2014-08-29 11:06:38 | SENT TO ZONING FOR PHOTOMETRIC REVIEW |
2014-08-29 11:03:31 | DATE: 8/29/2014 |
| PROJECT: MIZNER LAKES, SITE LIGHTING |
| PERMIT#: 14081250 |
| CODE: 2008 EDITION OF THE NEC |
| 2010 EDITION OF THE FBC |
| 2010 WPB AMENDMENTS TO THE FBC, CHAPTER 1, |
| ADMINISTRATION, 2012 FBC SUPPLEMENTS. |
| |
| 1ST ELECTRICAL PLAN REVIEW |
| ACTION: DENIED |
| |
| 1) PROVIDE AND INDICATE ON THE PLANS, THE LOCATION OF |
| THE SOURCE OF POWER, CONDUIT ROUTING, BURIAL DEPTH, |
| CIRCUIT #'S, AND GROUNDING DETAIL. PROVIDE VOLTAGE DROP |
| CALCULATIONS AS NEEDED. IF THERE ARE MULIPLE SOURCES |
| INDICATE EACH ONE INDIVIDUALLY AND COMPLETE THE REST OF |
| THE DETAIL FROM EACH INDIVIDUAL SOURCE. |
| |
| 2) PROVIDE A PANEL SCHEDULE INDICATEING THE SYSTEM |
| VOLTAGE, THE SIZE OF THE MAIN OCPD, AIC RATING, AND |
| IDENTIFY EACH INDIVIDUAL CIRCUIT FOR THE LIGHTING ON |
| THE PLAN. |
| |
| 3) PROVIDE A LOAD CALCULATION INDICATING THE TOTAL |
| CONNECTED LOAD ON THE WHOLE PANEL INCLUDING THE |
| ADDITIONAL LOAD OF THE NEW SITE LIGHTING. IF THERE ARE |
| MULTIPLE PANELS COMPLETE FOR EACH PANEL. |
| |
| 4) PROVIDE AND INDICATE ON THE PLANS THE METHOD OF |
| LIGHTING CONTROL AS REQUIRED IN THE FBC SECTION 505.2.4 |
| AGAIN IF THERE ARE MULTIPLE SOURCES COMPLETE FOR EACH. |
| |
| WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| RE-SUBMITTAL FORM. SEE LINK: |
| HTTP://WPB.ORG/DEVELOPMENT |
| /WP-CONTENT/UPLOADS/SITES/33/2013/09/APPLICATION_RESUBM |
| ITTAL_FORM_04132010.PDF |
| |
| ADDITIONALLY, PLEASE INSERT CORRECTED PAGES INTO |
| SUBMITTAL PACKAGE AND LEAVE THE PREVIOUSLY REVIEWED |
| SHEETS FOR COMPARATIVE REVIEW. |
| |
| DAVID HAYES, ELECTRICAL PLANS EXAMINER, PX3421, |
| 561-805-6717 OR [email protected] |
| |
| |