Plan Review Notes
Plan Review Notes For Permit 14081250
Permit Number 14081250
Review Stop E
Sequence Number 1
Notes
Date Text
2014-08-29 11:06:38SENT TO ZONING FOR PHOTOMETRIC REVIEW
2014-08-29 11:03:31DATE: 8/29/2014
 PROJECT: MIZNER LAKES, SITE LIGHTING
 PERMIT#: 14081250
 CODE: 2008 EDITION OF THE NEC
 2010 EDITION OF THE FBC
 2010 WPB AMENDMENTS TO THE FBC, CHAPTER 1,
 ADMINISTRATION, 2012 FBC SUPPLEMENTS.
  
 1ST ELECTRICAL PLAN REVIEW
 ACTION: DENIED
  
 1) PROVIDE AND INDICATE ON THE PLANS, THE LOCATION OF
 THE SOURCE OF POWER, CONDUIT ROUTING, BURIAL DEPTH,
 CIRCUIT #'S, AND GROUNDING DETAIL. PROVIDE VOLTAGE DROP
 CALCULATIONS AS NEEDED. IF THERE ARE MULIPLE SOURCES
 INDICATE EACH ONE INDIVIDUALLY AND COMPLETE THE REST OF
 THE DETAIL FROM EACH INDIVIDUAL SOURCE.
  
 2) PROVIDE A PANEL SCHEDULE INDICATEING THE SYSTEM
 VOLTAGE, THE SIZE OF THE MAIN OCPD, AIC RATING, AND
 IDENTIFY EACH INDIVIDUAL CIRCUIT FOR THE LIGHTING ON
 THE PLAN.
  
 3) PROVIDE A LOAD CALCULATION INDICATING THE TOTAL
 CONNECTED LOAD ON THE WHOLE PANEL INCLUDING THE
 ADDITIONAL LOAD OF THE NEW SITE LIGHTING. IF THERE ARE
 MULTIPLE PANELS COMPLETE FOR EACH PANEL.
  
 4) PROVIDE AND INDICATE ON THE PLANS THE METHOD OF
 LIGHTING CONTROL AS REQUIRED IN THE FBC SECTION 505.2.4
 AGAIN IF THERE ARE MULTIPLE SOURCES COMPLETE FOR EACH.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. SEE LINK:
 HTTP://WPB.ORG/DEVELOPMENT
 /WP-CONTENT/UPLOADS/SITES/33/2013/09/APPLICATION_RESUBM
 ITTAL_FORM_04132010.PDF
  
 ADDITIONALLY, PLEASE INSERT CORRECTED PAGES INTO
 SUBMITTAL PACKAGE AND LEAVE THE PREVIOUSLY REVIEWED
 SHEETS FOR COMPARATIVE REVIEW.
  
 DAVID HAYES, ELECTRICAL PLANS EXAMINER, PX3421,
 561-805-6717 OR [email protected]
  
  