |
| |
| BUILDING |
| |
| 1) FBC-107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS. |
| ALL INFORMATION, DRAWINGS, SPECIFICATIONS AND |
| ACCOMPANYING DATA SHALL BEAR THE NAME AND SIGNATURE OF |
| THE PERSON RESPONSIBLE FOR THE DESIGN. |
| |
| 2) THE WIND SPEED DESIGN IS NOT CONSISTENT WITH THE |
| ADOPTED MAP FBC 119, CITY AMENDMENTS. THE DEFAULT |
| WINDSPEED FOR THE CITY OF WEST PALM BEACH IS 170 MPH |
| VULT AND 132 VASD (NOMINAL). IF YOU WISH TO USE LINEAR |
| INTERPOLATION TO DETERMINE THE WIND SPEED BETWEEN THE |
| WIND SPEED CONTOUR LINES, SUBMIT TWO COPIES OF THE DATA |
| AND CALCULATIONS THAT WERE USED. THE REQUESTED |
| INFORMATION IS REQUIRED TO BEAR THE NAME AND SIGNATURE |
| OF THE PERSON RESPONSIBLE FOR IT. |
| |
| 3) THE INSTALLATION DRAWINGS FOR THE WINDOW PRODUCT |
| APPROVALS (NOA NO. 12-0127.16 & NOA NO. 12-0127.08) |
| REQUIRED BY DCA RULE 9N-3 ARE MISSING INFORMATION. WHEN |
| PRINTED THE DRAWINGS WERE NOT SHRUNK TO FIT ON THE 8.5 |
| X 11 INCH PAPER THAT WAS USED. FBC 107.2.1.4 |
| |
| 4) SUBMIT TWO COPIES OF PRODUCT APPROVALS FOR THE |
| STRUCTURAL WINDOW MULLIONS (LIVING ROOM WINDOWS) AND |
| THE SIMPSON COLUMN BASE AND CAP CONNECTORS AS REQUIRED |
| BY DCA RULE 9N-3 |
| |
| 5) THE PLANS SPECIFY A SIMPSON EPS 4Z COLUMN BASE FOR |
| THE 4 X 4 REPLACEMENT COLUMNS AT THE FRONT PORCH. THIS |
| CONNECTOR IS REQUIRED TO BE EMBEDDED INTO CONCRETE AND |
| THE PORCH SLAB IS EXISTING. PLEASE CLARIFY THE |
| INSTALLATION. FBC 107.2.1 |
| |
| 6) R319.1.4 WOOD COLUMNS. WOOD COLUMNS SHALL BE |
| APPROVED WOOD OF NATURAL DECAY RESISTANCE OR APPROVED |
| PRESSURE-PRESERVATIVE-TREATED WOOD. |
| |
| |
| |
| |